Plan Review Details - Permit 15110783
Plan Review Stops For Permit 15110783
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 12:43 Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By jwitmer Date 2015-12-15 Time 10:24 Rev Time  
Received By jwitmer Date 2015-12-15 Time 07:31 Sent To  
Notes
2015-12-15 10:24:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110783
 ADD: 2915 S. DIXIE HWY.
 CONT: SUPERIOR CONCRETE, INC.
 TEL: 561-329-3575
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. DEC. 15/2015
 ACTION: DENIED
  
 1A) SHEET 2 OF 6 INDICATES (2) NEW SILOS, AND SECONDARY
 CONTAINMENT WALLS. THE PLANS DO NOT INDICATE WHAT TYPE
 OF LIQIUDS ARE TO BE STORED IN THESE SILOS.
 PLEASE PROVIDE MSDS SHEETS FOR THE LIQUID TO BE STORED.
 THE UNKNOWN ELEMENT TO BE STORED IN THE TANKS, THIS
 CODE SECTION MAY OR MAY NOT BE APPLICABLE.
 2014 FBC-B 415.8 H2 OCCUPANCY.
 2014 FBC-B 415.2.2 TANK PROTECTION.
 2014 FBC-B 415.8.2.4 LEAKAGE CONTAINMENT. A
 LIQUID-TIGHT CONTAINMENT AREA COMPATIBLE WITH THE
 STORED LIQUID SHALL BE PROVIDED. THE METHOD OF SPILL
 CONTROL, DRAINAGE CONTROL AND SECONDARY CONTAINMENT
 SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE. EXCEPTION: ROOMS WHERE ONLY DOUBLE-WALL STORAGE
 TANKS CONFORMING TO SECTION 415.8.2.3 ARE USED TO STORE
 CLASS I, II AND IIIA FLAMMABLE AND COMBUSTIBLE LIQUIDS
 SHALL NOT BE REQUIRED TO HAVE A LEAKAGE CONTAINMENT
 AREA.
  
 1B) THE PLANS INDICATE THE INSTALATION OF 2 SILO TANKS
 WHERE AS THE PERMIT APPLICATION INDICATES 3 S. S. SILO
 TANKS? DISCREPANCY PLEASE PROVIDE ADDITIONAL
 INFORMATUION. 107.2.1.3.
  
 2) IF THE TERM SECONDARY CONTAINMENT IS A REQUIREMENT,
 SHEET 2 INDICATES 2 NEW OPENINGS BEING CUT IN THE WALL
 BETWEEN THE 2 NEW SILO TANKS, HOW WILL THE SECONDARY
 CONTAINMENT WORK WITH OPENINGS IN THE WALL. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 2 OF 6 INDICATES SILOS BY OTHERS. IT WOULD
 SEEM THE SILOS' WOULD BE A CRITICAL PART OF THIS
 PERMIT. WITHOUT THE KNOWLDGE OF WHAT IS TO BE
 CONTAINED, GALLONS OF LIQUID, TYPE OF LIQUID, WEIGHT OF
 LIQUID AND TANK, HOW CAN THE THICKNESS AND STRENGTH OF
 THE RE-INFORCED CONCRETE SLAB BE CALCULATED? HOW CAN
 THE ENGINEERING BE CALCULATED FOR THE MOMENT OF
 OVERTURNING? AT THIS TIME THERE ARE TO MANY UNKNOWNS TO
 BE ABLE TO DO A COMPLETE REVIEW ON THE SILO'S AND
 ADJACENT BUILDING. A THOROUGH REVIEW CANNOT BE MADE AT
 THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION
 REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT
 PART OF THIS REVIEW.
  
 4) SHEET S-4 SHOWS EXISITNG REFRIGARATED STORAGE AND
 NEW LOADING DOCK. DETAIL # 1 SHOWS A DEMO PLAN TO
 REMOVE SWING DOORS AND TO ENLARGE DOORS TO 84X90 INCHES
 OVERHEAD DOOR. PLEASE PROVIDE A EGRESS PLAN OF THE
 REFRIGARATED STORAGE AND NEW LOADING DOCK, THE CONCERN
 IS THE EGRESS REQUIREMENTS FOR THE REFRIGARATED STORAGE
 ROOM. PROVIDE SQUARE FOOTAGE OF UNIT, TRAVEL DISTANCES,
 IF FIRE SPRINKLERED OR NOT AND AMOUNT OF EGRESSES.
 2014 FBC-B 1015.5. ROOMS OR SPACES HAVING A FLOOR AREA
 LARGER THAN 1,000 SQUARE FEET (93 M2), CONTAINING A
 REFRIGERANT EVAPORATOR AND MAINTAINED AT A TEMPERATURE
 BELOW 68?F (20?C), SHALL HAVE ACCESS TO NOT LESS THAN
 TWO EXITS OR EXIT ACCESS DOORWAYS.
  
