| 2016-01-07 05:04:51 | 1) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU |
| | LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 113,000 |
| | BTU'S.THE 648M IS OBVIOUSLY WRONG. DELETE THIS NOTE |
| | FROM THE PLANS. |
| | 2) THERE IS A NOTE ON THE PLAN STATING THE TOTAL RUN IS |
| | 100 FT. BUT THE RISER SHOWS A TOTAL RUN OF 75 FT. WHICH |
| | IS IT? I CANNOT CHECK PIPE SIZES UNTIL THE CORRECT |
| | DEVELOPED LENGTH IS PLACED ON THE PLAN. CLARIFY. |
| | 3) THE DESCRIPTION OF WORK ON THE APPLICATION INCLUDES |
| | A BBQ AND A POOL HEATER. THESE APPLIANCES ARE NOT SHOWN |
| | ON THE RISER. REMOVE THEM FROM THE DESCRIPTION OF WORK |
| | ON THE PERMIT APPLICATION IF THEY ARE NOT BEING |
| | INSTALLED OR SHOW THE FUTURE OUTLETS AND BTU LOAD ON |
| | THE GAS RISER. |
| | 4) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED |
| | SUPPLYING THE DRYER AND COOKTOP SHALL BE 1" PER TABLE |
| | 402.4 (15). 2014 FUEL GAS CODE. |
| | 5) THERE IS A NOTE ON THE PLAN THAT STATES THE INLET |
| | PRESSURE IS LESS THAN 2 PSI BUT THERE IS A REFERENCE ON |
| | THE PLAN TO GAS TABLE 402.4 (19) WHICH IS FOR A SYSTEM |
| | WITH AN INLET PRESSURE OF 5 PSI. THIS IS OBVIOUSLY |
| | WRONG.REFER TO THE CORRECT GAS TABLE FROM THE 2014 FUEL |
| | GAS CODE FOR THIS SYSTEM. |
| | 6) THE PLANS ALSO REFER TO PE (POLYETHELYNE) PIPE.THERE |
| | IS NO PE PIPE SHOWN ON THE RISER.PE PIPE CAN ONLY BE |
| | INSTALLED OUTSIDE UNDERGROUND. EITHER SHOW THE PIPE AND |
| | LENGTH OF THE SECTION OR DELETE THIS NOTE FROM THE |
| | PLAN. |
| | 7) THE 1/2" GALVANIZED LINE TO THE COOKTOP MAY BE |
| | UNDERSIZED PER 2014 FGC TABLE 402.4 (2) DEPENDING ON |
| | THE DISTANCE OF THE TOTAL DEVELOPED LENGTH. |
| | 8) SUBMIT A LEGIBLE GAS VENT DETAIL FOR REVIEW. SUBMIT |
| | DETAILS FOR THE VENT FOR THE WATER HEATER IN THE |
| | GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF PENETRATION |
| | AND HOW IT IS TO BE SEALED AT THE ROOF PENETRATION, |
| | ETC. COMPLY WITH FGC SECS. 502 & 503. |
| | 9) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR |
| | ALL THE GAS APPLIANCES.WPB AMEND. TO FBC SEC. 107.1, |
| | ALL APPLIANCES SHALL BE LISTED AND LABELED PER 2014 FBC |
| | SEC.301.3. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |