Plan Review Details - Permit 15110710
Plan Review Stops For Permit 15110710
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By jwitmer Date 2016-05-09 Time 17:40 Rev Time 0.00
Received By jwitmer Date 2016-05-09 Time 16:57 Sent To  
Notes
2016-05-09 17:31:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110710
 ADD: 4316 BRAXTON AVE.
 CONT: LENNAR HOMES
 TEL: 954-533-5299
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 3RD REVIEW
 DATE: MON. MAY 09/2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO: FENCING DOES REQUIRE A SEPARATE PERMIT.
 NOTE THE FENCING AND GATES ARE INCLUDED IN THE DETAILS
 SUBMITTED UNDER THE SITE PLAN AND SURVEY. PLEASE NOTE
 THE GATE IN THE FENCE SEPARATING THE POOL DECK AND TOT
 LOT NEEDS TO SWING OUT AWAY FROM THE POOL. 2014 FBC-B
 454.1.3.1.9.
  
 2) PROVISO: THIS PERMIT IS FOR THE POOL CABANA ONLY!!!
 NO SITE AMENITIES!!!THIS IS JUST NOTICE TO THE
 FLORIDA DECLARATORY STATEMENT 2013-011COMMUNITIY POOLS
 THAT ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL
 COMMUNITY AND ARE LIMITED TO THE EXCLUSIVE USE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, ON THE OTHER HAND, IF A
 SWIMMING POOL/ CLUB LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL USE, IT IS
 COVERED UNDER TITLE III OF THE ADA. IF A COMMUNITY POOL
 IS OWNED OR OPERATED BY A STATE OR LOCAL GOVERNMENT
 ENTITY, IT IS COVERED BY TITLE II OF THE ADA, WHICH
 REQUIRES PROGRAM ACCESSIBILITY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 13:01 Sent To  
Notes
2016-04-21 16:10:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110710
 ADD: 4316 BRAXTON AVE.
 CONT: LENNAR HOMES
 TEL: 954-533-5299
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. APRIL 21/2016
 ACTION: DENIED
  
 1) COMPLIED
  
 2) PROVISO: FENCING DOES REQUIRE A SEPARATE PERMIT.
 NOTE THE FENCING AND GATES ARE INCLUDED IN THE DETAILS
 SUBMITTED UNDER THE SITE PLAN AND SURVEY. PLEASE NOTE
 THE GATE IN THE FENCE SEPARATING THE POOL DECK AND TOT
 LOT NEEDS TO SWING OUT AWAY FROM THE POOL. 2014 FBC-B
 454.1.3.1.9.
  
 3) COMPLIED. IN BOTH THE POOL & POOL DECK AS WELL AS
 THE TOT LOT THE OCCUPANT LOAD WILL BE ABOVE 50
 OCCUPANTS EACH AREA REQUIRING 2 ACCESSIBLE EXITS. 2014
 FBC-B TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT ACCESS
 DOORWAY.
  
 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF
 EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007.
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 4) PROVISO: THIS PERMIT IS FOR THE POOL CABANA ONLY!!!
 NO SITE AMENITIES!!!THIS IS JUST NOTICE TO THE
 FLORIDA DECLARATORY STATEMENT 2013-011COMMUNITIY POOLS
 THAT ARE ASSOCIATED WITH A PRIVATE RESIDENTIAL
 COMMUNITY AND ARE LIMITED TO THE EXCLUSIVE USE OF
 RESIDENTS AND THEIR GUESTS ARE NOT COVERED BY THE ADA
 ACCESSIBILITY REQUIREMENTS, ON THE OTHER HAND, IF A
 SWIMMING POOL/ CLUB LOCATED IN A RESIDENTIAL COMMUNITY
 IS MADE AVAILABLE TO THE PUBLIC FOR RENTAL USE, IT IS
 COVERED UNDER TITLE III OF THE ADA. IF A COMMUNITY POOL
 IS OWNED OR OPERATED BY A STATE OR LOCAL GOVERNMENT
 ENTITY, IT IS COVERED BY TITLE II OF THE ADA, WHICH
 REQUIRES PROGRAM ACCESSIBILITY.
  