 TRAVEL DISTANCE SHALL BE DETERMINED AS SPECIFIED IN
 SECTION 1016.1, BUT ALL PORTIONS OF A REFRIGERATED ROOM
 OR SPACE SHALL BE WITHIN 150 FEET (45 720 MM) OF AN
 EXIT OR EXIT ACCESS DOORWAY WHERE SUCH ROOMS ARE NOT
 PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
 EGRESS IS ALLOWED THROUGH ADJOINING REFRIGERATED ROOMS
 OR SPACES.
  
 5) SHEET 4 OF 6 INDICATES A DETAIL A/ S-2 THERE IS NO
 SUCH DETAIL THROUGH THE NEW SLAB AND RETAINING WALL
 FOUND ON S-2. PLEASE PROVIDE A DETAIL FOR THE RETAING
 WALL, WITH ELEVATIONS TO SEE HOW MUCH FILL IS TO BE
 RETAINED AGAINST THIS WALL? THE NOTE ON THIS PAGE
 INDICATES THE WALL TO BE A STEM WALL NOT A RETAINING
 WALL, THE BLOCK WORK SHOWN IN DETAIL A/ 4 WITH FINISH
 CONCRETE SLAB IS 72 INCHES IN HEIGHT. 2014 FBC-B 1807.2
 RETAINING WALLS SHALL BE DESIGNED IN ACCORDANCE WITH
 SECTION 1807.2.1 THROUGH 1807.2.4.
  
 6) SHEET 5 OF 6 SHOWS A WALL SECTION OF THE NEW
 ADDITION. THE SIZE OF THE REBAR AND SPACING IS NOT
 PROVIDED, FOR THE WALL FROM FINISH FLOOR TO BEAM. WALL
 HEIGHT IS 15 FEET TALL WITH NO INTERMEDIATE BEAM. THE
 PLANS FAIL TO PROVIDE WHAT THE SIZE OF THE STEEL IS IN
 THE SINGLE COURSE OF BEAM BLOCK, NOR DOES THE PLANS
 INDICATE THE HORIZONTAL STEEL IN THE BEAMS ABOVE THE
 DOOR OPENINGS OR IF LINTELS WILL BE USED, AND AMOUNT OF
 STEEL OF IF A COMBINATION OF LINTELS AND BEAM BLOCK
 WITH HAIR PINS WOULD BE REQUIRED.
  
 7) SHEET 5 OF 6 DOES NOT PROVIDE A END DETAIL OF THE
 WALL IS THE BLOCK WORK TO CONTINUE UP THE RACK OF THE
 WALL, IS THERE A DROPPED BEAM AND CATELIVERED OVERHANG
 ON THE END WALLS ? PLANS ARE INSEFICIENT ENOUGH IN
 DETIALS FOR PLAN REVIEW. . A THOROUGH REVIEW CANNOT BE
 MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL
 INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR
 THAT WERE NOT PART OF THIS REVIEW.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-12 Cont ID  
Sent By mvaldes Date 2016-05-12 Time 15:55 Rev Time 0.00
Received By mvaldes Date 2016-05-12 Time 15:26 Sent To  
Notes
2016-05-12 16:07:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 PROVISO: CLARIFY THIS ISSUE ON THE RISER AND PANEL
 SCHEDULE
  
 - NEC 110.15 HIGH-LEG MARKING. ON A 4-WIRE,
 DELTA-CONNECTED SYSTEM WHERE THE MIDPOINT OF ONE PHASE
 WINDING IS GROUNDED, ONLY THE CONDUCTOR OR BUSBAR
 HAVING THE HIGHER PHASE VOLTAGE TO GROUND SHALL BE
 DURABLY AND PERMANENTLY MARKED BY AN OUTER FINISH THAT
 IS ORANGE IN COLOR OR BY OTHER
 EDITION EFFECTIVE MEANS. SUCH IDENTIFICATION SHALL BE
 PLACED AT EACH POINT ON THE SYSTEM WHERE A CONNECTION
 IS MADE IF THE GROUNDED CONDUCTOR IS ALSO PRESENT.
  
 - NEC 408.3(E)(F) PHASE ARRANGEMENT. THE PHASE
 ARRANGEMENT ON 3-PHASE BUSES SHALL BE A, B, C FROM
 FRONT TO BACK, TOP TO BOTTOM, OR LEFT TO RIGHT, AS
 VIEWED FROM THE FRONT OF THE SWITCHBOARD OR PANELBOARD.
 THE B PHASE SHALL BE THAT PHASE HAVING THE HIGHER
 VOLTAGE TO GROUND ON 3-PHASE, 4-WIRE, DELTA-CONNECTED
 SYSTEMS.
 OTHER BUSBAR ARRANGEMENTS SHALL BE PERMITTED FOR
 ADDITIONS TO EXISTING INSTALLATIONS AND SHALL BE
 MARKED. HIGH-LEG IDENTIFICATION. A SWITCHBOARD OR
 PANELBOARD CONTAINING A 4-WIRE, DELTA-CONNECTED SYSTEM
 WHERE THE MIDPOINT OF ONE PHASE WINDING IS GROUNDED
 SHALL BE LEGIBLY AND PERMANENTLY FIELD MARKED AS
 FOLLOWS:
 ?CAUTION _____ PHASE HAS _____ VOLTS TO GROUND?
  
 - RE-CONFIGURE RISER DIAGRAM AND PANEL SCHEDULE
 ACCORDINGLY TO IDENTIFY THIS HAZARD !

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 12:02 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 10:51 Sent To  
Notes
2016-04-05 12:02:33ELECTRICAL REVIEW COMMENTS
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011
 EDITION
  
 CORRECTIONS REQUIRED:
 1. ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED, BUT FBC SECTION 107.1
 REQUIRES THAT YOU SUBMIT A MINIMUM OF TWO SETS OF PLANS
 WITH EACH APPLICATION AND ONLY WAS WAS AVAILABLE AT
 TIME OF REVIEW. ONE SET WAS SIGNED OUT TO SUPERIOR
 CONCRETE ON 3/21/16. THIS FILE WILL REMAIN IN FAILED
 STATUS UNTIL SUCH TIME AS THE REQUIRED SECOND SET OF
 DRAWINGS IS PROVIDED.
 2. ELECTRICAL REVIEW LIMITED ONLY TO THE SILO PORTION
 OF PROJECT. NO ELECTRIC WAS PROVIDED FOR DUMPSTER AREA.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-21 Cont ID  
Sent By albarran Date 2015-12-21 Time 19:51 Rev Time 0.00
Received By albarran Date 2015-12-21 Time 18:44 Sent To  
Notes
2015-12-21 19:51:59THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. NEC 230.2 PERMIT A SINGLE SERVICE TO EACH STRUCTURE
 AND THE PROPOSED ADDITION APPEARS TO BE ATTACHED TO THE
 EXISTING STRUCTURE, THEREFORE THE ELECTRICAL RISER
 DIAGRAM AS PROVIDED IS INCORRECT.
 2. NEC 215.5 REQUIRES THAT YOU PROVIDE FEEDER DIAGRAM
 WITH PROPER LOAD CALCS FOR THE ADDED LOAD. THIS FEEDER
 DIAGRAM SHALL BE SITE SPECIFIC.
 3. NEC 408.4 MARK ON THE FLOOR PLAN THE LOCATION OF THE
 ELECTRICAL PANEL. MARK ON THE PANEL THE LOCATION OF THE
 DISCONNECT AND POWER SOURCE. HERE IS WHERE YOU SHALL
 ALSO PROVIDE A SITE SPECIFIC CIRCUIT DIRECTORY.
 4. FBC-E C405 HAS MANDATORY SWITCHING REQUIREMENTS FOR
 EVERY COMMERCIAL INSTALLATION.
 5. YOU SHALL ILLUMINATE THE EXTERIOR STAIRWAYS AS
 REQUIRED BY CODE.
 6. YOU SHALL PROVIDE THE REQUIRED EMERGENCY AND EXIT
 LIGHTING.
 7. INCLUDE ON THE PLANS ANY ILLUMINATION OR OTHERWISE
 REQUIRED OR BEING INSTALLED AS PART OF THE SILOS OR
 DUMPSTER ENCLOSURE.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-05-24 Cont ID  
Sent By Mgonzale Date 2016-05-24 Time   Rev Time 0.25
Received By mgonzale Date 2016-05-24 Time   Sent To Z
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By Mgonzale Date 2015-12-22 Time   Rev Time 1.00
Received By mgonzale Date 2015-12-22 Time   Sent To Z
Notes
2015-12-22 16:08:54I HAVE PLACED A "F" FOR THE REVIEW STATUS FOR THE
 SUBJECT PERMITS TO ALLOW THE CONTRACTOR TO REVISE THE
 PLANS ACCORDINGLY. MOST OF OUR COMMENTS ARE TYPICAL TO
 THOSE OF THE PLANNING AND ZONING; THEREFORE, ON THE
 NEXT REVISION WHEN PLANNING AND ZONING COMMENTS AND
 SITE PLAN ARE ADDRESSED AND PRESENTED ENG WILL
 RE-REVIEW.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/WP-CONTENT/UPLOADS/2015/12/CROSS-CONNECT
 ION-MANUAL.PDF
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-04-19 Cont ID  
Sent By rlindow Date 2016-06-07 Time 17:10 Rev Time 0.00
Received By rlindow Date 2016-04-19 Time   Sent To  
Notes
2016-06-07 13:46:09PROVISO:
  
