Plan Review Details - Permit 15110492
Plan Review Stops For Permit 15110492
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-29 Cont ID  
Sent By jwitmer Date 2015-12-29 Time 16:53 Rev Time 0.00
Received By jwitmer Date 2015-12-29 Time 16:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-17 Cont ID  
Sent By jwitmer Date 2015-11-17 Time 14:42 Rev Time 0.00
Received By jwitmer Date 2015-11-17 Time 12:01 Sent To  
Notes
2015-11-17 14:10:35BUILDING PLAN REVIEW
 W. P. B. PERMIT:15110492
 ADD: 6212 GEORGIA AVE.
 CONT: FLORIDA FILTRATION
 TEL: (561)582-5543
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2014
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3. COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 17/ 2015
 ACTION: DENIED
  
 1) THERE IS A DISCREPANCY IN THE PLAN.SHEET B1. THE
 PLANS SHOW THE FLOOR LAYOUT OF 2 SPRAY BOOTHS, ONE WITH
 A MIXING ROOM & SPRAY BOOTH THE OTHER DETAIL SHOWING A
 SINGLE SPRAY BOOTH. PLEASE REPRESENT THE ACTUAL LAYOUT
 NOT A GENERIC SHEET THAT COVERS ALL INSTALLATIONS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS..
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 2) SHEET A-2 SHOWS AN OVER HEAD VIEW AND ELEVATIONS OF
 THE SPRAY BOOTH. THIS REVIEW THERE HAVE BEEN NO
 SUBMITTALS MANUFACTURERS SPECIFICATIONS, DETAILS OF
 COMPLIANCE WITH SECTION 416.4 SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE WITH
 THE FIRE PREVENTION CODE, NFPA 33. THE DESIGNER OF
 RECORD IS TO REVIEW ALL SUBMITTALS, SHOP DRAWING, ETC
 BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. ADDITIONAL
 COMMENTS MAY FOLLOW ONCE SHOP DRAWINGS ARE SUBMITTED.
  
 3) SHEET B-1 SHOWS A 48" X48" WALL LOVER THROUGH THE
 WALL. NOTE PLANS DO NOT INDICATE HOW THE HOLE IN THE
 WALL WILL BE RE-INFORCED? BLOCK WALL, LINTEL, NEW
 VERTICAL REBARS TO BE PART OF THE MWFRS (MAIN WINF
 FORCE RESISTING SYSTEM). WALL TYPE IS NOT IDENTIFIED?
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (C) WALL LOUVERS
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SHEET B-2 SHOWS SHOWS A SIDE ELEVATION WITH THE
 EXHAUST DUCT PENETRATING THE ROOF DECK. THE PLANS DO
 NOT INDICATE THE WHAT THE STRUCTURAL DECK AND FRAMING
 MEMBERS IS MADE OF. NO FRAMING OR INFILE FRAMING IS
 PROVIDED AROUND THE NEW ROOF DECK PENETRATION? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 7) THE PLANS DO NOT SHOW HOW COMPLIANCE WITH 2014 FBC-B
 416.5 FIRE PROTECTION. AN AUTOMATIC SPRINKLER SYSTEM OR
 FIRE -EXTINGUISHING SYSTEM SHALL BE PROVIDED IN ALL
 SPRAY BOOTHS AND INSTALLED IN ACCORDANCE WITH FBC-B
 CHAPTER 9.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By mvaldes Date 2016-01-25 Time 14:43 Rev Time 0.00
Received By mvaldes Date 2016-01-25 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By mvaldes Date 2015-12-07 Time 10:55 Rev Time 0.00
Received By mvaldes Date 2015-12-07 Time 10:55 Sent To  
Notes
2015-12-07 11:05:521ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 430.6 AMPACITY AND MOTOR RATING DETERMINATION. THE
 SIZE OF CONDUCTORS SUPPLYING EQUIPMENT COVERED BY
 ARTICLE
 430 SHALL BE SELECTED FROM THE ALLOWABLE AMPACITY
 TABLES IN
 ACCORDANCE WITH 310.15(B) OR SHALL BE CALCULATED IN
 ACCORDANCE
 WITH 310.15(C).
 (1) TABLE VALUES. OTHER THAN FOR MOTORS BUILT FOR LOW
 SPEEDS
 (LESS THAN 1200 RPM) OR HIGH TORQUES, AND FOR
 MULTISPEED
 MOTORS, THE VALUES GIVEN IN TABLE 430.247, TABLE
 430.248,
 TABLE 430.249, AND TABLE 430.250 SHALL BE USED TO
 DETERMINE
 THE AMPACITY OF CONDUCTORS OR AMPERE RATINGS OF
 SWITCHES,
 BRANCH-CIRCUIT SHORT-CIRCUIT AND GROUND-FAULT
 PROTECTION, INSTEAD
 OF THE ACTUAL CURRENT RATING MARKED ON THE MOTOR
 NAMEPLATE. WHERE A MOTOR IS MARKED IN AMPERES, BUT NOT
 HORSEPOWER, THE HORSEPOWER RATING SHALL BE ASSUMED TO
 BE
 THAT CORRESPONDING TO THE VALUE GIVEN IN TABLE 430.247,
 TABLE 430.248, TABLE 430.249, AND TABLE 430.250,
  
 PLEASE PROVIDE EQUIPMENT SPECS AND VERIFY LOCATION OF
 EQUIPMENT AS IN OTHER COMMENTS
 PLEASE PROVIDE A MORE DETAILED FIRE SYSTEM PLAN
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By pleduc Date 2015-12-21 Time   Rev Time 0.00
Received By pleduc Date 2015-12-21 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-16 Cont ID  
Sent By rlindow Date 2015-11-16 Time   Rev Time 0.00
Received By rlindow Date 2015-11-16 Time   Sent To  
Notes
2015-11-16 09:59:09 
  
 ALL WORK SUBJECT TO FIELD INSPECTION. LINDOW 11/16/15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-25 Cont ID  
Sent By lmarchan Date 2016-01-25 Time 16:24 Rev Time 0.00
Received By lmarchan Date 2015-12-16 Time 11:35 Sent To  
Notes
2015-12-17 11:35:17B06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-07 Cont ID  
Sent By cpuell Date 2015-12-07 Time 14:40 Rev Time 0.00
Received By cpuell Date 2015-11-12 Time 15:47 Sent To  
Notes
2015-11-12 16:05:01B07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-23 Cont ID  
Sent By ccole Date 2015-12-23 Time 17:00 Rev Time 0.00
Received By ccole Date 2015-12-23 Time 17:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-17 Cont ID  
Sent By ccole Date 2015-11-17 Time 07:20 Rev Time 0.00
Received By ccole Date 2015-11-17 Time 07:20 Sent To E
Notes
2015-11-17 07:44:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110492
 11/17/15
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 SPRAY BOOTH AND SPRAY EQUIPMENT REVIEWED AND STAMPED BY
 THE ENGINEER OF RECORD- REFERENCE NFPA 33 SECTIONS
 (5.1.1), )5.1.4), (7.10.1), (8.3.2), (11.1), (12.1).
 2) THE LOCATIONS OF THE SPRAY BOOTH SHOWN ABUTTING THE
 EXTERIOR CONCRETE WALL AT THE EAST SIDE DOES NOT LEAVE
 AMPLE SPACE FOR MAINTENANCE AS REQUIRED BY SECTION
 5.3.2 EXCEPTION (2) NFPA 33.
 3) A 4X4' LOUVER IS SHOWN IN THE PLAN FOR MAKE-UP AIR.
 PLEASE PROVIDE AN EXHAUST VENTILATION CALCULATION USING
 THE PERCENTAGE OF FREE AIR AVAILABLE THROUGH THE
 LOUVERED OPENING- SECTION 502.7.3.1 FBC-14 MECHANICAL.
 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE SPRAY
 BOOTH IN COMPLIANCE WITH SECTION 502.7.3.3 FBC-14
 MECHANICAL.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A FL.
 PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE LOUVER
 REVIEWED AND APPROVED BY THE ENGINEER OF RECORD. THE
 LOCATION OF THE LOUVERED OPENING SHALL BE IN COMPLIANCE
 WITH SECTION 401.4, AND BE PROTECTED FROM WEATHER IN
 ACCORDANCE WITH SECTION 401.5.
 6) INDICATE HOW THE EXHAUST DUCT IS BEING SUPPORTED IN
 THE AREA BETWEEN THE TOP OF THE BOOTH AND THE ROOF
 LEVEL- SECTION 7.8 NFPA 33.
 7) REFERENCE SECTION 501.3.1(1) FBC-14 MECHANICAL AND
 PROVIDE A PLAN VIEW OF THE ROOF AND SITE THAT SHOWS THE
 REQUIRED MINIMUM CLEARANCE DISTANCES FOR THE SPRAY
 BOOTH EXHAUST TERMINATION TO PROPERTY LINES, AIR
 INTAKES, COMBUSTIBLE CONSTRUCTION, EXTERIOR WALLS, AND
 OPERABLE OPENINGS.
 8) INDICATE THE TYPE AND SIZE OF COMPRESSED AIR PIPING
 TO BE INSTALLED AND HOW IT WILL BE SUPPORTED- INDICATE
 THE TYPE AND SPACING OF THE HANGERS.
 9) PROVIDE A THROUGH PENETRATION FIRE STOPPING METHOD
 FOR THE COMPRESSED AIR PIPING PENETRATING THE BOOTH.
 10) PROVIDE FIRE SUPPRESSION PLANS- SECTION 9.1 NFPA
 33.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  