Plan Review Details - Permit 15110523
Plan Review Stops For Permit 15110523
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-29 Cont ID  
Sent By rmcdouga Date 2016-03-29 Time 16:48 Rev Time 0.00
Received By rmcdouga Date 2016-03-28 Time 18:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-11 Cont ID  
Sent By rmcdouga Date 2016-03-11 Time 07:17 Rev Time 0.00
Received By rmcdouga Date 2016-03-10 Time 18:15 Sent To  
Notes
2016-03-11 07:20:52PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE STILL SOME CODE SECTIONS CITED ON THE
 PLANS THAT ARE INCORRECT. SEE THE MARKUPS ON THE PLANS
 AND MAKE CORRECTIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By rmcdouga Date 2016-01-13 Time 18:46 Rev Time 0.00
Received By rmcdouga Date 2016-01-13 Time 18:46 Sent To  
Notes
2016-01-13 18:05:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION. CHECK CODE SECTIONS AND THE EDITION OF
 THE CODE THAT IS CITED IN THE PLANS. I CLOUDED MOST OF
 THEM IN RED ON THE PLANS.
  
 2) THE EMERGENCY MEANS OF ESCAPE NOTE AT THE ENTRY DOOR
 IS INCORRECT. THE DOOR IS REQUIRED TO BE IMPACT
 RESISTANT AND IMPACT PROTECTION DEVICES CAN NOT BE USED
 PER FBCR 310.4.
  
 3) THE CODE SECTION FOR UNDER STAIR PROTECTION IS
 R302.7 IN THE 2014 FBCR AND NOT R311.2.2
  
 4) THE ROOF COVERING NOTES ON C2 AND C3 REFERENCE THE
 2010 FBC.
  
 5) THE GENERAL NOTES TYPICAL TO UNITS A, B AND C
 REFERENCE THE 2010 FBC AND WRONG CODE SECTIONS IN
 SEVERAL PLACES.
  
 6) THE FLAME SPRED AND SMOKE DEVELOPED NOTE #19 IS
 INCORRECT. INSULATION MATERIALS SHALL HAVE A FLAME
 SPRED INDEX NOT TO EXCEED 25 PER FBCR 302.10.1. SEE FBC
 R302.9.1 AND R302.9.2 FOR FLAME SPREAD AND SMOKE
 DEVELOPED REQUIREMENTS FOR WALL AND CEILING FINISHES.
  
 7) THERE IS A DETAIL FOR A SHADOW BOX WOOD FENCE (WING
 WALL) IN THE DOCUMENTS THAT NEEDS TO BE REMOVED. A
 SEPARATE PERMIT, APPLICATION AND DRAWINGS ARE REQUIRED
 FOR FENCES. THE DETAIL DOES NOT SPECIFY THE HEIGHT AND
 DOES NOT PROVIDE AND STRUCTURAL DETAILS. FBC 107.2.1
  
 8) THE -50 PSF DESIGN PRESSURE IN PRODUCT APPROVAL
 FL15037.3 FOR THE ENTRY DOOR IS NOT ADEQUATE. THE PLANS
 SPECIFY A REQUIRED NEGATIVE PRESSURE OF -55.08 PSF FOR
 THE DOOR. FBC R301.1
  
 9) THE ANCHOR SPACING COLUMN ON THE STORM PANEL
 INSTALLATION SCHEDULE FOR 1441-A END UNIT IS BLANK. THE
 ANCHOR SPACINGS ARE MISSING. FBC 107.2.1
  
 10) THE STORM PANEL INSTALLATION SCHEDULES FOR END
 UNITS A AND B ARE MISSING THE WINDOWS ON THE ENDS. FBC
 107.2.1
  
 11) SUBMIT TWO COPIES OF A KEY PLAN THAT CORRESPONDS
 WITH THE STORM PANEL INSTALLATION SCHEDULE TO SHOW THE
 LOCATIONS OF THE OPENINGS. FBC 107.2.1
  
 12) SOME OF THE PLAN SHEETS AND DOCUMENTS ARE NOT
 SIGNED AND SEALED. VERIFY THAT ALL REQUIRED SUBMITTALS
 ARE SIGNED AND SEALED. FS 471 AND 481
  
 13) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 11:15 Rev Time 0.00
Received By shill Date 2016-04-27 Time 12:08 Sent To  
Notes
2017-05-15 11:15:57CLOSED OPEN E STOP
 THIS WAS ADDED ACCIDENTALLY BY MALBARRAN
 PLAN REVIEWS ALREADY COMPLETE
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-23 Cont ID  
Sent By albarran Date 2016-03-23 Time 10:09 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-02 Cont ID  
Sent By albarran Date 2016-03-02 Time 15:19 Rev Time 0.00
Received By albarran Date 2016-03-02 Time 15:02 Sent To  
Notes
2016-03-02 15:20:06PER NOTES AND DISCUSSIONS PREVIOUSLY SHARED WITH THE
 DESIGN PROFESSIONAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By mvaldes Date 2016-01-13 Time 15:06 Rev Time 0.00
Received By mvaldes Date 2016-01-13 Time 11:26 Sent To  
Notes
2016-01-13 15:13:441ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
 JOB PERMIT NUMBER: 15110523
 JOB ADDRESS: CHARLESTON COMMONS VILLAS
 5025 ERNEST ST WEST PALM BEACH
 DATE: JAN 13 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1- IN REGARDS WITH UNIT A , B ,C THE OCPD RATING FOR
 THE WATER HEATER IS UNDERSIZED THE E3 FBC-R E4101.4.1
 SINGLE NON-MOTORED OPERATED APPLIANCE STATES THE
 FOLLOWING (3) NOT EXCEED 150 PERCENT OF THE APPLIANCE
 RATED CURRENT IF THE OVERCURRENT PROTECTION RATING IS
 NOT MARKED (?) AND THE APPLIANCE IS RATED OVER 13.3
 AMPERES. WHERE 150 PERCENT OF THE APPLIANCE RATING DOES
 NOT CORRESPOND TO A STANDARD OVERCURRENT DEVICE AMPERE
 RATING, THE NEXT HIGHER STANDARD RATING SHALL BE
 PERMITTED.
 2- ELECTRICAL NOTE #16 FOR UNIT C SAYS 50 % OF THE
 LAMPS WILL BE HIGH EFFICIENT ( MUST BE A TYPO
 CONSIDERING ALL OTHER STATE 75 % WHICH IS THE CORRECT
 NUMBER PLEASE FIX. ) FBC-ER 404.1
 3- TW-ROMEX IS A TECHNICALLY A BRAND NAME NOT A WIRING
 METHOD YOU MIGHT WANT TO REFERENCE TYPE NM , NMC, AND
 NMS IN YOUR PANEL SCHEDULE UNDER CONDUCTORS.
 4- PANELS SEEMED TO BE LOCATED IN A DARK AREA WERE
 SERVICING MIGHT REQUIRE ILLUMINATION FBC-R E3405.6
 5- PLEASE ADD TO NOTES R402.4.4 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS HAVING AN
 AIR LEAKAGE RATE NOT MORE THAN 2.0 CFM (0.944 L/S) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 283 AT A 1.57 PSF (75
 PA) PRESSURE DIFFERENTIAL. ALL RECESSED LUMINAIRES
 SHALL BE SEALED WITH A GASKET OR CAULK BETWEEN THE
 HOUSING AND THE INTERIOR WALL OR CEILING COVERING.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-30 Cont ID  
Sent By lmarchan Date 2016-03-30 Time 09:39 Rev Time 0.00
Received By lmarchan Date 2016-03-18 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By lmarchan Date 2016-03-14 Time 08:31 Rev Time 0.00
Received By lmarchan Date 2016-02-03 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-14 Cont ID  
Sent By hmoser Date 2016-01-14 Time 13:49 Rev Time 0.00
Received By hmoser Date 2015-11-23 Time 15:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2016-01-14 Cont ID  
Sent By hmoser Date 2016-01-14 Time 13:49 Rev Time 0.00
Received By hmoser Date 2016-01-14 Time 13:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-08 Cont ID  
Sent By tklarge Date 2016-02-08 Time 06:29 Rev Time 0.00
Received By tklarge Date 2016-02-08 Time 06:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-29 Cont ID  
Sent By tklarge Date 2015-11-29 Time 08:22 Rev Time 0.00
Received By tklarge Date 2015-11-29 Time 07:42 Sent To  
Notes
2015-11-29 07:46:481) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO SEC.107.2.1.
 2) THE WATER SHUTOFF VALVES FOR THE WASHING MACHINE
 SHALL NOT BE LOCATED BEHIND THE W/D STACK MODEL UNLESS
 THERE IS AN ACCESS PANEL ON THE W/D UNIT FOR THE
 VALVES. SUBMIT MANUF.SPECIFICATIONS FOR THE
 WASHER/DRYER UNIT.2014 FBC-RESIDENTIAL SEC. P2903.9.3.
 3) SHT. B-P-1 - NOTES- NOTE #3 STATES THAT THE HOT
 WATER HEATER TO BE SIZED PER TABLE 46-N-8.WHAT
 STANDARD/CODE IS THIS TABLE FROM? I COULDN'T FIND IT
 IMY CODE BOOKS. CLARIFY.
 4) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW. WPB AMEND. TO FBC SEC. 107.3.5.3 (11).
 5) THE PLUMBING PLANS REFER TO SHEET SP-1 FOR
 CONTINUATION OF THE WATER SERVICE. SHT. SP-1 IS NOT
 PART OF THIS SET. SUBMIT SHT. SP-1 FOR REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-01-13 Cont ID  
Sent By rmcdouga Date 2016-01-13 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2016-01-13 Time 14:46 Sent To  
Notes
2016-01-13 14:50:10ROOFING MATERIALS
 1) FL 5259 POLYGLASS TU-PLUS SELF ADHERING UNDERLAYMENT
 2) FL 6332 3M ROOF TILE ADHESIVE
 3) FL 7849 BORAL SPANISH "S" CEMENT ROOF TILE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2016-03-30 Cont ID  
Sent By skennedy Date 2016-03-30 Time 16:30 Rev Time 0.00
Received By skennedy Date 2016-03-30 Time 16:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-23 Cont ID  
Sent By llouie Date 2016-03-23 Time   Rev Time 0.00
Received By llouie Date 2016-03-23 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-08 Cont ID  
Sent By llouie Date 2015-12-08 Time 15:31 Rev Time 0.00
Received By llouie Date 2015-12-08 Time 15:31 Sent To  
Notes
***NONE***