Plan Review Details - Permit 15110777
Plan Review Stops For Permit 15110777
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-04-07 Time 18:06 Rev Time 0.00
Received By jgomez Date 2016-04-07 Time 18:06 Sent To  
Notes
2016-04-07 18:12:06BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL FOR: (A) HURRICANE SHUTTERS
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE. (B)
 PRECAST LINTELS. (C) GABLE END VENT. (D) ALL SIMPSON
 AND USP STRUCTURAL CONNECTORS SPECIFIED. (E) EXTERIOR
 SWING DOOR BY THE REAR DECK .
 2- ARCHITECT OF RECORD TO APPROVE ALL PRODUCT
 APPROVALS.
 3- REVISE ENERGY CALCULATIONS: (A) COMPLETE INFORMATION
 ON TOP OF FORM, INCLUDING BUILDER NAME, PERMIT OFFICE
 AND JURISDICTION #. (B) REVISE THE DESIGN LOCATION. (C)
 REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED
 FOR THE ENTRY DOOR DOESN'T MATCH PLANS. NOTE: DOORS
 WITH GLAZING NEED TO BE CONSIDERED ON THE GLAZING
 CALCULATIONS NO DOORS. (D) REVISE WINDOWS OVERHANG
 DEPTH AND SEPARATION TO MATCH PLANS. (E) BUILDER TO
 COMPLETE THE ENERGY PERFORMANCE LEVEL (EPL) DISPLAY
 CARD.
 4- REVISE DETAIL 4 ON SHEET A3 TO COMPLY WITH TABLE
 R302.1. (1) OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 5- ENTRY DOOR ON FLOOR PLAN ON SHEET A1 WAS REVISED.
 REVISE FRONT ELEVATION TO MATCH CHANGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-08 Cont ID  
Sent By jgomez Date 2016-03-08 Time 13:27 Rev Time 0.00
Received By jgomez Date 2016-03-08 Time 13:27 Sent To  
Notes
2016-03-08 13:28:47E-MAIL RECEIVED ON 03/08/16:
 JULIO:
 GOOD MORNING, THANK YOU VERY MUCH FOR YOUR TIME LAST
 WEEK.
 REGARDING PERMIT # 15110777, WE DECIDED TO GO PROVISO.
 HOW CAN WE PROCEED WITH IT.
 THANK YOU IN ADVANCE.
  
 CLAUDIA MENDOZA
 I.Q. CONSTRUCTIONS, INC
 CERTIFIED GENERAL CONTRACTOR 1505446
 SBE & M/WBE CERTIFIED
 140 VIA D ESTE (802)
 DELRAY BEACH FL 33445
 561 847 0694
 561 330 4986 FAX
 *******************************************************
 *******************************************************
 *******************************************************
 ***
  
 NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE
 ENGINEERING COMMENTS ARE ADDRESSED. THE ENGINEERING
 COMMENTS NEED TO BE ADDRESSED FIRST BECAUSE THEY AFFECT
 THE EARLY DEVELOPMENT OF THIS PROJECT.
  
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT THE REQUESTED ITEMS AFTER
 THE PERMIT IS ISSUED. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS OK OR IF
 RE-SUBMITTING REQUESTED ITEMS BEFORE ISSUING THE
 PERMIT.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T
 HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR
 PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT
 CONTAINS ALL THE REQUIRED INFORMATION.
 NOTE: IS NOT CLEAR IF USING IMPACT WINDOWS AND DOORS OR
 NON-IMPACT WINDOWS AND DOORS. PRODUCT APPROVALS
 SUBMITTED NOW ARE FOR IMPACT WINDOWS AND DOORS. IMPACT
 WINDOWS AND DOORS SUBMITTED NOW ARE VINYL. THEY MAY NOT
 BE APPROVED BY HISTORIC. ON THE OTHER HAND ARCHITECT
 SPECIFIES SHUTTERS FOR HURRICANE PROTECTION ON SHEET
 A1. PLEASE COORDINATE ALL THE INFORMATION TO AVOID MORE
 CONFUSION AND CONFLICTS.
  
 B) CLARIFY IF USING THE NON-IMPACT SINGLE HUNG WINDOWS
 NOA 15-0528.22 SUBMITTED THE FIRST TIME OR IF ANOTHER
 PRODUCT WILL BE USED. THERE WERE ANOTHER PRODUCT
 APPROVALS SUBMITTED FOR SLIDING GLASS DOORS AND FIXED
 WINDOWS WITH IMPACT GLASS. NOTE: VINYL DOORS AND
 WINDOWS MAY NOT BE APPROVED BY HISTORIC.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS (REPEAT
 COMMENT).
  
 D) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON
 SHEET A2 (REPEAT COMMENT).
  
 E) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE
 CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO
 THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION. (REPEAT
 COMMENT).
  
 F) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON
 PLANS (REPEAT COMMENT).
  
 G) SLIDING GLASS DOOR AS SHOWN ON PLANS. VINYL DOORS
 NOA 15-0409.02 NEEDS HISTORIC APPROVAL.
  
 H) FIXED WINDOWS. VINYL WINDOWS NOA 15-0415.01
 SUBMITTED NEEDS HISTORIC APPROVAL.
  
 I) METAL ROOF NOA 11-0810.10 SUBMITTED. CLEARLY
 IDENTIFY WHICH APPROVED SYSTEM IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
  
 2- ARCHITECT OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 B) REVISE THE DESIGN LOCATION SHOWN ON PAGE 2 OF 4.
 THIS IS WEST PALM BEACH NOT BELLE GLADE.
  
 C) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED
 FOR THE ENTRY DOOR DOESN'T MATCH PLANS.
 NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE
 GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED
 TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 D) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). (REPEAT COMMENT).
  
 E) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE
 ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO
 COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS
 REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH
 SIDE.
 NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE
 ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE
 RATING.
  
 RESPONSE: DETAIL 4 ON SHEET A3 DOESN'T COMPLY. NEED 1
 HOUR FIRE RESISTANCE ON THE UNDERSIDE OF THE
 PROJECTION. DETAIL SUBMITTED IS FOR A SHAFTWALL. THIS
 DOESN'T APPLY TO THE UNDERSIDE OF THE PROJECTION.
 PROVIDE COMPLETE SPECIFICATIONS FOR FIRE RATED ASSEMBLY
 THAT INCLUDES THE OUTRIGGERS AS SHOWN ON DETAIL 4/A3.
  
 5- SHEET A1: ARCHITECT CALLS FOR SHUTTERS FOR HURRICANE
 PROTECTION. PRODUCT APPROVALS SUBMITTED ARE IMPACT
 GLASS. PLEASE COORDINATE PLANS AND PRODUCT APPROVALS TO
 AVOID MORE CONFLICTS AND DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- ENTRY DOOR ON FLOOR PLAN ON SHEET A1 WAS REVISED.
 REVISE FRONT ELEVATION TO MATCH CHANGES. SEC. 107.2.1
 CITY AMENDMENTS.
  
 7- ARCHITECT TO SPECIFY METAL ROOF FASTENING AS
 REQUIRED BY SEC. 107.2.1.2. SEE NOA 11-0810.10
 SUBMITTED. COORDINATE WITH ITEM #1(I) ABOVE.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-16 Cont ID  
Sent By jgomez Date 2016-02-12 Time 16:47 Rev Time 0.00
Received By jgomez Date 2016-02-12 Time 16:47 Sent To  
Notes
2016-02-12 16:49:45NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT THE REQUESTED ITEMS AFTER
 THE PERMIT IS ISSUED. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS OK OR IF
 RE-SUBMITTING REQUESTED ITEMS BEFORE ISSUING THE
 PERMIT.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T
 HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR
 PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT
 CONTAINS ALL THE REQUIRED INFORMATION.
 NOTE: IS NOT CLEAR IF USING IMPACT WINDOWS AND DOORS OR
 NON-IMPACT WINDOWS AND DOORS. PRODUCT APPROVALS
 SUBMITTED NOW ARE FOR IMPACT WINDOWS AND DOORS. IMPACT
 WINDOWS AND DOORS SUBMITTED NOW ARE VINYL. THEY MAY NOT
 BE APPROVED BY HISTORIC. ON THE OTHER HAND ARCHITECT
 SPECIFIES SHUTTERS FOR HURRICANE PROTECTION ON SHEET
 A1. PLEASE COORDINATE ALL THE INFORMATION TO AVOID MORE
 CONFUSION AND CONFLICTS.
  
 B) CLARIFY IF USING THE NON-IMPACT SINGLE HUNG WINDOWS
 NOA 15-0528.22 SUBMITTED THE FIRST TIME OR IF ANOTHER
 PRODUCT WILL BE USED. THERE WERE ANOTHER PRODUCT
 APPROVALS SUBMITTED FOR SLIDING GLASS DOORS AND FIXED
 WINDOWS WITH IMPACT GLASS. NOTE: VINYL DOORS AND
 WINDOWS MAY NOT BE APPROVED BY HISTORIC.
  
 C) PRECAST LINTELS AS SPECIFIED ON PLANS (REPEAT
 COMMENT).
  
 D) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON
 SHEET A2 (REPEAT COMMENT).
  
 E) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE
 CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO
 THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION. (REPEAT
 COMMENT).
  
 F) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON
 PLANS (REPEAT COMMENT).
  
 G) SLIDING GLASS DOOR AS SHOWN ON PLANS. VINYL DOORS
 NOA 15-0409.02 NEEDS HISTORIC APPROVAL.
  
 H) FIXED WINDOWS. VINYL WINDOWS NOA 15-0415.01
 SUBMITTED NEEDS HISTORIC APPROVAL.
  
 I) METAL ROOF NOA 11-0810.10 SUBMITTED. CLEARLY
 IDENTIFY WHICH APPROVED SYSTEM IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
  
 2- ARCHITECT OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 B) REVISE THE DESIGN LOCATION SHOWN ON PAGE 2 OF 4.
 THIS IS WEST PALM BEACH NOT BELLE GLADE.
  
 C) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED
 FOR THE ENTRY DOOR DOESN'T MATCH PLANS.
 NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE
 GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED
 TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 D) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). (REPEAT COMMENT).
  
 E) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE
 ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO
 COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS
 REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH
 SIDE.
 NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE
 ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE
 RATING.
  
 RESPONSE: DETAIL 4 ON SHEET A3 DOESN'T COMPLY. NEED 1
 HOUR FIRE RESISTANCE ON THE UNDERSIDE OF THE
 PROJECTION. DETAIL SUBMITTED IS FOR A SHAFTWALL. THIS
 DOESN'T APPLY TO THE UNDERSIDE OF THE PROJECTION.
 PROVIDE COMPLETE SPECIFICATIONS FOR FIRE RATED ASSEMBLY
 THAT INCLUDES THE OUTRIGGERS AS SHOWN ON DETAIL 4/A3.
  
 5- SHEET A1: ARCHITECT CALLS FOR SHUTTERS FOR HURRICANE
 PROTECTION. PRODUCT APPROVALS SUBMITTED ARE IMPACT
 GLASS. PLEASE COORDINATE PLANS AND PRODUCT APPROVALS TO
 AVOID MORE CONFLICTS AND DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- ENTRY DOOR ON FLOOR PLAN ON SHEET A1 WAS REVISED.
 REVISE FRONT ELEVATION TO MATCH CHANGES. SEC. 107.2.1
 CITY AMENDMENTS.
  
 7- ARCHITECT TO SPECIFY METAL ROOF FASTENING AS
 REQUIRED BY SEC. 107.2.1.2. SEE NOA 11-0810.10
 SUBMITTED. COORDINATE WITH ITEM #1(I) ABOVE.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By jgomez Date 2015-12-23 Time 14:03 Rev Time 0.00
Received By jgomez Date 2015-12-23 Time 13:52 Sent To  
Notes
2015-12-23 14:05:01NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE SPECIFICATIONS FOR THE INTERIOR GARAGE DOOR
 LEADING FROM THE GARAGE TO THE MAIN HOUSE TO SHOW
 COMPLIANCE WITH SEC. R302.5.1 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: DOOR NEEDS TO BE SELF-CLOSING ALSO.
  
 3- SPECIFY SAFETY GLASS FOR WINDOW IN BEDROOM #2,
 MASTER BEDROOM AND WINDOW ADJACENT TO THE DOOR IN THE
 REAR DECK. SEC. R308.4.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 NOTE: WATER CAN NOT BE DIVERTED TO THE NEIGHBOR'S.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 ALSO, OPENINGS TO COMPLY WITH SEC. R312.13 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE OPENING
 SIZE SPECIFIED ON STAIR DETAIL #5 ON SHEET A3. THE CODE
 REQUIRES A DIMENSION THAT DOESN'T ALLOW A 4" SPHERE TO
 PAS THRU. 4" SPACING BETWEEN PICKETS WILL ALLOW A 4"
 SPHERE TO PASS THRU. REVISE AS REQUIRED.
  