 2014 FBC-ACCESSIBILITY CODE 1009.1 GENERAL. WHERE
 PROVIDED, POOL LIFTS, SLOPED ENTRIES, TRANSFER WALLS,
 TRANSFER SYSTEMS, AND POOL STAIRS SHALL COMPLY WITH
 1009. 1009.2 POOL LIFTS. POOL LIFTS SHALL COMPLY WITH
 1009.2.
  
 5) COMPLIED. 2014 FBC-B 454.1.6.1.1 ONE DIAPER CHANGING
 TABLE
  
 6)2ND REQUEST. RESPONSE INDICATES SEE 002.1 FOR
 COMPLIANCE. 2014 FBC-B 1008.2 GATES. GATES SERVING THE
 MEANS OF EGRESS SYSTEM SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION. GATES USED AS A COMPONENT
 IN A MEANS OF EGRESS SHALL CONFORM TO THE APPLICABLE
 REQUIREMENTS FOR DOORS.
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7-10) COMPLIED
  
 11) PLEASE NOTE THE LIFE SAFETY SHEET 002.1_A-0 VERSES
 THE POOL AND DECK PERMIT 16030514, THE POOL CABANA ARE
 LAYED OUT IN REVERSE, DISCREPANCY IN PLANS. ADDITIONAL
 INFORMATION IS REQUIED. PLEASE CORRECT WHICH EVER IS
 REVERSED. 107.2.1.3
  
 12) ELECTRONIC PLAN REVIEW AND ASSOCIATED SIGNATURES.
  
 12A) TRUSS SHOP DRAWINGS ARE SHOWING A ENGINEERS SEAL
 AND SIGNATURE, NOT ELECTRONIC SIGNATURE. WILL NEED TO
 COMPLY WITH 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS OR SUBMIT
 PAPER WITH SIGNATURE, DATED AND SEAL .
  
 12B) GEOTECHNICAL REPORT CONESTOGA-ROVERS P. E. NOT AN
 ELECTRONIC SIGNATURE. 61G15-23.005
  
 12C) GATE ENGINEERING BY VICTOR CERON P. E. ARE NOT
 SIGNED WITH ELECTRONIC SIGNATURE. 61G15-23.005
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-04 Cont ID  
Sent By jwitmer Date 2016-02-03 Time 07:00 Rev Time  
Received By jwitmer Date 2016-02-03 Time 11:58 Sent To  
Notes
2016-02-04 06:55:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110710
 ADD: 5025 ERNEST ST.
 CONT: LENNAR HOMES
 TEL: 954-533-5299
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. FEB. 03/2016
 ACTION: DENIED
  
 1A) THE PERMIT WAS SUBMITTED WITH A ERNEST ST. ADDRESS.
 PLEASE PROVIDE THE CORRECT ADDRESS FOR THE RECREATIONAL
 TRACT THE POOL CABANA IS LOCATED ON. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION WHERE WORK WILL BE COMPLETED.
 THURS. FEB. 04/2016 CITY STAFF HAS ASSIGNED THE
 ADDRESS:
 4316 BRAXTON AVE. PCN: 74-42-43-11-08-018-0000
 PLEASE UPDATE THE PLANS TITLE BLOCK TO REFLECT THE
 LOCATION OF THE PROJECT.
 2014 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS. EACH CHARACTER SHALL BE NOT
 LESS THAN 4 INCHES (102 MM) IN HEIGHT AND NOT LESS THAN
 0.5 INCH (12.7 MM) IN WIDTH. THEY SHALL BE INSTALLED ON
 A CONTRASTING BACKGROUND AND BE PLAINLY VISIBLE FROM
 THE STREET OR ROAD FRONTING THE PROPERTY
  
 1B) THERE IS NEITHER LIFE SAFETY NOR BUILDING CODE DATA
 SHEET IN THIS SUBMITTAL PROVIDING THE MINIMUM BUILDING
 TYPE, OCCUPANCY TYPE (A4) OCCUPANT LOADS, PLEASE
 PROVIDE FOR THE WHOLE OF THE ENCLOSED FENCED AREA. FOR
 THE POOL, POOL DECK AND THE TOT LOT PLEASE FIGURE 50
 SQUARE FEET PER OCCUPANT. THE FIGURE SHOULD BE WELL
 OVER 150 OCCUPANTS THAT WILL REQUIRE EGRESS. WHEN WE
 HIT OCCUPANT LOADS OF 50 AND GREATER 2 EXITS ARE
 REQUIRED.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 OCCUPANCY GROUP
 MINIMUM BUILDING TYPE
 BUILDING FIRE SPRINKLERED OR NOT
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
 2) FENCING DOES REQUIRE A SEPARATE PERMIT. NOTE THE
 FENCING AND GATES ARE INCLUDED IN THE DETAILS SUBMITTED
 UNDER THE SITE PLAN AND SURVEY. PLEASE NOTE THE GATE IN
 THE FENCE SEPARATING THE POOL DECK AND TOT LOT NEEDS TO
 SWING OUT AWAY FROM THE POOL. 2014 FBC-B 454.1.3.1.9.
  
 3) IN BOTH THE POOL & POOL DECK AS WELL AS THE TOT LOT
 THE OCCUPANT LOAD WILL BE ABOVE 50 OCCUPANTS EACH AREA
 REQUIRING 2 ACCESSIBLE EXITS. 2014 FBC-B TABLE 1015.1
 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY.
 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE MEANS OF
 EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION 1007.
 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF EGRESS IS
 REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 4) THIS IS JUST NOTICE TO THE REQUIREMENTS OF THE 2014
 FBC-ACCESSIBILITY CODE 1009.1 GENERAL.
 WHERE PROVIDED, POOL LIFTS, SLOPED ENTRIES, TRANSFER
 WALLS, TRANSFER SYSTEMS, AND POOL STAIRS SHALL COMPLY
 WITH 1009.
  
 2014 FBC-ACCESSIBILITY CODE. 1009.2 POOL LIFTS. POOL
 LIFTS SHALL COMPLY WITH 1009.2.
  
 ADVISORY 1009.2 POOL LIFTS. THERE ARE A VARIETY OF
 SEATS AVAILABLE ON POOL LIFTS RANGING FROM SLING SEATS
 TO THOSE THAT ARE PREFORMED OR MOLDED. POOL LIFT SEATS
 WITH BACKS WILL ENABLE A LARGER POPULATION OF PERSONS
 WITH DISABILITIES TO USE THE LIFT. POOL LIFT SEATS THAT
 CONSIST OF MATERIALS THAT RESIST CORROSION AND PROVIDE
 A FIRM BASE TO TRANSFER WILL BE USABLE BY A WIDER RANGE
 OF PEOPLE WITH DISABILITIES. ADDITIONAL OPTIONS SUCH AS
 ARMRESTS, HEAD RESTS, SEAT BELTS, AND LEG SUPPORT WILL
 ENHANCE ACCESSIBILITY AND BETTER ACCOMMODATE PEOPLE
 WITH A WIDE RANGE OF DISABILITIES.
 1009.2.1 POOL LIFT LOCATION. POOL LIFTS SHALL BE
 LOCATED WHERE THE WATER LEVEL DOES NOT EXCEED 48 INCHES
 (1220 MM).
  
 5) SHEET 033-A-1 FLOOR PLANS THE RESTROOMS DO NOT
 INDICATE COMPLIANCE WITH THE 2014 FBC-B 454.1.6.1.1
 ONE DIAPER CHANGING TABLE SHALL BE PROVIDED AT EACH
 RESTROOM. DIAPER CHANGING TABLES ARE NOT REQUIRED AT
 RESTROOMS WHERE ALL POOLS SERVED ARE RESTRICTED TO
 ADULT USE ONLY.
  
 6) 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF
 EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF
 EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR
 DOORS.
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 7) UNDER SUPPORTING DOCUMENTS THERE IS A PRODUCT
 APPROVAL FOR FIXED WINDOWS. F 1534R5 MI WINDOWS WITHIN
 THIS DOCUMENT THERE ARE SEVERAL WINDOW TYPES, PLEASE
 IDENTIFY WHICH TYPE OF WINDOW IS TO BE INSTALLED. NOTE
 THERE ARE IMPACT AND NON-IMPACT RATED WINDOWS, IF
 NON-IMPACT WINDOWS ARE TO BE INSTALLED THEN STORM
 SHUTTERS FOR OPENING PROTECTION AGAINST IMPACT WILL
 ALSO NEED TO BE SELECTED.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
 ( E ) SHUTTERS
  
 8) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) SHEET 101-S-2 SECTION 1 THROUGH THE BUILDING SHOWS
 THE MONOLITHIC FOOTER ONLY 8 INCHES BENEATH GRADE.
 PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 1809.4 DEPTH AND
 WIDTH OF FOOTINGS. THE MINIMUM DEPTH OF FOOTINGS BELOW
 THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES (305
 MM). SHEET 100-S-1 FOOTING SCHEDULE MF16A INDICATES HE
 DEPTH OF THE FOUNDATION AS 16 INCHES. PLEASE MAKE
 CORRECTION.
  
 10) SHEET 102-S-3 UNDER THE HEADING CRITERIA AND LOADS
 THE ROOF PRESSURES ARE GIVEN ASSUMED VASD NOT GIVEN,
 AND THERE ARE NO PRESSURES FOR WALL ZONES 4 & 5. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-09 Cont ID  
Sent By vperez Date 2016-05-09 Time 10:39 Rev Time 0.00
Received By vperez Date 2016-05-09 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-13 Cont ID  
Sent By vperez Date 2016-04-13 Time 14:34 Rev Time 0.00
Received By vperez Date 2016-04-13 Time 14:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By vperez Date 2016-02-17 Time 07:10 Rev Time 0.00
Received By vperez Date 2016-02-17 Time 07:12 Sent To  
Notes
2016-02-17 07:11:42INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2008 NEC
 COMMENTS:
  
 1. PROVIDE A NOTE TO COMPLY WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE AND UPDATE ALL CODE
 REFERENCES TO NEC 2011. A NOTE WILL SUFFICE.
 2. ADD A NOTE TO INDICATE REQUIREMENTS OF NEC 700.12A
 FOR THE EM FIXTURES AND THAT THEY BE AHEAD OF ANY
 SWITCHING MECHANISM.
 3. LABEL POOL PUMP IN PANEL SCHEDULE TO BE GFCI
 PROTECTED. FBC 107 NEC 680.21C
 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT
 THE SERVICE ONE-LINE. NEC 250.94
 5. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2016-03-05 Cont ID  
Sent By mgonzale Date 2016-03-05 Time   Rev Time 1.00
Received By mgonzale Date 2016-03-05 Time   Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-05-16 Cont ID  
Sent By scaldero Date 2016-05-16 Time 16:26 Rev Time 0.00
Received By scaldero Date 2016-05-16 Time 16:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-03 Cont ID  
Sent By scaldero Date 2016-02-03 Time 09:18 Rev Time 0.00
Received By scaldero Date 2016-02-03 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-06-01 Cont ID  
Sent By skennedy Date 2016-06-01 Time 08:29 Rev Time 0.00
Received By skennedy Date 2016-05-18 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-18 Cont ID  
Sent By lmarchan Date 2016-05-18 Time 09:11 Rev Time 0.00
Received By lmarchan Date 2016-05-04 Time 05:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-27 Cont ID  
Sent By   Date 2016-04-27 Time   Rev Time 0.00
Received By lmarchan Date 2016-04-11 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-08 Cont ID  
Sent By vperez Date 2016-03-08 Time 09:58 Rev Time 0.00
Received By lmarchan Date 2016-01-29 Time 14:29 Sent To  
Notes
2016-02-17 07:14:25EMAIL TO CAROLINE COMPLETION 2/17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 15:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-02-04 Cont ID  
Sent By jwitmer Date 2016-02-04 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2016-02-04 Time 07:00 Sent To  
Notes
2016-02-04 07:00:31IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-16 Cont ID  
Sent By ccole Date 2016-05-16 Time 11:42 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 11:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-15 Cont ID  
Sent By ccole Date 2016-04-15 Time 14:19 Rev Time 0.00
Received By ccole Date 2016-04-15 Time 14:19 Sent To  
Notes
2016-04-15 14:21:46 
 2ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110710
 4/15/16
  
