| 2015-11-19 16:51:11 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15110510 |
| | ADD: 1721 PALM BEACH LAKES SUITE: E419 |
| | CONT: INDUSTRIAL COMMERCIAL STRUCTURES, INC. |
| | TEL: 407-629-5431 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: THURS. NOV. 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-0.2 LIFE SAFETY PLAN DOES NOT PROVIDE THE |
| | MINIMUM BUILDING TYPE? 2014 FBC-B TABLE 503. |
| | |
| | 2) SHEET A-0.2 LIFE SAFETY PLAN. THE SEAT NEXT TO THE |
| | POS AREA IS APPROX. 40 FEET AISLE ACCESS WAY BEFORE |
| | THERE IS A CHOICE OF TWO OR MORE PATHS OF EGRESS TRAVEL |
| | TO SEPARATE EXITS. |
| | |
| | 3) SHEET A-0.2 LIFE SAFETY PLAN. THE SIDE ENTRY DOOR |
| | FROM THE INTERIOR DINING ROOM TO THE EXTERIOR COVERED |
| | SEATING IS MISSING THE 60 INCHES OF REQUIRED CLEARANCE |
| | IN THE DIRECTION OF TRAVEL. 2014 FBC-ACCESSIBILITY |
| | FIGURE 404.2.4.1(A). |
| | |
| | 4) ) SHEET D-1.0 NOTES 1 & 2 BOTH INDICATE 2 NEW |
| | OPENINGS CUT INTO CONCRETE TILT WALL PANELS. NOTE |
| | INDICATES PANELS ARE TO BE X-RAYED, PANELS ARE NOT TO |
| | BE CUT CLOSER THAN 2 FEET FROM THE OF PANEL. VERIFY |
| | WITH STRUCTURAL PLANS. NOTE THERE ARE NO STRUCTURAL |
| | PLANS SUPPLIED FOR AN ENGINEER TO ANALYZE. |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. |
| | |
| | 5A) SHEET A-2.2 AWNING PLAN. THIS SHEET DOES NOT |
| | PROVIDE TO WHAT CRITERIA THE WIND DESIGN IS FOR ANY OF |
| | THE FABRIC AWNINGS. |
| | 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL |
| | BE BASED ON RATIONAL ANALYSIS, USING THE APPLICABLE |
| | WIND LOADS OF CHAPTER 16 AS SHOWN BELOW. |
| | |
| | 3105.4.2.1 |
| | THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| | CRITERIA: |
| | 1. MINIMUM WIND SPEED 105 MPH. |
| | |
| | 2. EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER |
| | 16. |
| | |
| | 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| | MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR |
| | NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE |
| | FOLLOWING CRITERIA: |
| | 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER |
| | 16, USING FIGURE 1609C. |
| | 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16. |
| | |
| | 5B) 3105.6 CANOPY MATERIALS. CANOPIES SHALL BE |
| | CONSTRUCTED OF A RIGID FRAMEWORK WITH AN APPROVED |
| | COVERING THAT MEETS THE FIRE PROPAGATION PERFORMANCE |
| | CRITERIA OF NFPA 701 OR HAS A FLAME SPREAD INDEX NOT |
| | GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 84 OR UL 723. |
| | |
| | 5C) SHEET A-2.2 AWNING PLAN, DETAIL # 3. SHOWS POWER |
| | VINYL ROLL DOWN WIND BREAKS. PLEASE PROVIDE FIRE RATING |
| | OF THIS PRODUCT. 3105.6 CANOPY MATERIALS. CANOPIES |
| | SHALL BE CONSTRUCTED OF A RIGID FRAMEWORK WITH AN |
| | APPROVED COVERING THAT MEETS THE FIRE PROPAGATION |
| | PERFORMANCE CRITERIA OF NFPA 701 OR HAS A FLAME SPREAD |
| | INDEX NOT GREATER THAN 25 WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84 OR UL 723. |
| | 6A) SHEET A-4.4 WIND DESIGN CRITERIA. VULT 168 MPH, |
| | VASD 131MPH. MEAN ROOF HEIGHT OF 30 FEET. THE PLANS |
| | STATE A C EXPOSURE AND B SURFACE ROUGHNESS. PLEASE |
| | REVIEW 2014 FBC-B 1609.4.2 SURFACE ROUGHNESS C. THIS |
| | SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING |
| | LOCATED WITHIN SURFACE ROUGHNESS BTYPE TERRAIN WHERE |
| | THE BUILDING IS WITHIN 100 FEET (30 M) HORIZONTALLY IN |
| | ANY DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR |
| | D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9 |
| | M) IN THE UPWIND DIRECTION AND A WIDTH GREATER THAN 150 |
| | FEET (46 M). |
| | 6B THE PRESSURES STATED ARE LOW FOR168 VULT, EXPOSURE C |
| | @ 30 FT. MRH. |
| | 40 SQ. FT ZONE 4 -52.15 VULT |
| | 115 SQ. FT ZONE 4 -40.8167 VULT |
| | 6C) THE 2 PRODUCT APPROVALS SUBMITTED TRULITE GLASS |
| | 3000 REGISTOR STOREFRONT NOA 14-0203.01 AND 351 SERIES |
| | OUTSWING ALUMINUM ENTRANCE DOOR W/ TRANSOM, NOTE BOTH |
| | ARE GOOD FOR 10 FEET. THE SHEET INDICATES THE OPENINGS |
| | ARE 11 FT 10 INCHES IN HEIGHT OVER THE LIMITS OF THE |
| | PRODUCT APPROVALS UNLESS A SEPARATE MULLION REPORT IS |
| | SUBMITTED THAT WILL MEET THE VERTICAL HEIGHT AND |
| | PRESSURE REQUIREMENTS. |
| | 7A) 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | COMPONENTS & CLADDING |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, INTAKE & |
| | EXHAUST FANS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | |
| | |
| | 7B) FOR GLAZED UNITS, DOORS AND WINDOWS PLEASE CIRCLE |
| | HE SIZE(WIDTH & HEIGHT) OF THE WINDOW AND OR DOOR, TYPE |
| | OF GLAZING, MULLIONS PROVIDE THE TRIBUTARY AREA SIZE OF |
| | MULLION AND LENGTH, TYPES OF ANCHORS AS WELL AS |
| | PRESSURES. |
| | |
| | 7C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7D) IF EITHER THE CONTRACTOR OR DESIGNER OF RECORD |
| | WOULD PREFER TO SUBMIT PRODUCT APPROVALS AFTER PERMIT |
| | ISSUANCE THEN SEE 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENT 107.3.4.2 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| | ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| | THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| | NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| | BUILDING OFFICIAL. |
| | |
| | SHEET A-4.4 DETAIL # 6 THE INSULATION AND THICKNESS OF |
| | THE GYPSUM BOARD DO NOT MATCH THAT FOUND IN THE ENERGY |
| | CALCULATIONS. DISCREPANCY 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 8) THE ENERGY CALCULATIONS CHECKLIST HAS NOT BEEN FILED |
| | OUT AS REQUIRED BY THE ENERGY CODE. MANDATORY |
| | REQUIREMENT. |
| | |
| | 9) SHEET A-7.1 RESTROOM GRAB BARS SHOW THEY ARE TO BE |
| | INSTALLED 36 INCHES CENTERLINE OF BAR. THE 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 33-36 INCHES |
| | MAXIMUM MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| | |
| | 10) SHEET A-8.3 PROVIDE THE WIND DESIGN CRITERIA AND |
| | PRESSURES. THE PRESSURES DO NOT INDICATE IF THEY ARE |
| | VULT OR VASD NOR IF THEY ARE FOR 10 SQ. FT ? WE USE 10 |
| | SQ. FT. FOR ROOFING FOR FASTENERS WORST CASE. 2014 |
| | FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 11) SHEET A-8.0 ROOF TOP EQUIPMENT PLAN, DOESN?T SHOW |
| | HOW ACCESS TO ROOFTOP EQUIPMENT WILL BE ACHIEVED? |
| | 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED |
| | STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING |
| | ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT |
| | A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL |
| | BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, |
| | THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL |
| | TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. |
| | SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| | OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR |
| | WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| | |
| | 12) WILL NOT REQUIRE REVIEW FOR B. P. COUNTY IMPACT |
| | FEES, CHANGE IN OCCUPANCY. CALLED P. B. COUNTY IMPACT |
| | FEE OFFICE, SPOKE WITH MECHELLE. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |