Plan Review Details - Permit 15110575
Plan Review Stops For Permit 15110575
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-04 Cont ID  
Sent By cthroop Date 2016-02-04 Time 13:16 Rev Time 0.00
Received By cthroop Date 2016-02-04 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By shill Date 2015-12-15 Time 13:51 Rev Time 0.00
Received By shill Date 2015-12-15 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 18:39 Rev Time 0.00
Received By shill Date 2015-11-21 Time 18:39 Sent To  
Notes
2015-11-21 18:51:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A1, BUILDING TYPE (PER PERMIT 99010529, SHEET B
 LS1.01) IS TYPE II, 3 HOUR STRUCTURAL ELEMENTS. REVISE
 "CODE INFORMATION".
  
 2. REVISE DETAIL 4-A3 TO SHOW COMPLIANCE WITH FBC 2014
 ACCESSIBILITY 306.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-07 Cont ID  
Sent By mvaldes Date 2016-01-07 Time 10:43 Rev Time 0.00
Received By mvaldes Date 2016-01-07 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By dharvey Date 2015-11-30 Time 13:26 Rev Time 0.00
Received By dharvey Date 2015-11-30 Time 12:59 Sent To Z
Notes
2015-11-30 13:26:15CORRECT ELECTRICAL CODE REFERENCE IS 2011, NOT 2008.
 ALL DEVICES NOTED IN NOTE 7 ARE TO BE LABELED FOR THE
 LOCATION AS WELL.
 120V WATER HEATER FEED IN NOTE 8 DOES NOT APPEAR ON THE
 PAQNEL SCHEDULE.
 NOTE 16 DOES NOT INDICATETHE EQUIPMENT IT IS
 REFERENCING TO BE CONNECTED.
 NO ENERGY CODE COMPLIANCE FOR FBC-ENERGY APPEARS TO BE
 CONNECTED.
 NO REFERENCE IS MADE TO INDICATE COMPLIANCE WITH THE
 ELECTRICAL REQUIREMENTS OF THE FBC-ENERGY.
 CEILING FANS APPEAR TO BE EXISTING, HOWEVER, NO LOAD OR
 CIRCUITIS INDICATED.
 ARE GFCI RECEPTACLES PROPOSED AT THE BATHROOM BASINS?
 NONE APPEAR TO BE INDICATED.
 NOTES INDICATE AIR CONDITIONING/MECHANICAL WORK. NONE
 IS SHOWN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-29 Cont ID  
Sent By pleduc Date 2016-02-01 Time   Rev Time 0.00
Received By pleduc Date 2016-01-29 Time 16:00 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By pleduc Date 2015-12-11 Time   Rev Time 0.00
Received By pleduc Date 2015-12-11 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-25 Cont ID  
Sent By pleduc Date 2015-11-25 Time   Rev Time 0.00
Received By pleduc Date 2015-11-25 Time 11:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-04 Cont ID  
Sent By cthroop Date 2016-02-04 Time 13:16 Rev Time 0.00
Received By cthroop Date 2016-01-25 Time 11:25 Sent To  
Notes
2016-01-26 11:25:17RESUB ROUTED TO ESCHNEIDER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-07 Cont ID  
Sent By lmarchan Date 2016-01-07 Time 13:27 Rev Time 0.00
Received By lmarchan Date 2015-12-09 Time 14:09 Sent To  
Notes
2015-12-10 14:09:22B28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-03 Cont ID  
Sent By skennedy Date 2015-12-03 Time 14:45 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 12:54 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2016-02-04 Cont ID  
Sent By cthroop Date 2016-02-04 Time 14:00 Rev Time 0.00
Received By cthroop Date 2016-02-04 Time 14:00 Sent To  
Notes
2016-02-04 14:01:08IMPACT FEES NOT REQUIRED PER MICHELLE, PBC. CST

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-02-04 Cont ID  
Sent By cthroop Date 2016-02-04 Time 13:16 Rev Time 0.00
Received By cthroop Date 2016-02-04 Time 13:16 Sent To  
Notes
2016-02-04 13:18:09CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-01-07 Cont ID  
Sent By lmarchan Date 2016-01-07 Time 13:27 Rev Time 0.00
Received By lmarchan Date 2016-01-07 Time 13:27 Sent To  
Notes
2016-01-07 13:27:26IMPACT FEES STILL REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By skennedy Date 2015-12-03 Time 14:48 Rev Time 0.00
Received By skennedy Date 2015-12-03 Time 14:48 Sent To  
Notes
2015-12-03 14:49:121ST REVIEW: FBC 2014 5TH ED.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-12-17 Cont ID  
Sent By ccole Date 2015-12-17 Time 09:03 Rev Time 0.00
Received By ccole Date 2015-12-17 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-23 Cont ID  
Sent By ccole Date 2015-11-23 Time 09:27 Rev Time 0.00
Received By ccole Date 2015-11-23 Time 09:27 Sent To  
Notes
2015-11-23 09:33:181ST REVIEW 2014 MECHANICAL
 PERMIT #15110575
 11/23/15
  
