| 2015-11-24 09:08:38 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110637 |
| | ADD: 325 CLEMATIS ST. 1ST & 2ND FLOOR ALTERATIONS. |
| | CONT: MAC ENTERPRISES |
| | TEL: 561-236-3627 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: TUES. NOV. 24/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET T.1 : |
| | 1A) THE COVERSHEET NOR DOES THE LIFE SAFETY PLAN |
| | INDICATE TO WHAT CODES THIS PROJECT WAS DESIGNED TOO? |
| | THE 2014 FBC FAMILY OF CODES WAS ADOPTED STATEWIDE ON |
| | JUNE 30/ 2015. |
| | |
| | 1B) UNDER THE 2014 FL. EXISITING BUILDING CODE THE |
| | DESIGNER OF RECORD HAS NOT DECLARED UNDER WHICH |
| | COMPLIANCE METHOD THE PLANS WERE DEVELOPED. 2014 FL. |
| | EXISTING BUILDING CODE 301.1. |
| | |
| | 1C) THE COVERSHEET INDICATES UNDER A NOTE SPRINKLERS |
| | NOT APPLICABLE, I TAKE IT THIS BUILDING IS NOT FIRE |
| | SPRINKLERED NOR IS IT PLANNED TO BE IN THIS SCOPE OF |
| | WORK. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1D) THE COVERSHEET INDICATES THE 1ST FLOOR A TO BE A |
| | FUTURE 1ST FLOOR BUSINESS AND 2ND FLOOR FUTURE ASSEMBLY |
| | OCCUPANCY. TYPE OF ASSEMBLY OCCUPANCY A1, A2 OR A3 IS |
| | UNKNOWN. PLEASE REVIEW THE 2014 FBC-B TABLE 503 WILL |
| | NOT ALLOW ANY ASSEMBLY OCCUPANCY ON THE 2ND FLOOR IN A |
| | BUILDING TYPE VB-UNSPRINKLERED. THE OTHER ISSUE IS THE |
| | ALLOWABLE AREA FOR AN ASSEMBLY OCCUPANCY IN A TYPE VB |
| | UNSPRINKLERED BUILDING IS OVER THE ALLOWABLE AREA, |
| | AGAIN SEE TABLE 503.FBC-B . |
| | |
| | 1E) THE COVERSHEET VERSES THE LIFE SAFETY SHEET LS.1. |
| | THE QUESTION IS THE BUSINESS AND ASSEMBLY OCCUPANCIES |
| | ON THE COVER SHEET REVERSED TO WHAT FLOOR THEY ARE |
| | LOCATED? LS.1 APPEARS ON THE 1ST FLOOR TO HAVE A FRONT |
| | THAT OPENS ONTO CLEMATIS ST. THAT WOULD BE MORE SUITED |
| | FOR THE ASSEMBLY OCCUPANCY. IF SO PLEASE PROVIDE THE |
| | LEASABLE SQUARE FOOT AREA FOR THE TENANT SPACE. THE |
| | OTHER ISSUE THAT NEEDS ADDITIONAL INFORMATION IS THE |
| | MEZZANINE, THE PLANS SHEET A1 INDICATE THAT THE |
| | MEZZANINE IS USED FOR MECHANICAL ROOM OR IS THE |
| | MECHANICAL ROOM LOCATED ABOVE THE MEZZANINE ROOM? AND |
| | DOES THE MECHANICAL SYSTEM OPERATE FOR THE WHOLE |
| | BUILDING? |
| | |
| | 1F) DISCREPANCY IN PLANS THE COVERSHEET INDICATES THE |
| | 2ND FLOOR AS AN ASSEMBLY OCCUPANCY WHEREAS SHEET S-1.1 |
| | THE 2ND FLOOR STRUCTURAL SHEET INDICATES THE 2ND FLOOR |
| | LIVE LOAD AS 80 LBS. FBC-B TABLE 1607.1 LIVE LOADS FOR |
| | ASSEMBLY MOVABLE SEATS IS 100 LBS. WHEREAS OFFICE |
| | CORRIDORS IS 80 LBS./ PSF. |
| | |
| | 1G) THE COVERSHEET T.1 DOES NOT INDICATE IF THE 2 |
| | FLOORS ARE GOING TO BE UNDER THE CONTROL OF A SINGLE |
| | TENANT OR IF THERE ARE GOING TO BE (2) SEPERATE TENANTS |
| | THAT WILL SHARE BACK OF HOUSE RESTROOMS AND OTHER |
| | COMMON ELEMENTS? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED FOR A THOROUGH REVIEW. |
| | |
| | 1H) NEITHER THE COVERSHEET T.1 NOR LS.1 SHOW PROPOSED |
| | OCCUPANT LOADS FOR EACH FLOOR NOR DOES THE STAIRWELLS |
| | AND DOORS SHOW THE OCCUPANT LOAD ALLOWABLE OCCUPANT |
| | LOAD PER FBC-B 1005.3.1 STAIRWAYS A FACTOR OF 0.3 AND |
| | 1005.3.2 OTHER EGRESS COMPONENTS A FACTOR OF 0.2. |
| | |
| | 1I) THE COVERSHEET T.1 NOR THE LS.1 INDICATE COMPLIANCE |
| | WITH HORIZONTAL OCCUPANCY SEPARATION 2014 FBC-B |
| | 707.3.10 & TABLE 707.3.10. |
| | |
| | 2) SHEET A.1 BACK OF HOUSE WHAT APPEARS TO BE COMMON |
| | AREAS TO BOTH TENANTS. PLEASE PROVIDE A CUT SECTION |
| | THROUGH THE MEZZANINE AREA NORTH TO SOUTH THERE ARE A |
