Plan Review Details - Permit 15110463
Plan Review Stops For Permit 15110463
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-07 Cont ID  
Sent By shill Date 2015-12-07 Time 09:09 Rev Time 0.00
Received By shill Date 2015-12-07 Time 09:08 Sent To  
Notes
2015-12-07 09:09:39DH AND KC MADE A SITE VISIT. THEY CONFIRMED THAT, DUE
 TO THE ELEVATION DIFFERENCE BETWEEN THE PARKING LOT AND
 SIDEWALK, A RAMP IS NECESSARY AND PROPOSED NEW
 ACCESSIBLE PARKING SPACES ARE ON THE CLOSEST ACCESSIBLE
 ROUTE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 07:21 Rev Time 0.00
Received By shill Date 2015-11-20 Time 07:21 Sent To  
Notes
2015-11-20 07:26:23****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 5TH EDITION
  
 APPLICABLE FBC REFERENCES: SEE FBC 2010 ACCESSIBLITY
 202.3 (ALTERATIONS), 208.2 (PARKING SPACES), 502
 (PARKING SPACES), 206 (ACCESSIBLE ROUTE).
  
 1. PROVIDE MORE INFORMATION REGARDING THE "NO PARKING
 FDC." IT IS NOT CLEAR WHY NONE OF THE FOUR ACCESSIBLE
 SPACES ARE CLOSEST TO THE ACCESSIBLE ENTRANCES;
 NON-ACCESSIBLE SPACES ARE CLOSEST TO THE TWO DOORS. IT
 APPEARS THAT, EVEN IF ONE SPACE IS BLOCKED, THE
 REMAINING THREE ACCESSIBLE SPACES CAN BE RELOCATED SO
 THAT THEY ARE ON THE SHORTEST ROUTE.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-11-19 Cont ID  
Sent By cranford Date 2015-11-19 Time 11:01 Rev Time 0.00
Received By cranford Date 2015-11-19 Time 11:00 Sent To B
Notes
2015-11-19 11:00:59EXISTING NON-CONFORMING SITE. NEW PARKING LAYOUT BRINGS
 IT CLOSER TO COMPLIANCE WITH REGULATIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-23 Cont ID  
Sent By fstal Date 2015-11-23 Time 08:03 Rev Time 0.00
Received By fstal Date   Time   Sent To I
Notes
2015-11-23 08:40:26FRANK STALLWORTH, FIRE INSPECTOR I WEST PALM BEACH FIRE
 PREVENTION BUREAU
 500 N. DIXIE HWY WEST PALM BEACH, FLORIDA 33401
 OFFICE: 561-840-4780 FAX: 561-840-4774
 [email protected]
  
 PASS WITH THE BELOW COMMENTS:
  
 NFPA 1-18.2.3.1.2: FIRE DEPARTMENT ACCESS ROADS SHALL
 CONSIST OF ROADWAYS, FIRE LANES, PARKING LOT LANES, OR
 A COMBINATION THEREOF.
  
 NFPA 1-18.2.2.1: ACCESS BOX(ES) OR KNOX BOX. THE AHJ
 SHALL HAVE THE AUTHORITY TO REQUIRE AN ACCESS BOX(ES)
 TO BE INSTALLED IN AN ACCESSIBLE LOCATION WHERE ACCESS
 TO OR WITHIN A STRUCTURE OR AREA IS DIFFICULT BECAUSE
 OF SECURITY. PROVIDE KNOX BOX.
  
 NFPA1-18.2.2.2: ACCESS TO GATED SUBDIVISIONS OR
 DEVELOPMENTS. THE AHJ SHALL HAVE THE AUTHORITY TO
 REQUIRE FIRE DEPARTMENT ACCESS BE PROVIDED TO GATED
 SUBDIVISIONS OR DEVELOPMENTS THROUGH THE USE
 OF AN APPROVED DEVICE OR SYSTEM. PROVIDE KEY IN BOX AND
 OR KNOX BOX PADLOCK.
  
 NFPA 1-18.2.3.2.1: FIRE DEPARTMENT ACCESS ROAD SHALL
 EXTEND TO WITHIN 50 FT (15 M) OF AT LEAST ONE EXTERIOR
 DOOR THAT CAN BE OPENED FROM THE OUTSIDE AND THAT
 PROVIDES ACCESS TO THE INTERIOR OF THE BUILDING. WHEN
 REQUIRED BY THE AUTHORITY HAVING JURISDICTION, ROAD(S)
 OR PARKING LOTS PROVIDING ACCESS TO THE MAIN ENTRANCE
 DOOR(S) SHALL BE CONSIDERED ACCESS ROADS AND SHALL
 COMPLY WITH THE REQUIREMENTS OF 18.2.3.4.1.1 AND
 18.2.3.4.1.2.
  
 NFPA 1-18.2.3.4.2: SURFACE. FIRE DEPARTMENT ACCESS
 ROADS SHALL BE DESIGNED AND MAINTAINED TO SUPPORT THE
 IMPOSED LOADS OF FIRE APPARATUS AND SHALL BE PROVIDED
 WITH AN ALL-WEATHER DRIVING SURFACE. MAINTAIN ROAD
 SURFACE TO SUPPORT EMERGENCY APPARATUS.
  
 NFPA 1-18.3.4.1: HYDRANTS: CLEARANCES OF SEVEN AND ONE
 HALF FEET (7.6.) IN FRONT OF AND TO THE SIDES OF THE
 FIRE HYDRANT, WITH FOUR FEET (4.) CLEARANCE TO THE REAR
 OF THE HYDRANT.
  
 FIRE PROTECTION EQUIPMENT SHALL REMAIN IN SERVICE,
 DURING ALL PHASES OF CONSTRUCTION.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-07 Cont ID  
Sent By shill Date 2015-12-07 Time 09:09 Rev Time 0.00
Received By shill Date 2015-11-30 Time 10:02 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-30 Cont ID  
Sent By skennedy Date 2015-11-30 Time 14:49 Rev Time 0.00
Received By skennedy Date 2015-11-12 Time 13:17 Sent To Z
Notes
2015-11-30 14:50:00FOUND IN MISC 2
2015-11-20 07:29:1811/20 TO FIRE BOX
 (NEED MORE INFORMATION REGARDING THE AREA BLOCKED OFF
 AS "FDC NO PARKING")
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-30 Time 14:49 Rev Time 0.00
Received By rcaranci Date 2015-11-13 Time 15:38 Sent To ENG
Notes
***NONE***