 ALL OF THE BELOW PREVIOUS COMMENTS STILL STAND.
 SEE BELOW.
  
 -AS PREVIOUSLY NOTED.
  
 PER FFPC, FIFTH EDITION
  
 CHAPTER 40 INDUSTRIAL OCCUPANCIES
  
 40.1 GENERAL REQUIREMENTS.
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH
 NEW AND EXISTING INDUSTRIAL OCCUPANCIES.
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 40.2.5
  
 THE FOLLOWING AREAS LISTED EXCEED MAXIMUM ALLOWABLE
 COMMON PATH OF TRAVLEL.
 - PACKAGING WAREHOUSE ON FLOOR 2
 - REFRIGERATED STORAGE.
 - MIX ROOM.
 - SOUTH COMP ROOM.
 - OFFICE SPACE
  
 I AM THE FIRE INSPECTOR THAT INSPECTED THIS PROPERTY.
 OUR OFFICE IS CURRENTLY WORKING WITH
 THE OWNER'S OF THE BUSINESS. THE CODE REFERENCE BEING
 USED IS APPLIED BY THE PORTIONS
 OF THE MEANS OF EGRESS AS UNSPRINKLERED AS SHOWN IN THE
 TABLE OF THE REFERENCE PROVIDED TO
 YOU PREVIOUSLY. THE OWNER'S ARE WORKING ON WHAT WAS
 AGREED UPON, ONE OF
 WHICH WAS TO HAVE A THIRD PARTY RDP EVALUATE THEIR
 FACILITYTO ENSURE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND PROVIDE LIFE SAFEY
 DRAWINGS. THIS IS A SEPARATE ISSUE.
 R. LINDOW 4/19/2016
  
  
2016-04-19 17:10:06AS PREVIOUSLY NOTED.
  
 PER FFPC, FIFTH EDITION
  
 CHAPTER 40 INDUSTRIAL OCCUPANCIES
  
 40.1 GENERAL REQUIREMENTS.
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH
 NEW AND EXISTING INDUSTRIAL OCCUPANCIES.
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 40.2.5
  
 THE FOLLOWING AREAS LISTED EXCEED MAXIMUM ALLOWABLE
 COMMON PATH OF TRAVLEL.
 - PACKAGING WAREHOUSE ON FLOOR 2
 - REFRIGERATED STORAGE.
 - MIX ROOM.
 - SOUTH COMP ROOM.
 - OFFICE SPACE
  
 I AM THE FIRE INSPECTOR THAT INSPECTED THIS PROPERTY.
 OUR OFFICE IS CURRENTLY WORKING WITH
 THE OWNER'S OF THE BUSINESS. THE CODE REFERENCE BEING
 USED IS APPLIED BY THE PORTIONS
 OF THE MEANS OF EGRESS AS UNSPRINKLERED AS SHOWN IN THE
 TABLE OF THE REFERENCE PROVIDED TO
 YOU PREVIOUSLY. THE OWNER'S ARE WORKING ON WHAT WAS
 AGREED UPON, ONE OF
 WHICH WAS TO HAVE A THIRD PARTY RDP EVALUATE THEIR
 FACILITYTO ENSURE COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND PROVIDE LIFE SAFEY
 DRAWINGS. THIS IS A SEPARATE ISSUE.
 R. LINDOW 4/19/2016
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-02-25 Cont ID  
Sent By rlindow Date 2016-02-25 Time   Rev Time 0.00
Received By rlindow Date 2016-02-25 Time   Sent To  
Notes
2016-02-25 17:10:49 
 LIFE SAFETY PLAN PROVIDED DOES NOT INCLUDE ENTIRE
 BUILDING. PROVIDE COMPLETE LIFE SAFETY PLAN.
 COMMON PATH OF TRAVEL EXCEEDED.
  
 PER FFPC, FIFTH EDITION
  
 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS,
 ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT
 EXCEED THAT
 PROVIDED BY TABLE 40.2.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By rlindow Date 2015-12-03 Time   Rev Time 0.00
Received By rlindow Date 2015-12-03 Time   Sent To  
Notes
2015-12-03 09:24:34PROVIDE OVERALL LIFE SAFETY PLAN FOR BUILDING.
 EXITS APPEAR TO BE COMPROMISED BY NEW CONSTRUCTION
 ADDITIONS,
 LINDOW 12/03/2015

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-07 Cont ID  
Sent By skennedy Date 2016-06-07 Time 17:12 Rev Time 0.00
Received By skennedy Date 2016-04-08 Time 14:02 Sent To  
Notes
2016-04-08 14:02:38C14

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-08 Cont ID  
Sent By cpuell Date 2016-04-08 Time 14:00 Rev Time 0.00
Received By cpuell Date 2016-02-17 Time 09:50 Sent To  
Notes
2016-02-18 09:50:54C01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-23 Cont ID  
Sent By cpuell Date 2015-12-23 Time 11:53 Rev Time 0.00
Received By cpuell Date 2015-11-18 Time 14:59 Sent To  
Notes
2015-11-18 14:59:39C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-06-07 Cont ID  
Sent By skennedy Date 2016-06-07 Time 17:12 Rev Time 0.00
Received By skennedy Date 2016-06-07 Time 17:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-03-11 Cont ID  
Sent By jwitmer Date 2016-03-11 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2016-03-11 Time   Sent To  
Notes
2016-03-11 07:51:42BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By jwitmer Date 2015-12-15 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2015-12-15 Time 10:25 Sent To  
Notes
2015-12-15 10:26:01BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 09:57 Rev Time 0.00
Received By ccole Date 2016-03-07 Time 09:57 Sent To  
Notes
2016-03-10 09:58:29SEPARATE PERMIT REQUIRED FOR HVAC/REFRIGERATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By ccole Date 2015-12-16 Time 09:05 Rev Time 0.00
Received By ccole Date 2015-12-16 Time 09:05 Sent To  
Notes
2015-12-16 09:16:281ST REVIEW 2014 MECHANICAL
 PERMIT 15110783
 12/16/15
  
 1) PLEASE IDENTIFY THE TYPE OF LIQUID BEING STORED IN
 THE SILOS, AND CLARIFY WHY SECONDARY CONTAINMENT IS
 BEING PROVIDED.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE TANKS
 WITH REVIEW BY THE ENGINEER OF RECORD.
 3) CLARIFY HOW THE LIGUID WILL BE FILLED INTO, AND ALSO
 DISPENSED FROM THE TANKS.
 4) THE TANKS ARE SHOWN IN AN OPEN STRUCTURE: PROVIDE
 WINDLOAD ENGINEERING FOR ANCHORAGE OF THE TANKS TO THE
 STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-04-28 Cont ID  
Sent By dkittred Date 2016-04-28 Time 13:38 Rev Time 0.00
Received By dkittred Date 2016-04-25 Time 12:09 Sent To  
Notes
2016-04-28 13:55:25PLANNING AND ZONING COMMENTS:
  
 4/28/16
  
 APPROVED WITH THE FOLLOWING CONDITIONS:
  
 1. THE ADDITION OF THE SILOS WAS GRANTED WITH A CLASS B
 SPECIAL USE PERMIT (ZBA 3321) AND THE FOLLOWING
 CONDITIONS ARE APPLICABLE TO THIS PROJECT: AND A HOLD
 WILL BE PLACED ON THE FINAL INSPECTION UNTIL THESE
 ITEMS HAVE BEEN COMPLETED:
  
 PRIOR TO THE FINAL INSPECTION OF THE TWO SILOS:
 I. THE SILOS SHALL BE PAINTED TO MATCH THE BUILDING
 PAINT COLOR.
 II. REPAINT THE ENTIRE COMPLEX IN A COLOR PALETTE
 CONSISTING OF MORE THAN ONE COLOR AND AESTHETICALLY
 COMPLEMENTARY TO THE SOUTH DIXIE HIGHWAY CORRIDOR.
 III. INSTALL LANDSCAPING AND SITE IMPROVEMENTS IN
 ACCORDANCE WITH THE PLANS ATTACHED TO THE AUGUST 6,
 2015 ZBA STAFF REPORT WITH A MODIFICATION TO INCLUDE A
 TERMINAL LANDSCAPE ISLAND ON THE NORTH SIDE OF THE
 PROPOSED NEW PARKING. (PROPERTY PERMITS MUST BE
 OBTAINED FOR THE INSTALLATION OF THE LANDSCAPING AND
 SITE IMPROVEMENTS.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-04 Cont ID  
Sent By dkittred Date 2016-03-04 Time 14:52 Rev Time 0.00
Received By dkittred Date 2016-03-01 Time 08:42 Sent To  
Notes
2016-03-04 14:52:51PLANNING AND ZONING COMMENTS ***FAILED***
  
 3/4/16
  
 1. TWO COPIES OF THE SURVEY WERE NOT INCLUDED IN THE
 RESUBMITTAL AS STATED.
  
 2. ROLLING GATE IS PART OF THE DUMPSTER ENCLOSURE AND
 MUST MEET 5 FOOT MINIMUM SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-08 Cont ID  
Sent By dkittred Date 2015-12-08 Time 14:08 Rev Time 0.00
Received By dkittred Date 2015-12-07 Time 10:38 Sent To  
Notes
2015-12-08 14:22:01PLANNING AND ZONING COMMENTS: ***FAILED***
  
 12/8/15
  
 1. PLEASE REVISE GATE FOR DUMPSTER TO INDICATE THAT IT
 WILL BE OF AN OPAQUE MATERIAL TO SCREEN THE DUMPSTERS.
 PLEASE NOTE THAT ADDING SLATS TO THE PROPOSED
 CHAIN-LINK FENCE WILL NOT BE SUFFICENT.
  
 2. INCLUDE TWO COPIES OF THE SURVEY WITH THE
 APPLICATION.
  
 GENERAL COMMENTS:
  
 3. THE ADDITION OF THE SILOS WAS GRANTED WITH A CLASS B
 SPECIAL USE PERMIT (ZBA 3321) AND THE FOLLOWING
 CONDITIONS ARE APPLICABLE TO THIS PROJECT: AND A HOLD
 WILL BE PLACED ON THE FINAL INSPECTION UNTIL THESE
 ITEMS HAVE BEEN COMPLETED:
  
 PRIOR TO THE FINAL INSPECTION OF THE TWO SILOS:
 I. THE SILOS SHALL BE PAINTED TO MATCH THE BUILDING
 PAINT COLOR.
 II. REPAINT THE ENTIRE COMPLEX IN A COLOR PALETTE
 CONSISTING OF MORE THAN ONE COLOR AND AESTHETICALLY
 COMPLEMENTARY TO THE SOUTH DIXIE HIGHWAY CORRIDOR.
 III. INSTALL LANDSCAPING AND SITE IMPROVEMENTS IN
 ACCORDANCE WITH THE PLANS ATTACHED TO THE AUGUST 6,
 2015 ZBA STAFF REPORT WITH A MODIFICATION TO INCLUDE A
 TERMINAL LANDSCAPE ISLAND ON THE NORTH SIDE OF THE
 PROPOSED NEW PARKING. (PROPERTY PERMITS MUST BE
 OBTAINED FOR THE INSTALLATION OF THE LANDSCAPING AND
 SITE IMPROVEMENTS.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  