 6- SPECIFY CARBON MONOXIDE ALARM WITHIN THE BEDROOMS AS
 REQUIRED BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 7- PROVIDE 2 COPIES OF THE GEOTECHNICAL EXPLORATION
 ENGINEERING REPORT. ONLY ONE WAS SUBMITTED. SEC. 107.1
 CITY AMENDMENTS.
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) HURRICANE SHUTTERS FOR DOORS AND WINDOWS THAT DON'T
 HAVE IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE INSTALLATION SCHEDULE CITY SAMPLE. OR
 PROVIDE COMPLETE INFORMATION ON ANY OTHER FORMAT THAT
 CONTAINS ALL THE REQUIRED INFORMATION.
  
 B) ENTRY DOOR WITH SIDELITE AS SHOWN ON PLANS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 IDENTIFY MULLION SIZE TO VERIFY THE DESIGN PRESSURES.
  
 D) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 E) GABLE END VENT AS SPECIFIED ON WEST ELEVATION ON
 SHEET A2.
  
 F) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 NOTE: SOME FLORIDA PRODUCT APPROVALS LISTED ON THE
 CONNECTOR SCHEDULE ON SHEET S2 NEED TO BE UPDATED TO
 THE 2014 FLORIDA PRODUCT APPROVAL CODE VERSION.
  
 G) METAL ROOFING AS SPECIFIED ON PLANS.
  
 H) EXTERIOR SWING DOOR BY THE REAR DECK AS SHOWN ON
 PLANS.
  
 I) SLIDING GLASS DOOR AS SHOWN ON PLANS.
  
 9- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- ENERGY CALCULATIONS SUBMITTED;
 A) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER NAME, PERMIT OFFICE AND JURISDICTION #. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) OWNER OR AGENT NEED TO CERTIFY COMPLIANCE AT THE
 BOTTOM OF THE FORM. SEC. R103.1.1.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 NOTE: WRITING THE NAME OF THE OWNER AT THE BOTTOM OF
 THE FORM DOESN'T SATISFY THE REQUIREMENT.. OWNER OR
 AGENT NEED TO PHYSICALLY CERTIFY COMPLIANCE AT THE
 BOTTOM OF THE FORM.
  
 C) WALL TYPES ITEM #9 IS MISSING THE ADJACENT WALL
 SEPARATING THE GARAGE FROM THE MAIN HOUSE. INSULATION
 REQUIRED. SEC. R103.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 D) REVISE THE CLIMATE ZONE. SEE TABLE R301.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) REVISE DOORS SPECIFIED ON PAGE 3 OF 5. NEED TO MATCH
 PLANS AND PRODUCT APPROVALS SUBMITTED. SIZE SPECIFIED
 FOR THE ENTRY DOOR DOESN'T MATCH PLANS.
 NOTE: DOORS WITH GLAZING NEED TO BE CONSIDERED ON THE
 GLAZING CALCULATIONS NO DOORS. SLIDING GLASS DOORS NEED
 TO BE CONSIDERED IN WINDOWS SECTION. SEE SEC.
 R405.5.3.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014)
  
 F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014)
  
 G) TABLE 402.4.1.1 SUBMITTED IS INCOMPLETE. THERE ARE
 ITEMS THAT NEED TO BE CHECKED. SEC. R103.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014)
  
 H) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 11- CLEARLY SPECIFY ALL DESIGN LOADS INCLUDING THE
 ATTIC LIVE LOADS AS REQUIRED BY FOOTNOTES "B" AND "G"
 OF TABLE R301.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 12- THE ROOF PROJECTION ON THE SOUTH SIDE NEEDS TO
 COMPLY WITH THE 1 HOUR ON THE UNDERSIDE FIRE RATING AS
 REQUIRED BY TABLE R302.1. (1) OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR THE ROOF PROJECTION ON THE SOUTH
 SIDE.
 NOTE: KEEP IN MIND THAT VENTS ON THE UNDERSIDE OF THE
 ROOF PROJECTIONS DON'T COMPLY WITH THE 1 HR FIRE
 RATING.
  
 13- SHEET A1: ARCHITECT CALLS FOR WINDOWS AND DOORS
 IMPACT GLASS FOR HURRICANE PROTECTION. PRODUCT
 APPROVALS SUBMITTED ARE NOT IMPACT GLASS. PLANS AND
 PRODUCT APPROVALS TO MATCH. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By mvaldes Date 2016-02-11 Time 17:43 Rev Time 0.00
Received By mvaldes Date 2016-02-11 Time 17:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By mvaldes Date 2016-01-04 Time 11:37 Rev Time 0.00
Received By mvaldes Date 2016-01-04 Time 11:37 Sent To  
Notes
2016-01-04 11:46:051ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM. PLEASE SHOW ON FLOOR PLANS.
 R404.1 LIGHTING EQUIPMENT (MANDATORY). MUST BE IC RATED
 AND SEALED TYPE RECCESSED FIXTURES.
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
 SHOW NEC 2011 ON STANDARDS INSTEAD OF 2008 . BOXES AT
 CEILING-SUSPENDED (PADDLE) FAN OUTLETS.
 OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT
 OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED,
 SHALL BE
 MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS
 PURPOSE,
 AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT
 WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR
 OUTLET BOX
 SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE)
 FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL
 INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED. NEC 314.28
 C

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By Mgonzale Date 2016-04-07 Time   Rev Time 0.50
Received By mgonzale Date 2016-04-07 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By cranford Date 2016-03-08 Time 14:03 Rev Time 0.00
Received By cranford Date 2016-03-08 Time 14:03 Sent To  
Notes
2016-03-08 14:08:42PLEASE REVISE THE DESIGN TO INCORPORATE APPROPRIATE
 MEASURES TO ENSURE THAT THE STORMWATER DESIGN WILL NOT
 ADVERSELY AFFECT NEIGHBORING PROPERTIES OR THE PUBLIC
 STORM DRAINAGE SYSTEM.
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
2016-02-12 18:07:51PLEASE REVIEW PROPOSED DRAINAGE PLAN DRAWING C-1.
 DESIGNED BY DKK CONSULTING INCORPORATED.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By fmittner Date 2016-03-07 Time 16:32 Rev Time 0.00
Received By fmittner Date 2016-03-07 Time 16:32 Sent To  
Notes
2016-02-12 16:42:44NEW PLANS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-12-03 Cont ID  
Sent By fmittner Date 2015-12-03 Time 14:49 Rev Time 0.00
Received By fmittner Date 2015-12-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-04-08 Time 11:22 Rev Time 0.00
Received By jgomez Date 2016-03-15 Time 10:22 Sent To  
Notes
2016-03-16 10:23:08IMPACT FEES ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-08 Cont ID  
Sent By jgomez Date 2016-03-08 Time 14:20 Rev Time 0.00
Received By jgomez Date 2016-02-11 Time 17:42 Sent To  
Notes
2016-02-05 09:28:53R20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-04 Cont ID  
Sent By cpuell Date 2016-01-04 Time 13:27 Rev Time 0.00
Received By cpuell Date 2015-11-18 Time 13:53 Sent To  
Notes
2015-11-18 13:53:47R20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-04-07 Cont ID  
Sent By jgomez Date 2016-04-07 Time 18:12 Rev Time 0.00
Received By jgomez Date 2016-04-07 Time 18:12 Sent To  
Notes
2016-04-07 18:14:05NO FEES DUE. SEE COUNTY STAMPED PLANS. MU-2016-5946.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-02-12 Cont ID  
Sent By jgomez Date 2016-02-12 Time 18:52 Rev Time 0.00
Received By jgomez Date 2016-02-12 Time 18:52 Sent To  
Notes
2016-02-12 18:54:591- PLANS NEED THE STAMP FROM PALM BEACH COUNTY FOR
 IMPACT IMPACT FEES. NOTE: IMPACT FEES MU NUMBER SHOWN
 ON THE PLANS TO MATCH MU NUMBER ON RECEIPT SUBMITTED.
 COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED LAND
 DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By jgomez Date 2015-12-23 Time 14:01 Rev Time 0.00
Received By jgomez Date 2015-12-23 Time 14:01 Sent To  
Notes
2015-12-23 14:03:291-BRING PLANS TO PALM BEACH COUNTY (2300 N. JG RD.) FOR
 IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-04-08 Time 10:57 Rev Time 0.00
Received By jgomez Date 2016-04-08 Time 10:57 Sent To  
Notes
2016-04-08 11:07:21PROVIDE COMPLETE INFORMATION FOR REVIEW UNDER A
 SEPARATE PERMIT:
  
