Plan Review Details - Permit 15110667
Plan Review Stops For Permit 15110667
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-11 Cont ID  
Sent By cthroop Date 2015-12-11 Time 13:13 Rev Time 0.00
Received By cthroop Date 2015-12-11 Time 13:13 Sent To  
Notes
2015-12-11 14:39:45CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW. YOU MAY CHOOSE TO SEND ME RESPONSES TO THESE
 COMMENTS VIA E-MAIL.
 PROVIDE BEARING CAPACITY OF EXISTING FOUNDATION.
 PROVIDE DETAIL (SECTIONAL VIEW) OF EXTERIOR WALL.
 PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOOR.
 PROVIDE WIND SPEED DESIGN CALCS. BASED ON EXSPOSURE
 CATEGORY.
  
  
 1709.1 GENERAL.
 WHENEVER THERE IS A REASONABLE DOUBT AS TO THE
 STABILITY OR LOAD-BEARING CAPACITY OF A COMPLETED
 BUILDING, STRUCTURE OR PORTION THEREOF FOR THE EXPECTED
 LOADS, AN ENGINEERING ASSESSMENT SHALL BE REQUIRED. THE
 ENGINEERING ASSESSMENT SHALL INVOLVE EITHER A
 STRUCTURAL ANALYSIS OR AN IN-SITU LOAD TEST, OR BOTH.
 THE STRUCTURAL ANALYSIS SHALL BE BASED ON ACTUAL
 MATERIAL PROPERTIES AND OTHER AS-BUILT CONDITIONS THAT
 AFFECT STABILITY OR LOAD-BEARING CAPACITY, AND SHALL BE
 CONDUCTED IN ACCORDANCE WITH THE APPLICABLE DESIGN
 STANDARD. IF THE STRUCTURAL ASSESSMENT DETERMINES THAT
 THE LOAD-BEARING CAPACITY IS LESS THAN THAT REQUIRED BY
 THE CODE, LOAD TESTS SHALL BE CONDUCTED IN ACCORDANCE
 WITH SECTION 1709.2. IF THE BUILDING, STRUCTURE OR
 PORTION THEREOF IS FOUND TO HAVE INADEQUATE STABILITY
 OR LOAD-BEARING CAPACITY FOR THE EXPECTED LOADS,
 MODIFICATIONS TO ENSURE STRUCTURAL ADEQUACY OR THE
 REMOVAL OF THE INADEQUATE CONSTRUCTION SHALL BE
 REQUIRED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW, AND DOOR SUBMITTALS.
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By skennedy Date 2015-11-20 Time 10:08 Rev Time 0.00
Received By skennedy Date 2015-11-20 Time 10:08 Sent To  
Notes
2015-11-20 10:19:181ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLEASE PROVIDE AN ELECTRICAL PLAN PER FBC 107 TO
 DEMONSTRATE THE EXISTING ELECTRICAL SYSTEM CAN
 ACCOMODATE THE ADDED LOAD FOR NEW ELECTRICAL
 INSTALLATIONS AND SHOW THE PROPOSED LOCATION OF
 ELECTRICAL DEVICES. PROVIDE AN ELECTRICAL PANEL
 SCHEDULE. DEMONSTRATE COMPLIANCE WITH THE FOLLOWING:
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM IF APPLICABLE.
  
 E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT
 LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL
 ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED
 GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. A
 VEHICLE DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN
 OUTDOOR EGRESS DOOR. WHERE ONE OR MORE LIGHTING OUTLETS
 ARE INSTALLED FOR INTERIOR STAIRWAYS, THERE SHALL BE A
 WALL SWITCH AT EACH FLOOR LEVEL AND LANDING LEVEL THAT
 INCLUDES AN ENTRYWAY TO CONTROL THE LIGHTING OUTLETS
 WHERE THE STAIRWAY BETWEEN FLOOR LEVELS HAS SIX OR MORE
 RISERS.
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-11 Cont ID  
Sent By cthroop Date 2015-12-11 Time 13:13 Rev Time 0.00
Received By cthroop Date 2015-11-16 Time 09:36 Sent To  
Notes
2015-11-18 09:37:15R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By skennedy Date 2015-11-20 Time 11:21 Rev Time 0.00
Received By skennedy Date 2015-11-20 Time 11:21 Sent To  
Notes
2015-11-20 11:28:321ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By skennedy Date 2015-11-20 Time 10:30 Rev Time 0.00
Received By skennedy Date 2015-11-20 Time 10:30 Sent To  
Notes
2015-11-20 11:21:351ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLEASE PROVIDE A MECHANICAL PLAN PER FBC 107 TO SHOW
 DRYER VENTING DETAILS AND ANY PROPOSED MODIFICATIONS TO
 THE HVAC SYSTEM. ADDITIONALLY, PLEASE PROVIDE AN ENERGY
 SUBMITTAL AND SHOW COMPLIANCE WITH THE FOLLOWING:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBCR-M1502.4 DRYER EXHAUST DUCTS.
 DRYER EXHAUST DUCTS SHALL CONFORM TO THE REQUIREMENTS
 OF SECTIONS M1502.4.1 THROUGH M1502.4.6.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By gjohnson Date 2015-11-20 Time 13:39 Rev Time 0.00
Received By gjohnson Date 2015-11-20 Time 13:39 Sent To  
Notes
2015-11-20 13:43:521ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PLEASE PROVIDE PLUMBING RISER DIGRAM.
 PERWPB AMEND. TO FBC SEC 107.3.5.3(11)

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-04 Cont ID  
Sent By sgraham Date 2015-12-04 Time 16:09 Rev Time 0.00
Received By sgraham Date 2015-12-04 Time 16:09 Sent To  
Notes
***NONE***