Plan Review Details - Permit 15110707
Plan Review Stops For Permit 15110707
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-18 Cont ID  
Sent By shill Date 2016-02-18 Time 14:34 Rev Time 0.00
Received By shill Date 2016-02-18 Time 14:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 10:34 Rev Time 0.00
Received By shill Date 2016-02-12 Time 10:34 Sent To  
Notes
2016-02-12 10:34:51***PROVISOS***
  
 1. PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD,
 ARE TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
 DESIGN PRESSURES ARE TO COMPLY ON THE DESIGN PRESSURES
 SPECIFIED BY THE ENGINEER ON SHEET S02.
  
 2. A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO
 PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME.
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED.
 THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF
 ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL
 REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN
 PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE
 PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL.
  
 THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET
 S02:
  
 ZONE 1 -44.99
 ZONE 2 -75.34
 ZONE 3 -113.39
  
 3. GMA TO APPLY FOR CERTIFICATE OF AUTHORIZATION; SEND
 NUMBER VIA EMAIL WHEN THE AA LICENSE NUMBER IS ISSUED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-02 Cont ID  
Sent By shill Date 2016-02-02 Time 14:00 Rev Time 0.00
Received By shill Date 2016-01-26 Time 11:11 Sent To  
Notes
2016-02-02 14:02:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. RESIDENT INSPECTOR INFORMATION RECEIVED; CONTRACTOR
 RESUME IS REQUIRED.
  
 2. IMPACT FEES ARE TO BE PAID TO PALM BEACH COUNTY,
 561-233-5025. THIS MAY BE DONE AFTER ALL REVIEWS ARE
 COMPLETE, PRIOR TO PERMIT ISSUANCE.
  
 3. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISO:
  
 ***PROVISOS***
  
 1. PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD,
 ARE TO BE SUBMITTED FOR REVIEW PRIOR TO INSTALLATION.
 DESIGN PRESSURES ARE TO COMPLY ON THE DESIGN PRESSURES
 SPECIFIED BY THE ENGINEER ON SHEET S02.
  
 2. A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO
 PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME.
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED.
 THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF
 ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL
 REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN
 PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE
 PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL.
  
 THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET
 S02:
  
 ZONE 1 -44.99
 ZONE 2 -75.34
 ZONE 3 -113.39
  
 3. GMA TO APPLY FOR CERTIFICATE OF AUTHORIZATION; SEND
 NUMBER VIA EMAIL WHEN THE AA LICENSE NUMBER IS ISSUED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-10 Cont ID  
Sent By jwitmer Date 2015-12-10 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 06:54 Sent To  
Notes
2015-12-10 12:03:40BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110717
 ADD: 1300 ALLENDALE RD.
 CONT: TBD / DAN BERCOT
 TEL: 314-963-0715
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: THURS. DEC. 10/ 2015
 ACTION: DENIED
  
 1) SHEET 008-A1.1:
  
 1A) IS A ARCHITECTURAL SITE PLAN WHICH IS SUPPOSE TO
 SHOW 60 FEET CLEAR AROUND THE WHOLE BUILDING. THE COVER
 SHEET 001-T1.1 INDICATES UNDER THE HEADING PROJECT CODE
 DATA THAT THE DESIGNER HAS DESIGNED THE PROPOSED
 ADDITION TO CODE SECTION 2014 FBC-B 507 UNLIMITED AREA,
 BUILDING TYPE: IIB, FULLY SPRINKLERED, S-1 STORAGE
 OCCUPANCY NON-SEPERATED. THE DESIGNER HAS NOT DECLARED
 TO WHICH CODE SECTION WITHIN FBC-B 507 A ONE STORY OR A
 2 STORY?
  
 1B) IN THE NORTHWEST CORNER OF THE LOT THE BUILDING
 ABUTTS ANOTHER BUILDING.2014 FBC-B 507.5 ALLOWS FOR A
 REDUCED OPEN SPACE NOT LESS THAN 40 FEET. THE PALM
 BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST THIS SITE
 AS 1306 ALLENDALE RD. AND A OWNER OF ALLENDALE INC. A
 DIFFERENT OWNER THAT JRB WEST PALM BEACH LLC.
 THE BUILDING TYPE WILL NEED TO BE REVIEWED FOR CODE
 COMPLIANCE.
  
 2) THIS STRUCTURE WILL REQUIRE A RESIDENT INSPECTOR.
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR PILE DRIVING5. FOR BUILDINGS WITH AREA GREATER
 THAN 20,000 SQUARE FOOT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION. TILT WALL & METAL BUILDINGS
 REQUIRING EITHER WELDS OR BOLTED CONNECTIONS.
  
 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED.
  
 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) SHEET 022-S02 INDICATES THE WALL & ROOF PRESSURES IN
 VASD. WALL PRESSURES SEEM TO BE APPROXIMATELY 4-5 PSF
 LOWER THAN OUR CALCULATED PRESSURES, THE ROOF PRESSURES
 ARE GOOD APPROXIMATELY 0.2 PSF DIFFERENCE IN PRESSURES.
 PLEASE REVIEW THE NEGATIVE WALL PRESSURES WERE TAKEN AT
 THE 34 FEET MEAN ROOF HEIGHT. ASCE 7-10.
  
 4) BUILDING PROVISO: IN THIS SIBMISSION THERE IS A
 LETTER FROM ARCO SPECIALTY CONSTRUCTION COMPANY THAT
 REQUEST THE PRODUCT APPROVALS BE DEFERRED SUBMITTALS,
 TO BE SUBMITTED AFTER PERMIT ISSUANCE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,INSULATION, ROOF
 CURB ASSMBLIES, INTAKE OR EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) CONTRACTOR AT RISK. THE BAR JOIST SPACING VERSES THE
 ALLOWABLE SPANS FOUND IN THE ROOFING PRODUCT
 APPROVALSWITH THE ROOFING APPROVALS BEING SUBMITTED
 LATTER!
  
 6) SHEET 016-A5.1 ELEVATIONS SEE NOTE 8 FOR SCUPPERS
 AND OVERFLOW. SEE SHEET 014-A2.5 FOR SCUPPER AND
 EMERGENCY OVERFLOW SIZES. PLEASE PROVIDE THE SQUARE FT
 OF ROOFING TO BE DRAINED, THE RAINFALL AMOUNT/ HR FOR
 THE SIZING OF THE SCUPPERS AND EMERGENCY OVERFLOW
 SCUPPERS PER THE 2014 FBC-PLUMBING- CHAPTER 11.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 13:45 Rev Time 0.00
Received By albarran Date 2016-02-04 Time 13:06 Sent To  
Notes
2016-02-04 13:46:22ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-08 Cont ID  
Sent By albarran Date 2015-12-08 Time 19:23 Rev Time 0.00
Received By albarran Date 2015-12-08 Time 16:37 Sent To  
Notes
2015-12-08 19:24:10THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 PG. T1.1
 1. THE APPLICABLE NATIONAL ELECTRICAL CODE IS THE 2011
 EDITION. PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY.
 2. THE APPLICABLE FIRE CODES ARE THE 2012 EDITION.
 PLEASE CORRECT ALL PLAN NOTES ACCORDINGLY.
 PG. E1.1
 1. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE
 ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY
 LIGHTING REQUIRED. EXIT DISCHARGE LIGHTING REQUIRED AS
 WELL.
 2. PER FBC-B 1006.3 THIS STAIR LANDING SHALL BE
 ILLUMINATED IN THE EVENT OF POWER FAILURE. EMERGENCY
 LIGHTING REQUIRED.
 3. PER FBC-B 1011.1 AN EXIT LIGHT IS REQUIRED HERE.
 DEPENDING ON FINISHED FLOOR PLAN AND ISLE LAYOUT,
 ADDITIONAL EXIT LIGHTS MAY BE REQUIRED.
 PG. E2.1
 1. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15- AND 20-AMPERE, 125- AND 250-VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2016-02-04 Cont ID  
Sent By mgonzale Date 2016-02-04 Time   Rev Time 1.00
Received By mgonzale Date 2016-02-04 Time   Sent To  
Notes
2016-02-04 07:20:43PLANS AREA IN REVIEW THRU CITY OF WPB ENGINEERING.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By Mgonzale Date 2015-12-22 Time   Rev Time 1.00
Received By mgonzale Date 2015-12-22 Time   Sent To Z
Notes
2015-12-22 15:47:52PLEASE ADDRESS PLANNING'S COMMENTS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/WP-CONTENT/UPLOADS/2015/12/CROSS-CONNECT
 ION-MANUAL.PDF
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-09 Cont ID  
Sent By wjolin Date 2016-02-09 Time 13:57 Rev Time 0.00
Received By wjolin Date 2016-02-09 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-23 Cont ID  
Sent By wjolin Date 2015-11-23 Time 09:15 Rev Time 0.00
Received By wjolin Date 2015-11-20 Time 11:34 Sent To  
Notes
2015-11-23 09:11:391300 ALLENDALE ROAD
 PERMIT #15110707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
  
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 INSTALLATION.
  
 NOTE: REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE
 THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). FBC
 SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED SHALL BE
 CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND
 NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE
 ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR SHALL
 ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM
 THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS,
 CONSTRUCTION OR VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-19 Cont ID  
Sent By shill Date 2016-02-19 Time 12:17 Rev Time 0.00
Received By shill Date 2016-02-18 Time 13:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-10 Cont ID  
Sent By cpuell Date 2016-02-10 Time 11:55 Rev Time 0.00
Received By cpuell Date 2016-01-12 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-22 Cont ID  
Sent By cpuell Date 2015-12-22 Time 16:10 Rev Time 0.00
Received By cpuell Date 2015-11-19 Time 10:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 10:33 Rev Time 0.00
Received By shill Date 2016-02-12 Time 10:33 Sent To  
Notes
2016-02-12 10:33:40MU-2016-3229
 STAMPED PLAN AND RECEIPT RECEIVED
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-10 Cont ID  
Sent By jwitmer Date 2015-12-10 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 16:09 Sent To  
Notes
2015-12-10 16:10:03BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 10:49 Rev Time 0.00
Received By ccole Date 2016-02-19 Time 10:49 Sent To  
Notes
2016-02-19 10:56:04MECHANCIAL PROVISO:
 PERMIT #15110707
 2/19/16
  
 1) THE COMM CHECK MECHANICAL COMPLIANCE ENERGY FORM
 WITH COMPLETED INSPECTION CHECKLIST SHALL ME ON-SITE AT
 TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-22 Cont ID  
Sent By ccole Date 2016-01-22 Time 14:00 Rev Time 0.00
Received By ccole Date 2016-01-22 Time 14:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By ccole Date 2015-12-09 Time 10:05 Rev Time 0.00
Received By ccole Date 2015-12-09 Time 10:05 Sent To  
Notes
2015-12-09 10:17:381ST REVIEW 2014 MECHANICAL
 PERMIT #15110707
 12/9/15
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED OCCUPANCY PER TABLE 403.3 FBC-14 MECHANICAL.
 SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A.
 2) PROVIDE ENERGY CALCULATIONS FOR THE NEW ADDITION IN
 COMPLIANCE WITH SECTION C101.4.3 FBC-14 ENERGY
 CONSERVATION.
 3) THE SUMMER DESIGN DRY BULB TEMPERATURE LISTED ON THE
 TRACE 700 CALCULATIONS IS INCORRECT. DRY BULB TEMPS PER
 TABLE 1A ACCA MANUAL N- (90 DEGREES F), & PER APPENDIX
 D FBC-14 PLUMBING- (91 DEGREES F). PLEASE REVISE THE
 CALCS ACCORDINGLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-23 Cont ID  
Sent By tklarge Date 2016-01-23 Time 09:21 Rev Time 0.00
Received By tklarge Date 2016-01-23 Time 08:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By tklarge Date 2015-11-30 Time 06:32 Rev Time 0.00
Received By tklarge Date 2015-11-30 Time 04:24 Sent To  
Notes
2015-11-30 06:17:251) SUBMIT A FLOOR PLAN SHOWING THE AMOUNT, TYPE AND
 LOCATION OF THE EXISTING SANITARY FACILITIES IN THE
 STRUCTURE. THE ADDED 28,775 SQUARE FEET MAY REQUIRE
 ADDITIONAL SANITARY FACILITIES IN ACCORDANCE WITH 2014
 FBC-PLUMBING TABLE 403.1.
 2) SUBMIT CALCULATIONS FOR THE SIZING OF THE
 SCUPPERS.INDICATE ON THE PLANS THE SQUARE FOOTAGE BEING
 DRAINED BY EACH SCUPPER. THE SIZING OF THE SCUPPERS
 SHALL INCLUDE 1/2 THE AREA OF ANY VERTICAL WALLS THAT
 DIVERT RAINWATER TO THE ROOF. SCUPPERS SHALL BE SIZED
 IN ACCORDANCE WITH 2014 FBC-PLUMBING TABLE 1106.7 BASED
 ON A 5 INCH PER HOUR RAINFALL RATE. INDICATE THE DESIGN
 HEAD ( IN INCHES) FOR THE SCUPPERS.
 3) SHT. A2.5 - DETAIL # 2 - THE DOWNSPOUT SHALL
 DISCHARGE A MINIMUM OF ONE FOOT AWAY FROM THE STRUCTURE
 WALL PER 2014 FBC SEC.1503.7.
 4) THE OVERFLOW SCUPPERS SHALL BE LOCATED NO LESS THAN
 2 INCHES NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF
 SURFACE PER 2014 FBC SEC. 1503.4.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2016-01-27 Cont ID  
Sent By shill Date 2016-01-27 Time 08:54 Rev Time 0.00
Received By shill Date 2016-01-27 Time 08:54 Sent To  
Notes
2016-01-27 08:57:44PROVISO
  
 A SEPARATE ROOF PERMIT APPLICATION IS REQUIRED. NO
 PRODUCT APPROVALS HAVE BEEN SUBMITTED AT THIS TIME.
  
 AT TIME OF ROOF SUB PERMIT APPLICATION, PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD ARE REQUIRED.
 THE PROPOSED ASSEMBLY SHOULD BE INDICATED AND, IF
 ENHANCED FASTENING IS REQUIRED AND THE PRODUCT APPROVAL
 REQUIRES THAT THE CALCULATIONS BE DONE BY A DESIGN
 PROFESSIONAL, ENGINEERING CALCULATIONS ARE TO BE
 PROVIDED AT TIME OF ROOF SUB PERMIT SUBMITTAL.
  
 THE ROOF ASSEMBLY IS TO MEET THE MINIMUM DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER OF RECORD ON SHEET
 S02:
  
 ZONE 1 -44.99
 ZONE 2 -75.34
 ZONE 3 -113.39
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2016-02-23 Cont ID  
Sent By shill Date 2016-02-23 Time 07:25 Rev Time 0.00
Received By shill Date 2016-02-23 Time 07:25 Sent To  
Notes
2016-02-23 07:26:28BUILDING ENVELOPE SUPPORTING DOCUMENT RECEIVED VIA
 EMAIL PER PROVISO
 DIGITALLY SIGNED & SEALED BY ARCHITECT
 SENT VIA EMAIL TO CP/LEM
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-02-19 Cont ID  
Sent By shill Date 2016-02-19 Time 12:15 Rev Time 0.00
Received By shill Date 2016-02-19 Time 12:15 Sent To  
Notes
2016-02-19 12:16:02****PASSED WITH PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. OK
  
 2. SIGNATURE DOCUMENTS TO BE PASSED WITH PROVISO:
  
 CIVIL SHEETS PREPARED BY ADAM SWANEY (PE72235),
 ENGENUITY GROUP, INC. CA7095) - FILES IN PROJECTDOX DO
 NOT HAVE A VALID SIGNATURE BUT RECEIVED C102-C105 VIA
 EMAIL, SIGNATURES CONFIRMED,SENT VIA EMAIL TO CPUELL &
 LEMARCHANT
 PROVISO - ENGENUITY GROUP CA7095 TO REVISE TITLE BLOCK
 TO INCLUDE BUSINESS LICENSE NUMBER
  
 ARCHITECTURAL SHEETS PREPARED BY LOUIS VANDELOECHT
 (AR95072), GMA ARCHITECTS (C OF A PENDING) - DIGITALLY
 SIGNED & SEALED SIGNATURE DOCUMENTS SENT VIA EMAIL TO
 CPUELL & LEMARCHANT
 PROVISO - OBTAIN CERTIFICATE OF AUTHORIZATION, NOTIFY
 VIA EMAIL WHEN ISSUED BY THE FLORIDA BOARD OF
 ARCHITECTS)
  
 SUPPORTING DOCUMENTS BUILDING ENVELOPE COMCHECK
 PREPARED BY LOUIS VANDELOECHT ARCHITECT IS NOT SIGNED
 AND SEALED AS REQUIRED BY FS481 AND IS INCOMPLETE.
 PROVISO - SEND DIGITALLY SIGNED COMPLETE DOCUMENT VIA
 EMAIL WITHIN 5 WORKING DAYS TO [email protected]
  
 3. SIGNATURE DOCUMENTS SUBMITTED AND PASSED:
  
 STRUCTURAL SHEETS PREPARED BY RICHARD ADAMS (PE35836),
 RICHARD ADAMS ENGINEERS & CONSULTANTS, INC (CA35836) -
 ALL PAGES IN PROJECTDOX INCLUDE A VALID DIGITAL
 SIGNATURE/SEAL
  
 ELECTRICAL SHEETS PREPARED BY MATTHEW OTTO (PE58722),
 OTTO ENGINEERING, INC. (CA27523) - ALL PAGES IN
 PROJECTDOX INCLUDE A VALID DIGITAL SIGNATURE/SEAL
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-02-19 Cont ID  
Sent By shill Date 2016-02-19 Time 09:42 Rev Time 0.00
Received By shill Date 2016-02-18 Time 09:42 Sent To  
Notes
2016-02-19 08:41:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ACTIONS REQUIRED:
  