 1- PROVIDE PLANS AND COMPLETE EQUIPMENT SIZING
 CALCULATIONS THAT ARE DONE WITH AN APPROVED HEATING AND
 COOLING CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1
 OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-16 Cont ID  
Sent By jgomez Date 2016-02-16 Time 12:48 Rev Time 0.00
Received By jgomez Date 2016-02-16 Time 12:48 Sent To  
Notes
2016-02-16 12:49:01NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT THE REQUESTED ITEMS AFTER
 THE PERMIT IS ISSUED. REVISION FEES MAY APPLY.
 CONTRACTOR TO ADVICE IF PROVISO OPTION IS OK OR IF
 RE-SUBMITTING REQUESTED ITEMS BEFORE ISSUING THE
 PERMIT.
  
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT
 ARE DONE WITH AN APPROVED HEATING AND COOLING
 CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 INFORMATION SUBMITTED IS NOT AN APPROVED METHOD.
 (REPEAT COMMENT).
  
 2- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T
 MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY
 AMENDMENTS. (REPEAT COMMENT).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By jgomez Date 2015-12-28 Time 14:00 Rev Time 0.00
Received By jgomez Date 2015-12-28 Time 07:53 Sent To E
Notes
2015-12-28 14:27:58NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS THAT
 ARE DONE WITH AN APPROVED HEATING AND COOLING
 CALCULATION METHOD AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 INFORMATION SUBMITTED IS NOT AN APPROVED METHOD.
  
 2- A/C DRAWING TO HAVE THE EQUIPMENT MANUFACTURER'S
 NAME AND MODEL NUMBER SHOWING THE SENSIBLE AND AND
 TOTAL COOLING CAPACITY AS REQUIRED BY SEC. R403.6.1 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 3- A/C PLANS SHOWING ON SHEET M.1 DOESN'T COMPLY WITH
 THE BALANCED RETURN AIR SEC. M1602.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). PROVIDE COMPLETE
 INFORMATION FOR THE BALANCED RETURN AIR ON ALL
 BEDROOMS.
  
 4- PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 NUMBER OF CONNECTORS AS SPECIFIED ON THE CONDENSING
 UNIT MOUNTING DETAIL ARE ADEQUATE TO RESIST THE WIND
 LOADS OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). CHECK CONNECTIONS TO THE CONCRETE SLAB AND TO
 THE CONDENSING UNIT. ALSO, SPECIFY HOW LONG ARE THE
 3/8" BOLTS AND ANCHORS SPECIFIED.
  
 5- VERTICAL A/C UNIT DETAIL SHOWN ON SHEET M.1 DOESN'T
 MATCH PROPOSED INSTALLATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE SET OF PLANS RESUBMITTED. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 06:14 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 06:01 Sent To  
Notes
2016-02-12 16:43:23NEW PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-11-23 Cont ID  
Sent By tklarge Date 2015-11-23 Time 06:32 Rev Time 0.00
Received By tklarge Date 2015-11-23 Time 06:12 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-04-08 Time 11:22 Rev Time 0.00
Received By jgomez Date 2016-04-08 Time 11:22 Sent To  
Notes
2016-04-08 11:22:411) METAL ROOF NOA 11-0810.10

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-04-08 Cont ID  
Sent By jgomez Date 2016-02-16 Time 15:13 Rev Time 0.00
Received By jgomez Date 2016-02-16 Time 15:12 Sent To  
Notes
2016-02-16 15:13:321) METAL ROOF NOA 11-0810.10

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-12-28 Cont ID  
Sent By jgomez Date 2015-12-28 Time 13:59 Rev Time 0.00
Received By jgomez Date 2015-12-28 Time 13:59 Sent To  
Notes
2015-12-28 14:00:041- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) METAL ROOFING AS SPECIFIED ON PLANS.
  
 2- ARCHITECT OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By fmittner Date 2016-03-07 Time 16:32 Rev Time 0.00
Received By fmittner Date 2016-03-07 Time 16:32 Sent To  
Notes
2016-03-07 16:38:41STRUCTURE SHALL BE SETBACK 25'-0" PER SUBMITTED SURVEY
 (NOT SITE PLAN). FHM
2016-02-12 16:42:30NEW PLANS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-03 Cont ID  
Sent By fmittner Date 2015-12-03 Time 14:49 Rev Time 0.00
Received By fmittner Date 2015-12-03 Time 14:49 Sent To  
Notes
***NONE***