 1) PLEASE CLARIFY THE SCOPE OF MECHANICAL WORK FOR THE
 PROPOSED PROJECT. WILL ANY OF THE BAR EQUIPMENT REQUIRE
 REFRIGERATION SYSTEMS AND REMOTE CONDENSERS? WILL NEW
 TOILET ROOM EXHAUST FANS AND EXHAUST DUCTS BE
 INSTALLED?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-14 Cont ID  
Sent By gjohnson Date 2015-12-14 Time 15:06 Rev Time 0.00
Received By gjohnson Date 2015-12-14 Time 15:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By gjohnson Date 2015-11-20 Time 16:12 Rev Time 0.00
Received By gjohnson Date 2015-11-20 Time 16:12 Sent To  
Notes
2015-11-20 16:37:001ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW DISTANCE FROM WATER HEATER .HOT WATER
 SYSTEM SHALL CONFORM TO FBC P SEC 607.2 HOT OR TEMPERED
 WATER SUPPLY TO FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
 2.VENT NEEDED ON TH SIDE WHERE THER ARE 2 FLOOR SINKS
 AND1 FLOOR DRAIN.SHALL COMPLY WITH FBC P SEC 915.2.3
 CONNECTION.
 THE COMBINATION WASTE AND VENT SYSTEM SHALL BE PROVIDED
 WITH A DRY VENT CONNECTED AT ANY POINT WITHIN THE
 SYSTEM OR THE SYSTEM SHALL CONNECT TO A HORIZONTAL
 DRAIN THAT IS VENTED IN ACCORDANCE WITH ONE OF THE
 VENTING METHODS SPECIFIED IN THIS CHAPTER. COMBINATION
 WASTE AND VENT SYSTEMS CONNECTING TO BUILDING DRAINS
 RECEIVING ONLY THE DISCHARGE FROM A STACK OR STACKS
 SHALL BE PROVIDED WITH A DRY VENT. THE VENT CONNECTION
 TO THE COMBINATION WASTE AND VENT PIPE SHALL EXTEND
 VERTICALLY TO A POINT NOT LESS THAN 6 INCHES (152 MM)
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE BEING
 VENTED BEFORE OFFSETTING HORIZONTALLY.
 3.GRAB BARS SHALL BE MEASURED FROM THE TOP OF THE
 GRIPPING SURFACE. PER FBC ACC. SEC 609.4
 4. TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC.
 SEC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.

Review Stop Z ZONING
Rev No 3 Status P Date 2016-01-28 Cont ID  
Sent By eschneid Date 2016-01-28 Time 15:45 Rev Time 0.50
Received By eschneid Date 2016-01-28 Time 15:04 Sent To FIRE
Notes
2016-01-28 15:45:40PASSED
  
 THE TENSION FABRIC CANOPY MAY NOT BE MADE OUT OF VINYL.
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-12-16 Cont ID  
Sent By eschneid Date 2015-12-16 Time 17:17 Rev Time 0.25
Received By eschneid Date 2015-12-16 Time 16:44 Sent To  
Notes
2015-12-16 17:18:22FAILED
  
 1) REPEAT COMMENT: PLEASE PROVIDE INFORMATION ON THE
 NEW TENSION FABRIC. PLEASE NOTE THAT THIS MAY NOT BE
 MADE OUT OF VINYL.
  
 2) REPEAT COMMENT: STAFF IS CONCERNED WITH THE FOUR
 "HIGH COMMUNAL TABLES" AND THE ADJOINING CHAIRS
 IMPEDING THE TRAVEL WAYS. PLEASE PROVIDE THE DIMENSION
 LINE FROM THE BACK OF A CHAIR IN ITS OCCUPIED STATE TO
 THE WALL OF THE BAYS TO EITHER SIDE OF THE OUTDOOR BAR
 (CITY CELLAR AND THE FUTURE TAP HOUSE) ON THE OVERALL
 SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By eshcneid Date 2015-12-03 Time 13:52 Rev Time 0.50
Received By eschneid Date 2015-12-03 Time 13:52 Sent To  
Notes
2015-12-03 14:17:38FAILED
  
 1) PLEASE PROVIDE INFORMATION ON THE NEW TENSION
 FABRIC. PLEASE NOTE THAT THIS MAY NOT BE MADE OUT OF
 VINYL.
  
 2) STAFF IS CONCERNED WITH THE FOUR "HIGH COMMUNAL
 TABLES" AND THE ADJOINING CHAIRS IMPEDING THE TRAVEL
 WAYS. PLEASE PROVIDE THE DIMENSION LINE FROM THE BACK
 OF A CHAIR IN ITS OCCUPIED STATE TO THE WALL OF THE
 BAYS TO EITHER SIDE OF THE OUTDOOR BAR (CITY CELLAR AND
 THE FUTURE TAP HOUSE) ON THE OVERALL SITE PLAN.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  