 1) THE SUBMITTED NOA IS FOR GREENHECK EXHAUST FANS,
 HOWEVER BROAN FANS ARE SPECIFIED ON SHEET M-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By ccole Date 2016-02-08 Time 15:35 Rev Time 0.00
Received By ccole Date 2016-02-08 Time 15:35 Sent To  
Notes
2016-02-08 15:37:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110710
 2/8/16
  
 1) PROVIDE AN NOA OR PRODUCT APPROVAL FOR THE EXTERIOR
 WALL MOUNTED EXHAUST FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-05-10 Cont ID  
Sent By gjohnson Date 2016-05-10 Time 16:25 Rev Time 0.00
Received By gjohnson Date 2016-05-10 Time 16:24 Sent To  
Notes
2016-05-10 16:29:01PLUMBING PROVISO:
 1. PROVIDE HOT OR TEMPERED WATER TO LAVATORY'S AND
 WASHDOWN FOR FLOORS
 2. PROVIDE FLOOR DRAINS WITH TRAP PRIMERS.
 3. PROVIDE LETTER FROM ARCHITECT FOR RELIEF FROM
 SERVICE SINK REQUIREMENT.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-20 Cont ID  
Sent By gjohnson Date 2016-04-20 Time 08:45 Rev Time 0.00
Received By gjohnson Date 2016-04-19 Time 13:39 Sent To  
Notes
2016-04-20 09:42:31PLUMBING COMMENTS:
  
 1. SHT. A-3 MEN'S RESTROOM SHOWS THE URINALL OFFSET
 FROM WATER CLOSET AND NEITHER FIXTURE ENCROACHING ON
 THE CLEAR FLOOR SPACE OF THE OTHER, BUT SHT.P-2 SHOWS
 THE URINA DIRECTLY IN FRONT OF THE WATER CLOSET WITCH
 WOULD CAUSE THE WATER CLOSET TO ENCROACH ON THE CLEAR
 FLOOR SPACE OF THE URINAL SHALL COMPLY WITH FBC ACC.
 SEC. 604.3.2
 PLEASE CLARIFY THE DISCREPANCY'S BETWEEN SHTS. A-3,M-1.
 E-1,P-2 PER WPB AMEND. TO FBC 107.2.1
  
 2.SHT. A-0 THE OCCUPANCY GROUP USE IS LISTED AS U.
 UTILITY AND MISCELLANEOUS GROUP U ARE ACCESSORY
 BUILDINGS OR STRUCTURES TO MAIN BUILDINGS THAT DO NOT
 HAVE OR REQUIRE PLUMBING FACILITY'S. THIS IS PART OF A
 POOL AREA THAT REQUIRES PLUMBING FACILITY'S AND A POOL
 IS AN A-4 OCCUPANCY.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3.SHT. A-0 YOU AREA LISTING THE DECK AREA POOL AS 3482
 SF IS THIS THE SF OF THE POOL ITSELF OR THE POOL AND
 DECK AREA COMBINED.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 4. SHT. P-2 YOUR PLUMBING FIXTURE CALCULATIONS APPEAR
 TO BE BASED ON A POOL SF OF 2500 SF OR LESS SHT. A-0 IS
 CALLING OUT 3482 SF WITCH WOULD REQUIRE 2 URINALS IN
 MENS RESTROOM.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 5. PER FBC PL TABLE 403.1 A SERVICE SINK IS REQUIRED
 FOR A-4 OCCUPANCY'S.
  
 6. YOU SHALL PROVIDE HOT OR TEMPERED WATER TO
 LAVATORY'S. YOU SHALL PROVIDE HOT WATER TO THE SERVICE
 SINK.
 PER FBC PL SEC.607.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-03 Cont ID  
Sent By tklarge Date 2016-02-03 Time 10:47 Rev Time 0.00
Received By tklarge Date 2016-02-03 Time 06:24 Sent To  
Notes
2016-02-03 10:06:031) SHT. A-1 - THE NOTES STATE THAT THE TOILET ROOMS
 SHALL COMPLY WITH FBC SEC. 1210 BUT THE FINISH SCHEDULE
 SHOWS THE WALLS IN THE TOILET ROOMS TO BE PAINTEED. THE
 TOILET ROOMS SHALL COMPLY WITH 2014 FBC SEC. 1210.2.2.
 2) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET IN
 THE MEN'S RESTROOM. IT APPEARS THAT THE URINAL MAY
 ENCROACCH INTO THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE WATER CLOSET ENCOACH INTO THE CLEAR
 FLOOR SPACE FOR THE URINAL. NO OTHER FIXTURES OR
 OBSTRUCTIONS SHALL BE LOCATED WITHIN THE REQUIRED WATER
 CLOSET CLEARANCE.2014 FBC-ACCESS. SEC.604.3.2.
 3) SUBMIT THE OCCUPANCY TYPE AND OCCUPANT LOAD OF THE
 SWIMMING POOL, THE POOL DECK, THE TOT LOT AND THE
 CABANA PER THE 2014 FBC SEC.303 AND TABLE 1004.1.2.
 4) THE MINIMUM REQUIRED SANITARY FACILITIES SHALL BE
 BASED UPON THE SQUARE FOOTAGE OF THE SWIMMING POOL IN
 ACCORDANCE WITH THE 2014 FBC-PLUMBING SEC. 403.6.
 SUBMIT THE SQUARE FOOTAGE OF THE SWIMMING POOL.
 5) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 FBC-
 ACCESS. SEC.307.2 FOR PROTRUDING OBJECTS. THE HIGH SIDE
 DRINKING FOUNTAIN MAY REQUIRE A SKIRT TO HAVE THE
 LEADING EDGE BELOW 27 INCHES.
 6) PROVIDE A KEY LEGEND FOR THE KEY NOTES ON SHEETS P-1
 & P-2 .
 7) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE
 LAVATORIES PER THE 2014 FBC-PLUMBING SEC.607.1.
 8) A SERVICE SINK MAY BE REQUIRED DEPENDING ON THE
 OCCUPANCY PER 2014 FBC-PLUMBING TABLE 403.1. IF ONE IS
 REQUIRED, HOT WATER WILL BE REQUIRED TO THE FIXTURE PER
 2014 FBC-PLUMBING SEC.607.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-06-01 Cont ID  
Sent By skennedy Date 2016-06-01 Time 08:16 Rev Time 0.00
Received By skennedy Date 2016-06-01 Time 08:16 Sent To  
Notes
2016-05-26 15:08:36RECEIVED SIGNED AND SEALED TRUSSES, SENT TO SKENNEDY
 FOR REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-05-10 Cont ID  
Sent By skennedy Date 2016-05-10 Time 14:24 Rev Time 0.00
Received By skennedy Date 2016-05-10 Time 14:24 Sent To  
Notes
2016-05-10 14:27:34REVIEW OF DIGITALLY SIGNED & SEPARATELY SUBMITTED
 SIGNED AND SEALED ORIGINAL DOCUMENTS.
  
 AS IT STANDS, THE FOLLOWING REMAIN OUTSTANDING.
  
 12A) TRUSS SHOP DRAWINGS ARE SHOWING A ENGINEERS SEAL
 AND SIGNATURE, NOT ELECTRONIC SIGNATURE. WILL NEED TO
 COMPLY WITH 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS OR SUBMIT
 PAPER WITH SIGNATURE, DATED AND SEAL .
  
 12B) GEOTECHNICAL REPORT CONESTOGA-ROVERS P. E. NOT AN
 ELECTRONIC SIGNATURE. 61G15-23.005
  
 EITHER PROVIDE THE OROGINAL PAPER COPIES OR RE-SUBMIT
 WITH DIGITALLY APPLIED SIGNATUIRES.
  
 A SEPARATELY SUBMITTED GATE DRAWING WITH ORIGINAL S&S
 IS ACCEPTED.
  
 12C) GATE ENGINEERING BY VICTOR CERON P. E. ARE NOT
 SIGNED WITH ELECTRONIC SIGNATURE. 61G15-23.005
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  
  
  
2016-05-10 13:11:57SIGNATURE DOCUMENTS GIVEN TO SKENNEDY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-04-21 Cont ID  
Sent By jwitmer Date 2016-04-21 Time 16:11 Rev Time 0.00
Received By jwitmer Date 2016-04-21 Time 16:11 Sent To  
Notes
2016-04-21 16:12:13SEE COMMENTS UNDER BUILDING FOR ELECTRONIC SIGNATURES.
 JW
2016-02-03 15:34:05ORIGINAL SEALED DOCUMENTS SUBMITTED 2/3/16

Review Stop Z ZONING
Rev No 4 Status P Date 2016-05-19 Cont ID  
Sent By llouie Date 2016-05-19 Time   Rev Time 0.00
Received By llouie Date 2016-05-19 Time   Sent To  
Notes
2016-05-19 10:29:44REFERENCE: PB 1448 (MINOR PD AMENDMENT), APPROVED BY
 P&Z ON 3/24/16.

Review Stop Z ZONING
Rev No 3 Status F Date 2016-05-11 Cont ID  
Sent By llouie Date 2016-05-11 Time   Rev Time 0.00
Received By llouie Date 2016-05-11 Time   Sent To  
Notes
2016-05-11 10:55:54PLEASE ADDRESS THE FOLLOWING COMMENTS:
  
 1.) BICYCLE RACK DETAIL IS INCONSISTENT WITH THE CITY'S
 DESIGN STANDARDS FOR BICYCLE PARKING IN LATEST REVISION
 TO THE SITE PLAN. DIMENSIONS FOR RACK PAD DETAIL ALSO
 REQUIRED.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By llouie Date 2016-04-27 Time   Rev Time 0.00
Received By llouie Date 2016-04-27 Time   Sent To  
Notes
2016-04-27 16:30:30REFERENCE: PB 1448M (MINOR PD AMENDMENT) APPROVED
 3/24/16.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-09 Cont ID  
Sent By llouie Date 2016-02-09 Time 11:39 Rev Time 0.00
Received By llouie Date 2016-02-09 Time 11:39 Sent To  
Notes
2016-02-09 11:45:42** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS IN WRITING AND/OR
 ON THE PLANS WHERE APPLICABLE:
  
 1.) CHANGES DETECTED IN THE LAYOUT OF THE RECREATION
 AREA THAT DOES NOT MATCH THE APPROVED SITE PLAN. THE
 PROPOSED CHANGE REQUIRES AN APPLICATION FOR A MINOR PD
 AMENDMENT TO THE CHARLESTON COMMONS RPD. AN APPLICATION
 FOR A MINOR PD AMENDMENT CAN BE FOUND HERE: HTTP://WPB.
 ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/PLANNING-ZON
 ING-FORMS
  
 2.) SURVEY DOES NOT MATCH THE SITE PLAN. PLEASE ADDRESS
 FOR CONSISTENCY.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  