 AFTER MECHANICAL REVIEW IS PASSED, MECHANICAL SHEETS
 DIGITAL SIGNATURE WILL BE REVIEWED (PREPARED BY DANA
 TENNILL, PE55301), TENNILL & ASSOCIATES, INC (CA30058)
 SUPPORTING DOCUMENTS MECHANICAL LOAD CALCS PREPARED BY
 DANA TENNILL, PE DIGITAL SIGNATURE WILL BE REVIEWED
 AFTER MECHANICAL REVIEW IS COMPLETE
 SUPPORTING DOCUMENTS MECHANICAL COMPLIANCE CERTIFICATE
 PREPARED BY DANA TENNILL, PE DIGITAL SIGNATURE WILL BE
 REVIEWED AFTER MECHANICAL REVIEW IS COMPLETE
  
 2. SIGNATURE DOCUMENTS TO BE PASSED WITH PROVISO:
  
 CIVIL SHEETS PREPARED BY ADAM SWANEY (PE72235),
 ENGENUITY GROUP, INC. CA7095) - FILES IN PROJECTDOX DO
 NOT HAVE A VALID SIGNATURE BUT RECEIVED C102-C105 VIA
 EMAIL, SIGNATURES CONFIRMED,SENT VIA EMAIL TO CPUELL &
 LEMARCHANT AFTER C101 IS RECEIVED)
 PROVISO - ENGENUITY GROUP CA7095 TO REVISE TITLE BLOCK
 TO INCLUDE BUSINESS LICENSE NUMBER
 PROVISO - SHEET C101 DOES NOT HAVE A VALID DIGITAL
 SIGNATURE, SEND VIA EMAIL
  
 ARCHITECTURAL SHEETS PREPARED BY LOUIS VANDELOECHT
 (AR95072), GMA ARCHITECTS (C OF A PENDING) - DIGITALLY
 SIGNED & SEALED SIGNATURE DOCUMENTS SENT VIA EMAIL TO
 CPUELL & LEMARCHANT
 PROVISO - OBTAIN CERTIFICATE OF AUTHORIZATION, NOTIFY
 VIA EMAIL WHEN ISSUED BY THE FLORIDA BOARD OF
 ARCHITECTS)
  
 SUPPORTING DOCUMENTS BUILDING ENVELOPE COMCHECK
 PREPARED BY LOUIS VANDELOECHT ARCHITECT IS NOT SIGNED
 AND SEALED AS REQUIRED BY FS481 AND IS INCOMPLETE.
 PROVISO - SEND DIGITALLY SIGNED COMPLETE DOCUMENT VIA
 EMAIL WITHIN 5 WORKING DAYS TO [email protected]
  
 3. SIGNATURE DOCUMENTS SUBMITTED AND PASSED:
  
 STRUCTURAL SHEETS PREPARED BY RICHARD ADAMS (PE35836),
 RICHARD ADAMS ENGINEERS & CONSULTANTS, INC (CA35836) -
 ALL PAGES IN PROJECTDOX INCLUDE A VALID DIGITAL
 SIGNATURE/SEAL
  
 ELECTRICAL SHEETS PREPARED BY MATTHEW OTTO (PE58722),
 OTTO ENGINEERING, INC. (CA27523) - ALL PAGES IN
 PROJECTDOX INCLUDE A VALID DIGITAL SIGNATURE/SEAL
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By shill Date 2016-02-17 Time 09:24 Rev Time 0.00
Received By shill Date 2016-02-16 Time 09:24 Sent To  
Notes
2016-02-17 09:24:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CONTRACTOR IS TO CONFIRM ALL SIGNATURE DOCUMENTS PRIOR
 TO SUBMITTAL.
  
 1. 2/17/16 SOILS REPORT PREPARED BY JAIME VALEZ
 (PE66416), DUNKELBERGER (6870); UNABLE TO LOCATE THE
 ENGINEERING BUSINESS LICENSE NUMBER ON THE REPORT, SEE
 FAC61G15-23, WWW.FBPE.ORG. PLEASE INCLUDE. PLEASE
 UPLOAD AS A RESUBMITTAL (SAME NAME AS ORIGINAL SOILS
 REPORT FILE).
  
 2. CIVIL SHEETS HAVE THE FOLLOWING ERRORS:
 C101 IS NOT DIGITALLY SIGNED AND SEALED.
 C102, C103 SEAL IS INVALID.
 OTHER SHEETS NOT CHECKED. CONTRACTOR IS TO VERIFY VALID
 SIGNATURE OF ALL SHEETS PRIOR TO SUBMITTAL OF SIGNATURE
 DOCUMENTS.
 CIVIL SHEETS LACK A TITLE BLOCK IN ACCORDANCE WITH
 FAC61G-15.
  
 3. FIRE PROTECTION SHEET NOT SIGNED AND SEALED. NO
 ACTION REQUIRED; THIS SHEET HAS BEEN MARKED "FOR
 REFERENCE ONLY" (WORK IS UNDER A SEPARATE ISSUED
 PERMIT)
  
 4. 2/17/16 SHEETS PREPARED BY LOUIS VANDELOECHT
 (AR95072), GMA ARCHITECTS, INC (C OF A PENDING) - OK
 WITH PROVISOS:
 OBTAIN CERTIFICATE OF AUTHORIZATION
 PAGE A6.3 ON INDEX PAGE WAS NOT SUBMITTED, PER
 APPLICANT THE INDEX IS INCORRECT. ARCHITECT TO REVISE
 HIS PLAN TO REMOVE THIS SHEET FROM INDEX. (EMAIL FROM
 ARCHITECT CONFIRMING THAT THIS SHEET WAS INCLUDED ON
 INDEX IN ERROR WAS ROUTED TO RECORDS)
  
 5. REVISED MECHANICAL SHEETS TO BE RESUBMITTED WITH
 REVISED TITLE BLOCK INFORMATION.
  
 6. "BUILDING ENVELOPE COMCHECK" LACK A DIGITAL
 SIGNATURE (ARCHITECT). PLEASE UPLOAD TO PROJECTDOX.
  
 7. "MECHANICAL ENERGY COMPLIANCE FORM" IS SIGNED BY
 "TIM SCHAEFFER PE". THIS DESIGN PROFESSIONAL'S NAME
 DOES NOT APPEAR ON ANY OF THE CONSTRUCTION DOCUMENTS,
 AND THIS DOCUMENT LACKS THE INFORMATION REQUIRED BY
 FAC61G15-23. IF THIS IS DELEGATED ENGINEERING, ENGINEER
 OF RECORD IS TO REVIEW THIS DOCUMENT, SEE FAC61G-15.
  
 8. "MECHANICAL LOAD CALCULATIONS" STATES THAT THEY ARE
 PREPARED BY ICON MECHANICAL, AND THERE IS NO TITLE
 BLOCK FOR MR. TENNILL.
  
 THE FOLLOWING DESIGN PROFESSIONALS SIGNATURE DOCUMENTS
 ARE IN COMPLIANCE WITH FAC61G15:
  
 9. STRUCTURAL SHEETS, RICHARD ADAMS (PE35836), RICHARD
 ADAMS ENGINEERS & CONSULTANTS, PA (7565) - OK
  
 10. ELECTRICAL SHEETS, MATTHEW OTTO (PE58722), OTTO
 ENGINEERING, INC. (27523) - OK
  
  
2016-02-16 09:24:16SHILL WORKING ON

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2016-02-10 Cont ID  
Sent By shill Date 2016-02-10 Time 11:48 Rev Time 0.00
Received By shill Date 2016-02-10 Time 11:48 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2016-02-08 Cont ID  
Sent By shill Date 2016-02-08 Time 16:49 Rev Time 0.00
Received By shill Date 2016-02-08 Time 16:49 Sent To  
Notes
2016-02-08 16:50:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVIDE A RESUME FOR THE CONTRACTOR SHOWING EXPERIENCE
 WITH THIS TYPE OF CONSTRUCTION, FBC 107.
  
 THIS MAY BE SUBMITTED MID-REVIEW.
  
 (RESIDENT INSPECTOR AGREEMENT AND INSPECTOR INFORMATION
 RECEIVED, APPROVED BY K.CONRAD AND ROUTED TO RECORDS)

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By shill Date 2016-01-26 Time 18:01 Rev Time 0.00
Received By shill Date 2016-01-26 Time 18:01 Sent To  
Notes
2016-01-26 18:02:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PER APPLICANT, RESIDENT INSPECTOR WILL BE LOU PERINI,
 TERRACON.
  
 PROVIDE A COMPLETED RESIDENT INSPECTOR AGREEMENT AND
 SUBMIT. ALSO SUBMIT INSPECTOR INFORMATION (ALL
 INSPECTORS PROPOSED).
  
 PROVIDE A RESUME FOR THE CONTRACTOR SHOWING EXPERIENCE
 WITH THIS TYPE OF CONSTRUCTION, FBC 107.
  
 THIS MAY BE SUBMITTED MID-REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2016-02-05 Cont ID  
Sent By jroach Date 2016-02-05 Time 16:27 Rev Time 0.00
Received By jroach Date 2016-02-05 Time 16:26 Sent To  
Notes
2016-02-05 16:28:58PROVISOS
  
 LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED
 BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
  
 PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT,
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE
 LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE,
 SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT
 COULD BE IMPACTED BY TREE ROOTS.
  
 PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON THE
 PROPERTY, A TREE ALTERATION PERMIT SHALL BE SUBMITTED,
 REVIEWED AND APPROVED BY THE DEVELOPMENT SERVICES
 DEPARTMENT - PLANNING DIVISION.
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY FOR
 THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL:
  
 A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
 B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE
 SITE.
 C. THE SITE PLAN SHALL BE REVISED TO ACCURATELY REFLECT
 THE CONDITIONS NORTH OF THE DUMPSTER, THE PROPOSED
 PARKING, AND EXPSNSION OF THE LANDSCAPE ISLAND.
  
 ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE
 PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY
 ACCESS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2016-02-04 Cont ID  
Sent By jroach Date 2016-02-04 Time 09:42 Rev Time 0.00
Received By jroach Date 2016-02-04 Time 09:42 Sent To  
Notes
2016-02-04 09:44:57ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.04.2016
 PERMIT NO.: 15110707
 ADDRESS: 1300 ALLENDALE ROAD
 CONTRACTOR/CONTACT: DAN BERCOT
 TELEPHONE NO.: 314.963.0715
 SCOPE OF REVIEW: 28,775 SQUARE FOOT EXPANSION TO
 EXISTING WAREHOUSE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE ARCHITECTURAL SITE PLAN (SHEET A1.1) DOES NOT
 MATCH THE SITE PLAN THAT WAS INCLUDED IN THE IPD
 APPLICATION:
  
  A. THE SITE PLAN SUBMITTED AS PART OF THE IPD
 APPLICATION PROVIDED FOR A 30 FOOT SETBACK FROM THE
 PROPERTY LINE. ALL WAIVERS APPROVED ARE BASED UPON THIS
 SETBACK. ONCE THE IPD IS APPROVED, THE PROPOSED
 ADDITION CANNOT BE ANY CLOSER THAN 30 FEET UNLESS A
 MAJOR AMENDMENT TO THE IPD IS SUBMITTED.
  
  B. THE SITE PLAN SUBMITTED AS PART OF THE IPD
 APPLICATION IDENTIFIED THE AREA NORTH OF DUMPSTER AS
 FOUR (4) PARKING SPACES...THIS ENTIRE AREA DIFFERS
 BETWEEN SHEETS A1.1 AND SP-1.
  
 2. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED
 BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
  
 WHILE THEY DO NOT AFFECT THE ISSUANCE OF A BUILDING
 PERMIT, PLEASE TAKE NOTE OF THE FOLLOWING:
  
 1. ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE
 PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY
 ACCESS.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT - PLANNING DIVISION.
  
 3. PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT,
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE
 LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE,
 SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT
 COULD BE IMPACTED BY TREE ROOTS.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL:
  
  A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
  B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE
 SITE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By jroach Date 2015-12-09 Time 16:38 Rev Time 0.00
Received By jroach Date 2015-12-09 Time 16:38 Sent To  
Notes
2015-12-09 16:39:57ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.09.2015
 PERMIT NO.: 15110707
 ADDRESS: 1300 ALLENDALE ROAD
 CONTRACTOR/CONTACT: DAN BERCOT
 TELEPHONE NO.: 314.963.0715
 SCOPE OF REVIEW: 28,775 SQUARE FOOT EXPANSION TO
 EXISTING WAREHOUSE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, THE
 APPLICATION FOR AN INDUSTRIAL PLANNED DEVELOPMENT (IPD)
 SHALL BE APPROVED BY THE CITY COMMISSION. THIS IS
 TENTATIVELY SCHEDULED FOR PRESENTATION TO THE
 COMMISSION ON 1/4/2015 AND 1/19/2015.
  
 2. A CURRENT/ACCURATE SURVEY SHALL BE PROVIDED.
  
 3. A SITE PLAN SHALL BE PROVIDED THAT INCLUDES THE
 FOLLOWING:
  
  A. VICINITY MAP SHOWING THE PROPERTY IN RELATION TO
 THE SURROUNDING AREA.
  
  B. SETBACK DIMENSIONS FROM ALL SIDES OF THE BUILDING
 TO ADJACENT PROPERTY LINES.
  
  C. LOCATION AND DIMENSIONS OF ALL PERIMETER TREATMENT
 (SIDEWALKS, FENCES, WALLS, OR BERMS).
  
  D. LOCATION AND SCREENING OF ALL GARBAGE RECEPTACLES.
  
  E. STANDARD CITY DETAILS OF PARKING (SMALL CAR,
 HANDICAP SPACE, STANDARD SPACE), HANDICAP RAMPS,
 DRIVEWAYS, DUMPSTERS AND SIGNS.
  
  F. DIMENSIONS OF ALL PARKING ROW, DRIVE AISLES,
 LANDSCAPE BUFFERS, WALKWAYS, ETC.
  
  G. SUPPLY A DATA TABLE IN THE FOLLOWING FORMAT:
  
  I. EXISTING/PROPOSED LAND USE AND ZONING.
  II. TOTAL ACRES OF THE PROJECT.
  III. TOTAL GROSS BUILDING SQUARE FOOTAGE.
  IV. PERCENT OF OPEN SPACE, LANDSCAPING, BUILDING
 COVERAGE & IMPERMEABLE SURFACE.
  V. ACRES AND PERCENT OF WATER BODIES.
  VI. DENSITY AND NUMBER OF DWELLING UNITS
 (RESIDENTIAL).
  VII. PARKING COMPUTATIONS (PARKING REQUIRED,
 PROVIDED, ETC.)
  VIII. FLOOR AREA RATIO (FAR).
  
 4. THE ARCHITECTURAL SITE PLAN (SHEET A1.1) DOES NOT
 MATCH THE SITE PLAN THAT WAS INCLUDED IN THE IPD
 APPLICATION:
  
  A. THE SITE PLAN SUBMITTED AS PART OF THE IPD
 APPLICATION PROVIDED FOR A 30 FOOT SETBACK FROM THE
 PROPERTY LINE. ALL WAIVERS APPROVED ARE BASED UPON THIS
 SETBACK. ONCE THE IPD IS APPROVED, THE PROPOSED
 ADDITION CANNOT BE ANY CLOSER THAN 30 FEET UNLESS A
 MAJOR AMENDMENT TO THE IPD IS SUBMITTED.
  
  B. THE SITE PLAN SUBMITTED AS PART OF THE IPD
 APPLICATION IDENTIFIED THE AREA NORTH OF DUMPSTER AS
 FOUR (4) PARKING SPACES, THESE ARE NOT SHOWN ON SHEET
 A1.1.
  
  C. THE LAYOUT OF THE PARKING LOT DIFFERS BETWEEN THE
 SITE PLAN SUBMITTED AS PART OF THE IPD APPLICATION AND
 SHEET A1.1, WHICH WAS SUBMITTED WITH THE BUILDING
 PERMIT APPLICATION.
  
 5. LANDSCAPE PLANS SHALL BE SUBMITTED UNDER A SEPARATE
 LANDSCAPE PERMIT APPLICATION, AND SHALL BE ACCOMPANIED
 BY A CERTIFIED COST ESTIMATE (MATERIAL + LABOR).
  
 6. DETAILS SHALL BE PROVIDED FOR BIKE RACKS AND THEIR
 LOCATION SHALL BE IDENTIFIED ON THE SITE PLAN.
  
 7. PHOTOMETRIC PLAN SHALL BE PROVIDED FOR ALL OUTDOOR
 ILLUMINATION.
  
 8. AN APPLICATION FOR A UNITY OF TITLE SHALL BE
 SUBMITTED TO THE CITY?S PUBLIC WORKS DEPARTMENT ?
 ENGINEERING DIVISION, AND SUCH UNITY OF TITLE SHALL BE
 RECORDED IN THE PUBLIC RECORDS OF PALM BEACH COUNTY,
 FOR ALL REAL PROPERTY CONTAINED WITHIN THE IPD. A
 CERTIFIED COPY OF THE RECORDED UNITY OF TITLE SHALL BE
 PROVIDED TO THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION.
  
 WHILE THEY DO NOT AFFECT THE ISSUANCE OF A BUILDING
 PERMIT, PLEASE TAKE NOTE OF THE FOLLOWING:
  
 1. ALL GATES THAT ARE TO BE LOCKED AT ANY TIME SHALL BE
 PROVIDED WITH A KNOX PADLOCK FOR 24-HOUR EMERGENCY
 ACCESS.
  
 2. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT - PLANNING DIVISION.
  
 3. PRIOR TO THE ISSUANCE OF THE LANDSCAPE PERMIT,
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS SHALL BE SHOWN ON THE
 LANDSCAPE PLAN. THIS INCLUDES WATER, SEWER, DRAINAGE,
 SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT
 COULD BE IMPACTED BY TREE ROOTS.
  
 4. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE NEW WAREHOUSE BUILDING, THE APPLICANT SHALL:
  
  A. PROVIDE SCREENING FOR ANY NEW GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
  B. REMOVE ALL INVASIVE EXOTIC PLANTS FROM THE ENTIRE
 SITE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved