Plan Review Details - Permit 15110671
Plan Review Stops For Permit 15110671
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2016-01-29 Cont ID  
Sent By tklarge Date 2016-01-29 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-01-29 Time 05:59 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-01-07 Cont ID  
Sent By tklarge Date 2016-01-07 Time 06:34 Rev Time 0.00
Received By tklarge Date 2016-01-07 Time 05:18 Sent To  
Notes
2016-01-07 06:20:011) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS.IT
 APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC. 107.1, ALL APPLIANCES SHALL BE LISTED AND
 LABELED PER 2014 FBC FUEL GAS CODE SEC.301.3.
 2) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL
 BE 1 1/4" PER TABLE 402.4(15) OF THE FGC.THIS LINE
 SUPPLIES THE DRYER, COOKTOP, AND SUMMER KITCHEN.
 3) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE
 402.4 (21) FGC.
 4) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS
 TABLE IS FOR SCH. 40 METALLIC PIPE. THE CORRECT TABLE
 FROM THE GAS CODE FOR PE PIPE IS TABLE 402.4 (21). NOTE
 THIS ON THE PLANS.
 5) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT SHOW
 THAT THE RANGE IS LISTED OR LABELED PER FUEL GAS CODE
 SEC. 301.3. THE SUBMITTED DOCUMENT IS NOTHING MORE THAN
 AN INTERNET SALES SHEET.SUBMIT 2 COPIES OF
 SPECIFICATIONS THAT SHOW THAT THIS APPLIANCE IS LISTED
 AND LABELED.
 6) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL
 BE ONSITE FOR THE INSPECTOR PER THE 2014 FGC SEC.305.1.
 7) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN
 THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF
 PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF
 PENETRATION, ETC. THE PRINTING ON THE DETAIL IS ALSO
 TOO SMALL TO READ.WPB AMEND. TO FBC SEC. 107.2.1, FGC
 SEC. 502 & 503.
 8) THERE IS A NOTE ON THE PLAN STATING THE TOTAL BTU
 LOAD IS 648,000 BTU'S AND THE TABLE SHOWS 568,000
 BTU'S.THE 648M IS OBVIOUSLY WRONG. DELETE THIS NOTE
 FROM THE PLANS.
 9) THERE IS A NOTE ON THE PLAN THAT STATES THE INLET
 PRESSURE IS LESS THAN 2 PSI BUT THERE IS A REFERENCE ON
 THE PLAN TO GAS TABLE 402.4 (19) WHICH IS FOR A SYSTEM
 WITH AN INLET PRESSURE OF 5 PSI. THIS IS OBVIOUSLY
 WRONG.REFER TO THE CORRECT GAS TABLE FROM THE 2014 FUEL
 GAS CODE FOR THIS SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By tklarge Date 2015-11-19 Time 06:38 Rev Time 0.00
Received By tklarge Date 2015-11-19 Time 06:10 Sent To  
Notes
2015-11-19 06:25:091) SHOW THE EHD NUMBER OF THE CSST FOR EACH PIPE SIZE
 BEING USED.WPB AMENDMENTS TO FBC SEC. 107.2.1.
 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES LOCATED ON THE INTERIOR OF THE STRUCTURE.
 COMPLY W/2010 FBC-RESIDENTIAL SEC.G2407.1 & G2407.5
 THROUGH G2407.11.
 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS.IT
 APPEARS ONLY ONE COPY HAS BEEN SUBMITTED. WPB AMEND. TO
 FBC SEC. 107.1, ALL APPLIANCES SHALL BE LISTED AND
 LABELED PER 2014 FBCR SEC.G2404.3.
 4) THE 1/2 " GALVANIZED DROP TO THE SUMMER KITCHEN
 SHALL BE 3/4". TABLE 402.4(2) FGC.
 5) THE 1/2" CSST TO THE SUMMER KITCHEN SHALL BE 3/4".
 TABLE 402.4(15) FGC.
 6) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL
 BE 1". TABLE 402.4(15) FGC.
 7) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE
 402.4 (21) FGC.
 8) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS
 TABLE IS FOR SCH. 40 METALLIC PIPE. INDICATE THE
 CORRECT SIZING TABLES FOR ALL THE DIFFERENT TYPE OF
 PIPE MATERIAL ON THE PLANS.
 9) IF ANY MP REGULATORS ARE GOING TO BE INSTALLED, SHOW
 THE LOCATION ON THE PLANS AND LIST THE CORRECT SIZING
 TABLE FOR THE SYSTEM.
 10) THE BTU LOAD OF THE APPLIANCES ON THE GAS TABLE DO
 NOT CORRELATE WITH THE RISER DIAGRAM. CLARIFY.
 11) THE SUBMITTED DOCUMENT FOR GAS COOKTOP DOES NOT
 SHOW THAT THE RANGE IS LISTED OR LABELED PER 2010
 FBC-RES. SEC. G2404.3. THE SUBMITTED DOCUMENT IS
 NOTHING MORE THAN AN INTERNET SALES SHEET.
 12) THE INSTALLATION MANUALS FOR ALL GAS EQUIPMENT
 SHALL BE ONSITE FOR THE INSPECTOR PER THE 2010 FBC-RES.
 SEC. G 2408.1.
 13) SUBMIT DETAILS FOR THE VENT FOR THE WATER HEATER IN
 THE GARAGE. INDICATE VENT TYPE, DIAMETER, ROOF
 PENETRATION AND HOW IT IS TO BE SEALED AT THE ROOF
 PENETRATION, ETC. COMPLY WITH 2010 FBC-RES.SECS.G2426 &
 G2427.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-29 Cont ID  
Sent By tklarge Date 2016-01-29 Time 06:49 Rev Time 0.00
Received By tklarge Date 2016-01-27 Time 13:49 Sent To  
Notes
2016-01-28 13:49:28RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-07 Cont ID  
Sent By tklarge Date 2016-01-07 Time 06:34 Rev Time 0.00
Received By tklarge Date 2016-01-06 Time 09:03 Sent To  
Notes
2016-01-06 09:03:54RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By tklarge Date 2015-11-19 Time 06:38 Rev Time 0.00
Received By tklarge Date 2015-11-16 Time 09:40 Sent To  
Notes
2015-11-18 09:41:09PLUMB <5K