| | LOT OF QUESTIONS IN REGARDS TO THIS AREA. |
| | |
| | 2A) THE REAR STAIRS, IT IS HARD TO TELL IF THIS STAIR |
| | IS BEING DESIGNED AS A ENCLOSED STAIR OR IF THE |
| | DESIGNER IS TRYING TO VIEW THIS STAIR AS A EXIT ACCESS |
| | STAIRWELL (FBC-B 1009.3 & 1016.3.1) OR AS A RATED EXIT |
| | STAIR ( 1022.2). IF DESIGNED AS A EXIT ACCESS STAIR |
| | TRAVEL DISTANCE NEEDS TO BE IN CONFORMANCE WITH FBC-B |
| | 1016.3. |
| | |
| | 2B) THE REAR STAIR WALL RATING IS CLEARLY SHOWN ON THE |
| | 2ND FLOOR AS DARKER AROUND THE 2ND FLOOR CORRIDOR AND |
| | LIGHTER IN THE SOUTH WALL OF THE STAIRWELL. ON THE 1ST |
| | FLOOR THERE APPEARS TO BE NO RATING THAT WOULD SEPARATE |
| | THE STAIRWELL FROM THE 1ST FLOOR TENANT. FBC-B 1022.2). |
| | |
| | 2C) !ST FLOOR BACK OF HOUSE, IF THE REAR STAIR IS TO BE |
| | CONSIDERED A EXIT STAIR (1 HOUR RATED) THEN 3 THINGS |
| | NEED TO HAPPEN: |
| | |
| | 2C)(1) THE REAR EXIT WILL LEAD INTO A EXIT PASSAGE WAY |
| | AND TO THE EXIT DOOR. BETWEEN THE EXIT STAIR WELL AND |
| | EXIT PASSAGE WAY SECTION FBC-B 1022.3.1 EXTENSION. THE |
| | FIRE-RESISTANCE RATING SHALL BE AT LEAST EQUAL TO THAT |
| | REQUIRED FOR THE INTERIOR EXIT STAIRWAY AND RAMP. A |
| | FIRE DOOR ASSEMBLY COMPLYING WITH SECTION 716.5 SHALL |
| | BE INSTALLED IN THE FIRE BARRIER TO PROVIDE A MEANS OF |
| | EGRESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP TO THE |
| | EXIT PASSAGEWAY. OPENINGS IN THE FIRE BARRIER OTHER |
| | THAN THE FIRE DOOR ASSEMBLY ARE PROHIBITED. |
| | PENETRATIONS OF THE FIRE BARRIER ARE PROHIBITED. |
| | |
| | 2C)(2) THE EXIT PASSAGEWAY WILL NEED TO BE SEPARATED |
| | FROM THE ELEVATOR AND REMOVAL OF THE HOUSE PANELS. |
| | 1023.5 OPENINGS AND PENETRATIONS. |
| | EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. EXCEPT |
| | AS PERMITTED IN SECTION 402.8.7, OPENINGS IN EXIT |
| | PASSAGEWAYS OTHER THAN EXTERIOR OPENINGS SHALL BE |
| | LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE EXIT |
| | PASSAGEWAY FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS |
| | FROM THE EXIT PASSAGEWAY. WHERE AN INTERIOR EXIT |
| | STAIRWAY OR RAMP IS EXTENDED TO AN EXIT DISCHARGE OR A |
| | PUBLIC WAY BY AN EXIT PASSAGEWAY, THE EXIT PASSAGEWAY |
| | SHALL ALSO COMPLY WITH SECTION 1022.3.1. ELEVATORS |
| | SHALL NOT OPEN INTO AN EXIT PASSAGEWAY. |
| | |
| | 1023.6 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND |
| | TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE |
| | INCHES (0.010M2). SUCH PENETRATIONS SHALL BE PROTECTED |
| | IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO |
| | PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS. |
| | |
| | 2C)(3) THE 3RD ISSUE IS THERE IS A COLUMN LOCATED IN |
| | THE EXIT PASSAGE WAY OR EXIT ACCESS STAIRWELL AND |
| | MEZZANINE ABOVE. PLEASE PROVIDE THE CLEAR HEIGHT FROM |
| | THE BOTTOM OF THE MEZZANINE LEVEL TO THE TOP OF THE 1ST |
| | FLOOR FINISH FLOOR. SEE FBC-B 1003.2 & 1003.3.1 |
| | HEADROOM. |
| | |
| | 3) THE MEZZANINE LEVEL IS NOT CLEAR AS TO WHERE THE |
| | WALL LINE IS FOR THE MEZZANINE NONE ARE SHOWN. THE |
| | OTHER ISSUE THAT IS UNCLEAR ON THE 2ND FLOOR PLAN |
| | VIEWING THE MEZZANINE LEVEL THE WORDS STATE, INDICATES |
| | MEZZANINE ABOVE, IS THERE 2 MEZZANINES ONE ON THE 1ST |
| | FLOOR AND 1 ON THE 2ND FLOOR? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. THIS AREA MAYNOT BE AN ACTUAL |
| | MEZZANINE BY DEFINITION BUT A 505.3 EQUIPMENT |
| | PLATFORMS. |
| | |
| | EQUIPMENT PLATFORMS IN BUILDINGS SHALL NOT BE |
| | CONSIDERED AS A PORTION OF THE FLOOR BELOW. SUCH |
| | EQUIPMENT PLATFORMS SHALL NOT CONTRIBUTE TO EITHER THE |
| | BUILDING AREA OR THE NUMBER OF STORIES AS REGULATED BY |
| | SECTION 503.1. THE AREA OF THE EQUIPMENT PLATFORM SHALL |
| | NOT BE INCLUDED IN DETERMINING THE FIRE AREA IN |
| | ACCORDANCE WITH SECTION 903. EQUIPMENT PLATFORMS SHALL |
| | NOT BE A PART OF ANY MEZZANINE AND SUCH PLATFORMS AND |
| | THE WALKWAYS, STAIRS, ALTERNATING TREAD DEVICES AND |
| | LADDERS PROVIDING ACCESS TO AN EQUIPMENT PLATFORM SHALL |
| | NOT SERVE AS A PART OF THE MEANS OF EGRESS FROM THE |
| | BUILDING. |
| | |
| | 505.3.1 AREA LIMITATION. |
| | THE AGGREGATE AREA OF ALL EQUIPMENT PLATFORMS WITHIN A |
| | ROOM SHALL BE NOT GREATER THAN TWO-THIRDS OF THE AREA |
| | OF THE ROOM IN WHICH THEY ARE LOCATED. WHERE AN |
| | EQUIPMENT PLATFORM IS LOCATED IN THE SAME ROOM AS A |
| | MEZZANINE, THE AREA OF THE MEZZANINE SHALL BE |
| | DETERMINED BY SECTION 505.2.1 AND THE COMBINED |
| | AGGREGATE AREA OF THE EQUIPMENT PLATFORMS AND |
| | MEZZANINES SHALL BE NOT GREATER THAN TWO-THIRDS OF THE |
| | ROOM IN WHICH THEY ARE LOCATED. |
| | |
| | 4) THE STRUCTURAL SHEETS SHOW A SCOPE OF WORK THAT WILL |
| | REQUIRE A RESIDENT INSPECTOR ON THIS PROJECT. 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR HELICAL PILE |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| | PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| | DEPARTMENT. |
| | FORMS WERE E-MAILED TO: [email protected] |
| | TUES. NOV. 24/ 2015 02:40 PM. |
| | |
| | 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 4E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS |
| | |
| | 5) TO DATE NO SOILS REPORTS WERE SUBMITTED FOR THIS |
| | PROJECT. SHEET S-4.0 NOTE 4 INDICATES THE GEOTECHNICAL |
| | ENGINEER SHALL INSPECT AND REQUIRE TESTING AS NECESSARY |
| | TO ASSURE THAT THE FOUNDATION PILES ARE INSTALLED IN |
| | ACCORDANCE WITH THEIR SPECIFICATIONS AND REPORT ANY |
| | DEVIATIONS TO THE ENGINEER. |
| | 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION FOR ANY |
| | PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM ANY |
| | FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING THE |
| | FOUNDATION AGAINST SETTLEMENT OR LATERAL TRANSLATION. |
| | |
| | 6) SHEET S-1.0 SHOWS A HELICAL PIER BEING INSTALLED |
| | UNDER THE FOUNDATION IN A DOORWAY. THE INSTALLATION OF |
| | THE HELICAL PIER WILL CREATE A POINT LOAD THAT WILL |
| | TRANSFER UPWARDS ON A 45 DEGREE ANGLE, WILL THIS LOAD |
| | TRANSFER INTO THE COLUMNS OR WILL IT TRANSFER THROUGH |
| | THE FOUNDATION & BLOCK WORK AND CRACK THE FLOOR IN THE |
| | DOOR OPENING? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 7) SHEET S-1.0 IN THE SOUTHEAST CORNER OF THE BUILDING |
| | THERE IS A NOTE PRE-ENGINEERED STAIRS BY OTHERS, THERE |
| | IS NO DESIGN CRITERIA FOR LIVE LOADS (FBC-B TABLE |
| | 1604.5) TO BE CARRIED NOR DOE THE NOTE INDICATE CLOSED |
| | RISERS FBC-B 1009.7.5. |
| | |
| | 8) NONE OF THE STRUCTURAL SHEETS,NEITHER ARCHITECTURAL |
| | SHEETS NOR THE MECHANICAL SHEETS SHOW ROOF TOP ACCESS |
| | FOR THE MECHANICAL EQUIPMENT. PLEASE SHOW COMPLIANCE |
| | WITH: |
| | FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR |
| | ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES |
| | REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED |
| | STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 MM), |
| | SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED |
| | MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM |
| | GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES? |
| | LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE |
| | CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES (762 |
| | MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER |
| | THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (33-PERCENT SLOPE). |
| | PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED |
| | ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN |
| | CRITERIA: |
| | 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR |
| | ROOF EDGE NOT LESS THAN 30 INCHES (762 MM). |
| | 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14 |
| | INCHES (356 MM) ON CENTER. |
| | 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN |
| | 6-INCHES (152 MM) DEEP. |
| | 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM) |
| | BETWEEN RAILS. |
| | 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM) |
| | DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND |
| | (136.1 KG) LOAD. |
| | 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE |
| | PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF |
| | WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2). |
| | 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY |
| | APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE |
| | REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610 |
| | MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR |
| | SERVICE PLATFORMS |
| | |
| | 9A) ROOF TOP MECHANICAL EQUIPMENT MAY REQUIRE SCREENING |
| | AS A ZONING REQUIREMENT. ? 1509.6 MECHANICAL EQUIPMENT |
| | SCREENS. |
| | MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| | THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| | ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| | BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| | THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| | SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| | FIRE-RESISTANCE RATING REQUIREMENTS. |
| | |
| | 9B) IF MECHANICAL SCREENS ARE REQUIRED THEN THE |
| | STRUCTURAL MEMBERS WILL BE REQUIRED TO BE ATTACHED TO |
| | THE ROOF FRAMING TO BE PART OF THE MWFRS (MAIN WIND |
| | FORCE RESISTING SYSTEM). |
| | |
| | 10) ROOF TOP MECHANICAL EQUIPMENT WILL NEED TO SHOW |
| | COMPLIANCE WITH: 2014 FBC- ? M- 301.15 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 11) NOTE DEPENDING ON THE 2ND FLOOR EXITING IS TO BE |
| | DEFINED IF IT IS A EXIT ACCESS STAIR OR AS A VERTICAL |
| | EXIT AND EXIT PASSAGE WAY FBC-B 1022.5 PENETRATIONS |
| | ONLY ALLOWS IN EXITS EQUIPMENT, DUCTWORK NECESSARY FOR |
| | INDEPENDENT VENTILATION OR PRESSURIZATION. |
| | |
| | 12) SHEET S-4.0 PROVIDES THE WIND DESIGN CRITERIA, THE |
| | MEAN ROOF HEIGHT IS NOT PROVIDED NEITHER IS THE |
| | PRESSURES FOR COMPONENTS AND CLADDING. |
| | FBC-B 2014 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR |
| | HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | FBC-B 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5) VASD |
| | POSITIVE AND NEGATIVE PRESSURES. |
| | |
| | 13) PRODUCT APPROVALS: COMPONENTS & CLADDING. 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 14) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 15) EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD MAY |
| | REQUEST THE PRODUCT APPROVALS FOR COMPONENTS AND |
| | CLADDING TO BE DEFERRED. 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 16) CHANGE OF OCCUPANCY ASSEMBLY: IMPACT FEES BEFORE A |
| | PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE |
| | PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |