Plan Review Details - Permit 15110707
| Plan Review Stops For Permit 15110707 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2016-02-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-18 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-12 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-12 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2016-02-12 10:34:51 | ***PROVISOS*** | | | | | | 1. PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD, | | | ARE TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION. | | | DESIGN PRESSURES ARE TO COMPLY ON THE DESIGN PRESSURES | | | SPECIFIED BY THE ENGINEER ON SHEET S02. | | | | | | 2. A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO | | | PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME. | | | | | | AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT | | | APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED. | | | THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF | | | ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL | | | REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN | | | PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE | | | PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL. | | | | | | THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET | | | S02: | | | | | | ZONE 1 -44.99 | | | ZONE 2 -75.34 | | | ZONE 3 -113.39 | | | | | | 3. GMA TO APPLY FOR CERTIFICATE OF AUTHORIZATION; SEND | | | NUMBER VIA EMAIL WHEN THE AA LICENSE NUMBER IS ISSUED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-02-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-02 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-26 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2016-02-02 14:02:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. RESIDENT INSPECTOR INFORMATION RECEIVED; CONTRACTOR | | | RESUME IS REQUIRED. | | | | | | 2. IMPACT FEES ARE TO BE PAID TO PALM BEACH COUNTY, | | | 561-233-5025. THIS MAY BE DONE AFTER ALL REVIEWS ARE | | | COMPLETE, PRIOR TO PERMIT ISSUANCE. | | | | | | 3. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING | | | PROVISO: | | | | | | ***PROVISOS*** | | | | | | 1. PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD, | | | ARE TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION. | | | DESIGN PRESSURES ARE TO COMPLY ON THE DESIGN PRESSURES | | | SPECIFIED BY THE ENGINEER ON SHEET S02. | | | | | | 2. A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO | | | PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME. | | | | | | AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT | | | APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED. | | | THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF | | | ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL | | | REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN | | | PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE | | | PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL. | | | | | | THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET | | | S02: | | | | | | ZONE 1 -44.99 | | | ZONE 2 -75.34 | | | ZONE 3 -113.39 | | | | | | 3. GMA TO APPLY FOR CERTIFICATE OF AUTHORIZATION; SEND | | | NUMBER VIA EMAIL WHEN THE AA LICENSE NUMBER IS ISSUED. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-12-10 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-10 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2015-12-10 12:03:40 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15110717 | | | ADD: 1300 ALLENDALE RD. | | | CONT: TBD / DAN BERCOT | | | TEL: 314-963-0715 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | | FLORIDA BUILDING CODE, BUILDING. | | | | | | | | | 1ST REVIEW | | | DATE: THURS. DEC. 10/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET 008-A1.1: | | | | | | 1A) IS A ARCHITECTURAL SITE PLAN WHICH IS SUPPOSE TO | | | SHOW 60 FEET CLEAR AROUND THE WHOLE BUILDING. THE COVER | | | SHEET 001-T1.1 INDICATES UNDER THE HEADING PROJECT CODE | | | DATA THAT THE DESIGNER HAS DESIGNED THE PROPOSED | | | ADDITION TO CODE SECTION 2014 FBC-B 507 UNLIMITED AREA, | | | BUILDING TYPE: IIB, FULLY SPRINKLERED, S-1 STORAGE | | | OCCUPANCY NON-SEPERATED. THE DESIGNER HAS NOT DECLARED | | | TO WHICH CODE SECTION WITHIN FBC-B 507 A ONE STORY OR A | | | 2 STORY? | | | | | | 1B) IN THE NORTHWEST CORNER OF THE LOT THE BUILDING | | | ABUTTS ANOTHER BUILDING.2014 FBC-B 507.5 ALLOWS FOR A | | | REDUCED OPEN SPACE NOT LESS THAN 40 FEET. THE PALM | | | BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST THIS SITE | | | AS 1306 ALLENDALE RD. AND A OWNER OF ALLENDALE INC. A | | | DIFFERENT OWNER THAT JRB WEST PALM BEACH LLC. | | | THE BUILDING TYPE WILL NEED TO BE REVIEWED FOR CODE | | | COMPLIANCE. | | | | | | 2) THIS STRUCTURE WILL REQUIRE A RESIDENT INSPECTOR. | | | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS | | | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F ?C) IN EXCESS OF 3000 | | | POUNDS PER SQUARE INCH | | | 4. FOR PILE DRIVING5. FOR BUILDINGS WITH AREA GREATER | | | THAN 20,000 SQUARE FOOT | | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION. TILT WALL & METAL BUILDINGS | | | REQUIRING EITHER WELDS OR BOLTED CONNECTIONS. | | | | | | 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL | | | PARTIES NOTARIZED AND RETURNED TO THE BUILDING | | | DEPARTMENT. | | | | | | 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. | | | | | | 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. | | | | | | 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR | | | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS. | | | | | | 3) SHEET 022-S02 INDICATES THE WALL & ROOF PRESSURES IN | | | VASD. WALL PRESSURES SEEM TO BE APPROXIMATELY 4-5 PSF | | | LOWER THAN OUR CALCULATED PRESSURES, THE ROOF PRESSURES | | | ARE GOOD APPROXIMATELY 0.2 PSF DIFFERENCE IN PRESSURES. | | | PLEASE REVIEW THE NEGATIVE WALL PRESSURES WERE TAKEN AT | | | THE 34 FEET MEAN ROOF HEIGHT. ASCE 7-10. | | | | | | 4) BUILDING PROVISO: IN THIS SIBMISSION THERE IS A | | | LETTER FROM ARCO SPECIALTY CONSTRUCTION COMPANY THAT | | | REQUEST THE PRODUCT APPROVALS BE DEFERRED SUBMITTALS, | | | TO BE SUBMITTED AFTER PERMIT ISSUANCE. | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. | | | | | | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT | | | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) | | | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT | | | WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS. | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES,INSULATION, ROOF | | | CURB ASSMBLIES, INTAKE OR EXHAUST FANS | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 5) CONTRACTOR AT RISK. THE BAR JOIST SPACING VERSES THE | | | ALLOWABLE SPANS FOUND IN THE ROOFING PRODUCT | | | APPROVALSWITH THE ROOFING APPROVALS BEING SUBMITTED | | | LATTER! | | | | | | 6) SHEET 016-A5.1 ELEVATIONS SEE NOTE 8 FOR SCUPPERS | | | AND OVERFLOW. SEE SHEET 014-A2.5 FOR SCUPPER AND | | | EMERGENCY OVERFLOW SIZES. PLEASE PROVIDE THE SQUARE FT | | | OF ROOFING TO BE DRAINED, THE RAINFALL AMOUNT/ HR FOR | | | THE SIZING OF THE SCUPPERS AND EMERGENCY OVERFLOW | | | SCUPPERS PER THE 2014 FBC-PLUMBING- CHAPTER 11. | | | | | | 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2016-02-04 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2016-02-04 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2016-02-04 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2016-02-04 13:46:22 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN | | | SATISFACTORILY ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-12-08 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-12-08 |
Time |
19:23 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-12-08 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2015-12-08 19:24:10 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF | | | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, | | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | PG. T1.1 | | | 1. THE APPLICABLE NATIONAL ELECTRICAL CODE IS THE 2011 | | | EDITION. PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY. | | | 2. THE APPLICABLE FIRE CODES ARE THE 2012 EDITION. | | | PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY. | | | PG. E1.1 | | | 1. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE | | | ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY | | | LIGHTING REQUIRED. EXIT DISCHARGE LIGHTING REQUIRED AS | | | WELL. | | | 2. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE | | | ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY | | | LIGHTING REQUIRED. | | | 3. PER FBC-B 1011.1 AN EXIT LIGHT IS REQUIRED HERE. | | | DEPENDING ON FINISHED FLOOR PLAN AND ISLE LAYOUT, | | | ADDITIONAL EXIT LIGHTS MAY BE REQUIRED. | | | PG. E2.1 | | | 1. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 | | | AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET | | | LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF | | | WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL | | | 15- AND 20-AMPERE, 125- AND 250-VOLT NONLOCKING | | | RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE | | | ?WR?. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE | | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. | | | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2016-02-04 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2016-02-04 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2016-02-04 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-02-04 07:20:43 | PLANS AREA IN REVIEW THRU CITY OF WPB ENGINEERING. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2015-12-22 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
2015-12-22 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2015-12-22 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2015-12-22 15:47:52 | PLEASE ADDRESS PLANNING'S COMMENTS. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/2015/12/CROSS-CONNECT | | | ION-MANUAL.PDF | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2016-02-09 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2016-02-09 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-11-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-11-23 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-11-20 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2015-11-23 09:11:39 | 1300 ALLENDALE ROAD | | | PERMIT #15110707 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND | | | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE | | | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE | | | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL | | | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE | | | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. | | | | | | TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS | | | WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE | | | FOLLOWING: | | | | | | PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, | | | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: | | | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF | | | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE | | | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, | | | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. | | | PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET | | | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 50 FEET | | | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE | | | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET | | | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL | | | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC | | | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. | | | | | | PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN | | | TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE | | | PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE | | | PROVIDED AS REQUIRED BY THE AUTHORITY HAVING | | | JURISDICTION. | | | | | | SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER | | | INSTALLATION. | | | | | | NOTE: REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE | | | THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF | | | COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). FBC | | | SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED SHALL BE | | | CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND | | | NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE | | | ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR SHALL | | | ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM | | | THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS, | | | CONSTRUCTION OR VIOLATIONS OF THIS CODE. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-19 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-18 |
Time |
13:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-02-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-02-10 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2016-01-12 |
Time |
14:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-12-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-12-22 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-11-19 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2016-02-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-12 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-12 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2016-02-12 10:33:40 | MU-2016-3229 | | | STAMPED PLAN AND RECEIPT RECEIVED | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-12-10 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-12-10 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2015-12-10 16:10:03 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-02-19 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-02-19 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2016-02-19 10:56:04 | MECHANCIAL PROVISO: | | | PERMIT #15110707 | | | 2/19/16 | | | | | | 1) THE COMM CHECK MECHANICAL COMPLIANCE ENERGY FORM | | | WITH COMPLETED INSPECTION CHECKLIST SHALL ME ON-SITE AT | | | TIME OF INSPECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2016-01-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-01-22 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-01-22 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-12-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-12-09 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-12-09 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2015-12-09 10:17:38 | 1ST REVIEW 2014 MECHANICAL | | | PERMIT #15110707 | | | 12/9/15 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | PROPOSED OCCUPANCY PER TABLE 403.3 FBC-14 MECHANICAL. | | | SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A. | | | 2) PROVIDE ENERGY CALCULATIONS FOR THE NEW ADDITION IN | | | COMPLIANCE WITH SECTION C101.4.3 FBC-14 ENERGY | | | CONSERVATION. | | | 3) THE SUMMER DESIGN DRY BULB TEMPERATURE LISTED ON THE | | | TRACE 700 CALCULATIONS IS INCORRECT. DRY BULB TEMPS PER | | | TABLE 1A ACCA MANUAL N- (90 DEGREES F), & PER APPENDIX | | | D FBC-14 PLUMBING- (91 DEGREES F). PLEASE REVISE THE | | | CALCS ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-23 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2016-01-23 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2016-01-23 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-11-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-30 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-30 |
Time |
04:24 |
Sent To |
|
|
| Notes |
| 2015-11-30 06:17:25 | 1) SUBMIT A FLOOR PLAN SHOWING THE AMOUNT, TYPE AND | | | LOCATION OF THE EXISTING SANITARY FACILITIES IN THE | | | STRUCTURE. THE ADDED 28,775 SQUARE FEET MAY REQUIRE | | | ADDITIONAL SANITARY FACILITIES IN ACCORDANCE WITH 2014 | | | FBC-PLUMBING TABLE 403.1. | | | 2) SUBMIT CALCULATIONS FOR THE SIZING OF THE | | | SCUPPERS.INDICATE ON THE PLANS THE SQUARE FOOTAGE BEING | | | DRAINED BY EACH SCUPPER. THE SIZING OF THE SCUPPERS | | | SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALLS THAT | | | DIVERT RAINWATER TO THE ROOF. SCUPPERS SHALL BE SIZED | | | IN ACCORDANCE WITH 2014 FBC-PLUMBING TABLE 1106.7 BASED | | | ON A 5 INCH PER HOUR RAINFALL RATE. INDICATE THE DESIGN | | | HEAD ( IN INCHES) FOR THE SCUPPERS. | | | 3) SHT. A2.5 - DETAIL # 2 - THE DOWNSPOUT SHALL | | | DISCHARGE A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE | | | WALL PER 2014 FBC SEC.1503.7. | | | 4) THE OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN | | | 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF | | | SURFACE PER 2014 FBC SEC. 1503.4.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2016-01-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-01-27 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-27 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2016-01-27 08:57:44 | PROVISO | | | | | | A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO | | | PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME. | | | | | | AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT | | | APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED. | | | THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF | | | ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL | | | REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN | | | PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE | | | PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL. | | | | | | THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN | | | PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET | | | S02: | | | | | | ZONE 1 -44.99 | | | ZONE 2 -75.34 | | | ZONE 3 -113.39 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2016-02-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-23 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-23 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2016-02-23 07:26:28 | BUILDING ENVELOPE SUPPORTING DOCUMENT RECEIVED VIA | | | EMAIL PER PROVISO | | | DIGITALLY SIGNED & SEALED BY ARCHITECT | | | SENT VIA EMAIL TO CP/LEM | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-19 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-19 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2016-02-19 12:16:02 | ****PASSED WITH PROVISOS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. OK | | | | | | 2. SIGNATURE DOCUMENTS TO BE PASSED WITH PROVISO: | | | | | | CIVIL SHEETS PREPARED BY ADAM SWANEY (PE72235), | | | ENGENUITY GROUP, INC. CA7095) - FILES IN PROJECTDOX DO | | | NOT HAVE A VALID SIGNATURE BUT RECEIVED C102-C105 VIA | | | EMAIL, SIGNATURES CONFIRMED,SENT VIA EMAIL TO CPUELL & | | | LEMARCHANT | | | PROVISO - ENGENUITY GROUP CA7095 TO REVISE TITLE BLOCK | | | TO INCLUDE BUSINESS LICENSE NUMBER | | | | | | ARCHITECTURAL SHEETS PREPARED BY LOUIS VANDELOECHT | | | (AR95072), GMA ARCHITECTS (C OF A PENDING) - DIGITALLY | | | SIGNED & SEALED SIGNATURE DOCUMENTS SENT VIA EMAIL TO | | | CPUELL & LEMARCHANT | | | PROVISO - OBTAIN CERTIFICATE OF AUTHORIZATION, NOTIFY | | | VIA EMAIL WHEN ISSUED BY THE FLORIDA BOARD OF | | | ARCHITECTS) | | | | | | SUPPORTING DOCUMENTS BUILDING ENVELOPE COMCHECK | | | PREPARED BY LOUIS VANDELOECHT ARCHITECT IS NOT SIGNED | | | AND SEALED AS REQUIRED BY FS481 AND IS INCOMPLETE. | | | PROVISO - SEND DIGITALLY SIGNED COMPLETE DOCUMENT VIA | | | EMAIL WITHIN 5 WORKING DAYS TO [email protected] | | | | | | 3. SIGNATURE DOCUMENTS SUBMITTED AND PASSED: | | | | | | STRUCTURAL SHEETS PREPARED BY RICHARD ADAMS (PE35836), | | | RICHARD ADAMS ENGINEERS & CONSULTANTS, INC (CA35836) - | | | ALL PAGES IN PROJECTDOX INCLUDE A VALID DIGITAL | | | SIGNATURE/SEAL | | | | | | ELECTRICAL SHEETS PREPARED BY MATTHEW OTTO (PE58722), | | | OTTO ENGINEERING, INC. (CA27523) - ALL PAGES IN | | | PROJECTDOX INCLUDE A VALID DIGITAL SIGNATURE/SEAL | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2016-02-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-19 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-18 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2016-02-19 08:41:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ACTIONS REQUIRED: | | | | | | AFTER MECHANICAL REVIEW IS PASSED, MECHANICAL SHEETS | | | DIGITAL SIGNATURE WILL BE REVIEWED (PREPARED BY DANA | | | TENNILL, PE55301), TENNILL & ASSOCIATES, INC (CA30058) | | | SUPPORTING DOCUMENTS MECHANICAL LOAD CALCS PREPARED BY | | | DANA TENNILL, PE DIGITAL SIGNATURE WILL BE REVIEWED | | | AFTER MECHANICAL REVIEW IS COMPLETE | | | SUPPORTING DOCUMENTS MECHANICAL COMPLIANCE CERTIFICATE | | | PREPARED BY DANA TENNILL, PE DIGITAL SIGNATURE WILL BE | | | REVIEWED AFTER MECHANICAL REVIEW IS COMPLETE | | | | | | 2. SIGNATURE DOCUMENTS TO BE PASSED WITH PROVISO: | | | | | | CIVIL SHEETS PREPARED BY ADAM SWANEY (PE72235), | | | ENGENUITY GROUP, INC. CA7095) - FILES IN PROJECTDOX DO | | | NOT HAVE A VALID SIGNATURE BUT RECEIVED C102-C105 VIA | | | EMAIL, SIGNATURES CONFIRMED,SENT VIA EMAIL TO CPUELL & | | | LEMARCHANT AFTER C101 IS RECEIVED) | | | PROVISO - ENGENUITY GROUP CA7095 TO REVISE TITLE BLOCK | | | TO INCLUDE BUSINESS LICENSE NUMBER | | | PROVISO - SHEET C101 DOES NOT HAVE A VALID DIGITAL | | | SIGNATURE, SEND VIA EMAIL | | | | | | ARCHITECTURAL SHEETS PREPARED BY LOUIS VANDELOECHT | | | (AR95072), GMA ARCHITECTS (C OF A PENDING) - DIGITALLY | | | SIGNED & SEALED SIGNATURE DOCUMENTS SENT VIA EMAIL TO | | | CPUELL & LEMARCHANT | | | PROVISO - OBTAIN CERTIFICATE OF AUTHORIZATION, NOTIFY | | | VIA EMAIL WHEN ISSUED BY THE FLORIDA BOARD OF | | | ARCHITECTS) | | | | | | SUPPORTING DOCUMENTS BUILDING ENVELOPE COMCHECK | | | PREPARED BY LOUIS VANDELOECHT ARCHITECT IS NOT SIGNED | | | AND SEALED AS REQUIRED BY FS481 AND IS INCOMPLETE. | | | PROVISO - SEND DIGITALLY SIGNED COMPLETE DOCUMENT VIA | | | EMAIL WITHIN 5 WORKING DAYS TO [email protected] | | | | | | 3. SIGNATURE DOCUMENTS SUBMITTED AND PASSED: | | | | | | STRUCTURAL SHEETS PREPARED BY RICHARD ADAMS (PE35836), | | | RICHARD ADAMS ENGINEERS & CONSULTANTS, INC (CA35836) - | | | ALL PAGES IN PROJECTDOX INCLUDE A VALID DIGITAL | | | SIGNATURE/SEAL | | | | | | ELECTRICAL SHEETS PREPARED BY MATTHEW OTTO (PE58722), | | | OTTO ENGINEERING, INC. (CA27523) - ALL PAGES IN | | | PROJECTDOX INCLUDE A VALID DIGITAL SIGNATURE/SEAL | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2016-02-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-17 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-16 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2016-02-17 09:24:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | CONTRACTOR IS TO CONFIRM ALL SIGNATURE DOCUMENTS PRIOR | | | TO SUBMITTAL. | | | | | | 1. 2/17/16 SOILS REPORT PREPARED BY JAIME VALEZ | | | (PE66416), DUNKELBERGER (6870); UNABLE TO LOCATE THE | | | ENGINEERING BUSINESS LICENSE NUMBER ON THE REPORT, SEE | | | FAC61G15-23, WWW.FBPE.ORG. PLEASE INCLUDE. PLEASE | | | UPLOAD AS A RESUBMITTAL (SAME NAME AS ORIGINAL SOILS | | | REPORT FILE). | | | | | | 2. CIVIL SHEETS HAVE THE FOLLOWING ERRORS: | | | C101 IS NOT DIGITALLY SIGNED AND SEALED. | | | C102, C103 SEAL IS INVALID. | | | OTHER SHEETS NOT CHECKED. CONTRACTOR IS TO VERIFY VALID | | | SIGNATURE OF ALL SHEETS PRIOR TO SUBMITTAL OF SIGNATURE | | | DOCUMENTS. | | | CIVIL SHEETS LACK A TITLE BLOCK IN ACCORDANCE WITH | | | FAC61G-15. | | | | | | 3. FIRE PROTECTION SHEET NOT SIGNED AND SEALED. NO | | | ACTION REQUIRED; THIS SHEET HAS BEEN MARKED "FOR | | | REFERENCE ONLY" (WORK IS UNDER A SEPARATE ISSUED | | | PERMIT) | | | | | | 4. 2/17/16 SHEETS PREPARED BY LOUIS VANDELOECHT | | | (AR95072), GMA ARCHITECTS, INC (C OF A PENDING) - OK | | | WITH PROVISOS: | | | OBTAIN CERTIFICATE OF AUTHORIZATION | | | PAGE A6.3 ON INDEX PAGE WAS NOT SUBMITTED, PER | | | APPLICANT THE INDEX IS INCORRECT. ARCHITECT TO REVISE | | | HIS PLAN TO REMOVE THIS SHEET FROM INDEX. (EMAIL FROM | | | ARCHITECT CONFIRMING THAT THIS SHEET WAS INCLUDED ON | | | INDEX IN ERROR WAS ROUTED TO RECORDS) | | | | | | 5. REVISED MECHANICAL SHEETS TO BE RESUBMITTED WITH | | | REVISED TITLE BLOCK INFORMATION. | | | | | | 6. "BUILDING ENVELOPE COMCHECK" LACK A DIGITAL | | | SIGNATURE (ARCHITECT). PLEASE UPLOAD TO PROJECTDOX. | | | | | | 7. "MECHANICAL ENERGY COMPLIANCE FORM" IS SIGNED BY | | | "TIM SCHAEFFER PE". THIS DESIGN PROFESSIONAL'S NAME | | | DOES NOT APPEAR ON ANY OF THE CONSTRUCTION DOCUMENTS, | | | AND THIS DOCUMENT LACKS THE INFORMATION REQUIRED BY | | | FAC61G15-23. IF THIS IS DELEGATED ENGINEERING, ENGINEER | | | OF RECORD IS TO REVIEW THIS DOCUMENT, SEE FAC61G-15. | | | | | | 8. "MECHANICAL LOAD CALCULATIONS" STATES THAT THEY ARE | | | PREPARED BY ICON MECHANICAL, AND THERE IS NO TITLE | | | BLOCK FOR MR. TENNILL. | | | | | | THE FOLLOWING DESIGN PROFESSIONALS SIGNATURE DOCUMENTS | | | ARE IN COMPLIANCE WITH FAC61G15: | | | | | | 9. STRUCTURAL SHEETS, RICHARD ADAMS (PE35836), RICHARD | | | ADAMS ENGINEERS & CONSULTANTS, PA (7565) - OK | | | | | | 10. ELECTRICAL SHEETS, MATTHEW OTTO (PE58722), OTTO | | | ENGINEERING, INC. (27523) - OK | | | | | | | | 2016-02-16 09:24:16 | SHILL WORKING ON |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2016-02-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-10 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-10 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2016-02-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-02-08 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-02-08 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2016-02-08 16:50:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PROVIDE A RESUME FOR THE CONTRACTOR SHOWING EXPERIENCE | | | WITH THIS TYPE OF CONSTRUCTION, FBC 107. | | | | | | THIS MAY BE SUBMITTED MID-REVIEW. | | | | | | (RESIDENT INSPECTOR AGREEMENT AND INSPECTOR INFORMATION | | | RECEIVED, APPROVED BY K.CONRAD AND ROUTED TO RECORDS) |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2016-01-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2016-01-26 |
Time |
18:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2016-01-26 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2016-01-26 18:02:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | PER APPLICANT, RESIDENT INSPECTOR WILL BE LOU PERINI, | | | TERRACON. | | | | | | PROVIDE A COMPLETED RESIDENT INSPECTOR AGREEMENT AND | | | SUBMIT. ALSO SUBMIT INSPECTOR INFORMATION (ALL | | | INSPECTORS PROPOSED). | | | | | | PROVIDE A RESUME FOR THE CONTRACTOR SHOWING EXPERIENCE | | | WITH THIS TYPE OF CONSTRUCTION, FBC 107. | | | | | | THIS MAY BE SUBMITTED MID-REVIEW. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-02-05 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-02-05 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-02-05 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2016-02-05 16:28:58 | PROVISOS | | | | | | LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED | | | BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | | | | | PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT, | | | LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE | | | AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE | | | LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE, | | | SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT | | | COULD BE IMPACTED BY TREE ROOTS. | | | | | | PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON THE | | | PROPERTY, A TREE ALTERATION PERMIT SHALL BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE DEVELOPMENT SERVICES | | | DEPARTMENT - PLANNING DIVISION. | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR | | | THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL: | | | | | | A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED | | | EQUIPMENT AND UTILITIES. | | | B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE | | | SITE. | | | C. THE SITE PLAN SHALL BE REVISED TO ACCURATELY REFLECT | | | THE CONDITIONS NORTH OF THE DUMPSTER, THE PROPOSED | | | PARKING, AND EXPSNSION OF THE LANDSCAPE ISLAND. | | | | | | ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE | | | PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY | | | ACCESS. | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2016-02-04 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2016-02-04 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2016-02-04 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2016-02-04 09:44:57 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 02.04.2016 | | | PERMIT NO.: 15110707 | | | ADDRESS: 1300 ALLENDALE ROAD | | | CONTRACTOR/CONTACT: DAN BERCOT | | | TELEPHONE NO.: 314.963.0715 | | | SCOPE OF REVIEW: 28,775 SQUARE FOOT EXPANSION TO | | | EXISTING WAREHOUSE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. THE ARCHITECTURAL SITE PLAN (SHEET A1.1) DOES NOT | | | MATCH THE SITE PLAN THAT WAS INCLUDED IN THE IPD | | | APPLICATION: | | | | | | A. THE SITE PLAN SUBMITTED AS PART OF THE IPD | | | APPLICATION PROVIDED FOR A 30 FOOT SETBACK FROM THE | | | PROPERTY LINE. ALL WAIVERS APPROVED ARE BASED UPON THIS | | | SETBACK. ONCE THE IPD IS APPROVED, THE PROPOSED | | | ADDITION CANNOT BE ANY CLOSER THAN 30 FEET UNLESS A | | | MAJOR AMENDMENT TO THE IPD IS SUBMITTED. | | | | | | B. THE SITE PLAN SUBMITTED AS PART OF THE IPD | | | APPLICATION IDENTIFIED THE AREA NORTH OF DUMPSTER AS | | | FOUR (4) PARKING SPACES...THIS ENTIRE AREA DIFFERS | | | BETWEEN SHEETS A1.1 AND SP-1. | | | | | | 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED | | | BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | | | | | WHILE THEY DO NOT AFFECT THE ISSUANCE OF A BUILDING | | | PERMIT, PLEASE TAKE NOTE OF THE FOLLOWING: | | | | | | 1. ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE | | | PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY | | | ACCESS. | | | | | | 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 3. PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT, | | | LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE | | | AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE | | | LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE, | | | SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT | | | COULD BE IMPACTED BY TREE ROOTS. | | | | | | 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | FOR THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL: | | | | | | A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED | | | EQUIPMENT AND UTILITIES. | | | | | | B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE | | | SITE. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-12-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2015-12-09 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2015-12-09 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2015-12-09 16:39:57 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 12.09.2015 | | | PERMIT NO.: 15110707 | | | ADDRESS: 1300 ALLENDALE ROAD | | | CONTRACTOR/CONTACT: DAN BERCOT | | | TELEPHONE NO.: 314.963.0715 | | | SCOPE OF REVIEW: 28,775 SQUARE FOOT EXPANSION TO | | | EXISTING WAREHOUSE. | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE | | | APPLICATION FOR AN INDUSTRIAL PLANNED DEVELOPMENT (IPD) | | | SHALL BE APPROVED BY THE CITY COMMISSION. THIS IS | | | TENTATIVELY SCHEDULED FOR PRESENTATION TO THE | | | COMMISSION ON 1/4/2015 AND 1/19/2015. | | | | | | 2. A CURRENT/ACCURATE SURVEY SHALL BE PROVIDED. | | | | | | 3. A SITE PLAN SHALL BE PROVIDED THAT INCLUDES THE | | | FOLLOWING: | | | | | | A. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO | | | THE SURROUNDING AREA. | | | | | | B. SETBACK DIMENSIONS FROM ALL SIDES OF THE BUILDING | | | TO ADJACENT PROPERTY LINES. | | | | | | C. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT | | | (SIDEWALKS, FENCES, WALLS, OR BERMS). | | | | | | D. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES. | | | | | | E. STANDARD CITY DETAILS OF PARKING (SMALL CAR, | | | HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS, | | | DRIVEWAYS, DUMPSTERS AND SIGNS. | | | | | | F. DIMENSIONS OF ALL PARKING ROW, DRIVE AISLES, | | | LANDSCAPE BUFFERS, WALKWAYS, ETC. | | | | | | G. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT: | | | | | | I. EXISTING/PROPOSED LAND USE AND ZONING. | | | II. TOTAL ACRES OF THE PROJECT. | | | III. TOTAL GROSS BUILDING SQUARE FOOTAGE. | | | IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING | | | COVERAGE & IMPERMEABLE SURFACE. | | | V. ACRES AND PERCENT OF WATER BODIES. | | | VI. DENSITY AND NUMBER OF DWELLING UNITS | | | (RESIDENTIAL). | | | VII. PARKING COMPUTATIONS (PARKING REQUIRED, | | | PROVIDED, ETC.) | | | VIII. FLOOR AREA RATIO (FAR). | | | | | | 4. THE ARCHITECTURAL SITE PLAN (SHEET A1.1) DOES NOT | | | MATCH THE SITE PLAN THAT WAS INCLUDED IN THE IPD | | | APPLICATION: | | | | | | A. THE SITE PLAN SUBMITTED AS PART OF THE IPD | | | APPLICATION PROVIDED FOR A 30 FOOT SETBACK FROM THE | | | PROPERTY LINE. ALL WAIVERS APPROVED ARE BASED UPON THIS | | | SETBACK. ONCE THE IPD IS APPROVED, THE PROPOSED | | | ADDITION CANNOT BE ANY CLOSER THAN 30 FEET UNLESS A | | | MAJOR AMENDMENT TO THE IPD IS SUBMITTED. | | | | | | B. THE SITE PLAN SUBMITTED AS PART OF THE IPD | | | APPLICATION IDENTIFIED THE AREA NORTH OF DUMPSTER AS | | | FOUR (4) PARKING SPACES, THESE ARE NOT SHOWN ON SHEET | | | A1.1. | | | | | | C. THE LAYOUT OF THE PARKING LOT DIFFERS BETWEEN THE | | | SITE PLAN SUBMITTED AS PART OF THE IPD APPLICATION AND | | | SHEET A1.1, WHICH WAS SUBMITTED WITH THE BUILDING | | | PERMIT APPLICATION. | | | | | | 5. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE | | | LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED | | | BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR). | | | | | | 6. DETAILS SHALL BE PROVIDED FOR BIKE RACKS AND THEIR | | | LOCATION SHALL BE IDENTIFIED ON THE SITE PLAN. | | | | | | 7. PHOTOMETRIC PLAN SHALL BE PROVIDED FOR ALL OUTDOOR | | | ILLUMINATION. | | | | | | 8. AN APPLICATION FOR A UNITY OF TITLE SHALL BE | | | SUBMITTED TO THE CITY?S PUBLIC WORKS DEPARTMENT ? | | | ENGINEERING DIVISION, AND SUCH UNITY OF TITLE SHALL BE | | | RECORDED IN THE PUBLIC RECORDS OF PALM BEACH COUNTY, | | | FOR ALL REAL PROPERTY CONTAINED WITHIN THE IPD. A | | | CERTIFIED COPY OF THE RECORDED UNITY OF TITLE SHALL BE | | | PROVIDED TO THE DEVELOPMENT SERVICES DEPARTMENT - | | | PLANNING DIVISION. | | | | | | WHILE THEY DO NOT AFFECT THE ISSUANCE OF A BUILDING | | | PERMIT, PLEASE TAKE NOTE OF THE FOLLOWING: | | | | | | 1. ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE | | | PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY | | | ACCESS. | | | | | | 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 3. PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT, | | | LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE | | | AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE | | | LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE, | | | SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT | | | COULD BE IMPACTED BY TREE ROOTS. | | | | | | 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY | | | FOR THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL: | | | | | | A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED | | | EQUIPMENT AND UTILITIES. | | | | | | B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE | | | SITE. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|