Plan Review Details - Permit 15110411
Plan Review Stops For Permit 15110411
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2016-04-11 Time 09:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 07:54 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-15 Cont ID  
Sent By jwitmer Date 2016-01-15 Time 11:38 Rev Time 0.00
Received By jwitmer Date 2016-01-15 Time 11:02 Sent To  
Notes
2016-01-15 11:40:31BUILDING PLAN REVIEW
 W. P. B. REVISION: 15110411
 W. P. B. PERMIT; 14120130
 ADD: 1901 S. DIXIE HWY
 CONT: SISCA CONSTRUCTION
 TEL: 561-846-1179
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: SAT. NOV. 14/2014
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) 2ND REQUEST. SHEET R-2 SHOWS THE USE OF A MINI-PAKT
 CONDENSING UNIT FOR ROOF TOP USE. IN DETAIL C/R-2
 SECTION A-A THE DETAIL SHOWS THE USE OF A 2X6 BUILT UP
 CURB. THIS DETAIL IS NOT FOR A RTU DOWN UNIT WHERE
 THERE WOULDBE NO ROOFING MATERIAL BENEATH IT. IT WOULD
 APPEAR 2 SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN
 PARALLELL WHERE WOULD BE ROOFING BENEATH IT.
  
 2ND REQUEST. PLEASE REVIEW SECTION 1509.7 OF THE 2010
 FBC-B. 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS
  
 2ND REQUEST. OF THE PERMITED SET OF DRAWINGS SHEET A4.0
 ONLY SHOWS THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH
 S3 & M1.3 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE
 3 RTU'S AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS
 A NOTE THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL
 LOCATIN SHALL BE DETERMINED BY OWNER/ ARCHITECT.
 REVISION # 15090594 DOES NOT SHOW A REVISION TO THE
 ROOF PLAN NOR WAS SHEET S3 UPDATED TO SHOW NEW
 LOCATIONS, SHEET M1.3 DOES SHOW ON THE MECHANICAL ROOF
 TOP SHEET A REVISION SHOWING THE LOCATION FOR 3 NEWLY
 LOCATED, (NOT HIGHLIGHTED SHOWING A REVISION), ROOF TOP
 CU UNITS, NO DETAILS UNDER MECHANICAL NOR STRUCTURAL
 SHEETS!!!!!
  
 2ND REQUEST. THE STRUCTURAL ENGINEER HAS NOT INDICATED
 ON ANY PLANS HOW THIS UNIT WILL ATTACH TO THE MWFRS.
 THE ENGINEER HAS PROVIDED (PERMIT SET OF DRAWINGS)
 DETAILS ON SHEET S6 FOR THE ATTACHMENT OF THE RTU'S
 CURB TO THE MWFRS AND THE CLIP SYSTEM FOR MOUNTING THE
 RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-14 Cont ID  
Sent By jwitmer Date 2015-11-14 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2015-11-14 Time 06:58 Sent To  
Notes
2015-11-14 08:06:51BUILDING PLAN REVIEW
 W. P. B. REVISION: 15110411
 W. P. B. PERMIT; 14120130
 ADD: 1901 S. DIXIE HWY
 CONT: SISCA CONSTRUCTION
 TEL: 561-846-1179
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: SAT. NOV. 14/2014
 ACTION: DENIED
  
 1) SHEET R-2 SHOWS THE USE OF A MINI-PAKT CONDENSING
 UNIT FOR ROOF TOP USE. IN DETAIL C/R-2 SECTION A-A THE
 DETAIL SHOWS THE USE OF A 2X6 BUILT UP CURB. THIS
 DETAIL IS NOT FOR A RTU DOWN UNIT WHERE THERE WOULDBE
 NO ROOFING MATERIAL BENEATH IT. IT WOULD APPEAR 2
 SLEEPERS OR CURBS WOULD BE REQUIRED PLACED IN PARALLELL
 WHERE WOULD BE ROOFING BENEATH IT.
  
 PLEASE REVIEW SECTION 1509.7 OF THE 2010 FBC-B. 1509.7
 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
 TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS
  
 OF THE PERMITED SET OF DRAWINGS SHEET A4.0 ONLY SHOWS
 THE LOCATION OF THE ROOFTOP RTU UNITS. BOTH S3 & M1.3
 BOTH SHOW A ROOF TOP VEIW OF THE PROJECT THE 3 RTU'S
 AND INTAKE AND ROOF TOP EXHAUST FANS. THERE IS A NOTE
 THE WALKIN CONDENSING UNIT TO BE REMOTE. FINAL LOCATIN
 SHALL BE DETERMINED BY OWNER/ ARCHITECT. REVISION #
 15090594 DOES NOT SHOW A REVISION TO THE ROOF PLAN NOR
 WAS SHEET S3 UPDATED TO SHOW NEW LOCATIONS, SHEET M1.3
 DOES SHOW ON THE MECHANICAL ROOF TOP SHEET A REVISION
 SHOWING THE LOCATION FOR 3 NEWLY LOCATED, (NOT
 HIGHLIGHTED SHOWING A REVISION), ROOF TOP CU UNITS, NO
 DETAILS UNDER MECHANICAL NOR STRUCTURAL SHEETS!!!!!
  
 THE STRUCTURAL ENGINEER HAS NOT INDICATED ON ANY PLANS
 HOW THIS UNIT WILL ATTACH TO THE MWFRS. THE ENGINEER
 HAS PROVIDED (PERMIT SET OF DRAWINGS) DETAILS ON SHEET
 S6 FOR THE ATTACHMENT OF THE RTU'S CURB TO THE MWFRS
 AND THE CLIP SYSTEM FOR MOUNTING THE RTU TO THE CURB.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 18:16 Rev Time 0.00
Received By albarran Date 2016-02-29 Time 17:42 Sent To I
Notes
2016-02-29 18:17:38PREVIOUSLY MADE COMMENTS HAVE BEEN SATISFACTORILY
 ADDRESSED. THE ENGINEER HAS NOT DEFINED THE FINAL
 LOCATION OF THE REFRIGERATION EQUIPMENT. REGARDLESS OF
 LOCATION AS LONG AS THERE IS AN OUTLET WITHIN 25' ALL
 IS GOOD.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 09:25 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 09:08 Sent To I
Notes
2015-11-24 09:29:03IN ADDITION TO THE ALREADY MENTIONED COMMENTS FROM THE
 MECHANICAL & BUILDING REVIEWS, SPEC SHEETS INDICATING
 MINIMUM LOAD AND MAX OCP SHALL BE PROVIDED. NEC 210 .63
 REQUIRES THAT THERE BE A 15 20 AMP 125 VOLT GFCI
 SERVICE OUTLET WITHIN 25' OF THE UNIT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-11 Cont ID  
Sent By jwitmer Date 2016-04-11 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2016-04-04 Time 11:28 Sent To  
Notes
2016-04-04 11:28:22CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-18 Cont ID  
Sent By ccole Date 2016-03-18 Time 15:22 Rev Time 0.00
Received By ccole Date 2016-03-08 Time 12:46 Sent To  
Notes
2016-03-08 13:23:47B13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 18:39 Rev Time 0.00
Received By albarran Date 2015-12-31 Time 16:49 Sent To  
Notes
2016-02-29 18:41:132/29/16 PASSED ELECTRICAL REVIEW BUT OTHER TRADE ISSUES
 REMAIN . CONTRACTOR NOTIFIED VIA VOICE MAIL AT OFFICE
 NUMBER. FILE SENT TO SMALL DENIED BIN S. MA
2015-12-31 16:55:12B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 09:30 Rev Time 0.00
Received By albarran Date 2015-11-10 Time 09:08 Sent To  
Notes
2015-11-24 09:34:2311/24/15 FAILED ELECTRICAL REVIEW. IN LIEU OF THE
 MISSING EMAIL ADDRESS, AN ATTEMPT WAS MADE VIA PHONE TO
 CONTACT THE CONTRACTOR ON CELL PHONE (DISCONNECTED
 NUMBER). SENT TO SMALL DENIED BIN "S". MA
2015-11-12 09:09:35B04

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-04-04 Cont ID  
Sent By ccole Date 2016-04-04 Time 13:44 Rev Time 0.00
Received By ccole Date 2016-04-04 Time 13:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-18 Cont ID  
Sent By ccole Date 2016-03-18 Time 15:16 Rev Time 0.00
Received By ccole Date 2016-03-18 Time 15:15 Sent To  
Notes
2016-03-18 15:22:253RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110411
 3/18/16
  
 1) THE REVISED PLANS DO NOT PROVIDE A STRUCTURAL DETAIL
 FOR MOUNTING THE COLD ZONE UNIT TO THE ENGINEERED CURB-
 PLEASE PROVIDE THE ENGINEERING.
 2) SHEET S3: IT APPEARS THAT WORKING CLEARANCE ON THE
 NORTH SIDE OF THE COLD ZONE WILL BE OBSTRUCTED BY THE
 SKYLIGHT. IS THIS THE ACTUAL LOCATION OF THE UNIT?
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-04 Cont ID  
Sent By ccole Date 2016-01-04 Time 11:03 Rev Time 0.00
Received By ccole Date 2016-01-04 Time 11:03 Sent To  
Notes
2016-01-04 11:10:492ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110411
 01/04/16
  
 THE PREVIOUS (1ST) REVIEW COMMENTS STILL EXIST. I HAVE
 REPRINTED THEM BELOW WITH SOME ADDITIONAL NOTES IN
 PARENTHESIS.
 1) SUBMIT A REVISED M1.3 PLAN SHEET SHOWING THE
 LOCATION OF THE COLDZONE MINI-PAK ROOFTOP UNIT. (THE
 REQUESTED M1.3 SHEET WAS NOT REVISED AND SUBMITTED).
 2) SUBMIT A REVISED S3 SHEET SHOWING THE ROOFTOP
 LOCATIONS OF THE COLDZONE MINI-PAK UNIT, AND THE
 WALK-IN COOLER AND FREEZER CONDENSERS. (COLD ZONE
 ROOFTOP UNIT IS NOT SHOWN ON THE REVISED S3 PLAN DATED
 12/18/15.)
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 MINI-PAK AND THE CONDENSERS TO THE ROOF STRUCTURE-
 SECTION 301.12 FBC-10 MECHANICAL. PLEASE NOTE THAT THE
 COLDZONE SUBMITTAL DOES NOT PROVIDE WIND LOAD DESIGN
 CRITERIA OR STRUCTURAL DETAILS. (THERE ARE NOTES ON S3
 BY THE WALK-IN CONDENSERS REFERENCING THE ARCHITECTURAL
 ROOF PLAN AND NOA'S, HOWEVER NEITHER WERE SUBMITTED).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By hmoser Date 2015-11-16 Time 15:58 Rev Time 0.00
Received By ccole Date 2015-11-16 Time 15:58 Sent To  
Notes
2015-11-16 16:01:341ST REVIEW: FBC 2010 MECHANICAL
 REVISION #15110411
 MASTER #14120130
  
 1) SUBMIT A REVISED M1.3 PLAN SHEET SHOWING THE
 LOCATION OF THE COLDZONE MINI-PAK ROOFTOP UNIT.
 2) SUBMIT A REVISED S3 SHEET SHOWING THE ROOFTOP
 LOCATIONS OF THE COLDZONE MINI-PAK UNIT, AND THE
 WALK-IN COOLER AND FREEZER CONDENSERS.
 3) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 MINI-PAK AND THE CONDENSERS TO THE ROOF STRUCTURE-
 SECTION 301.12 FBC-10 MECHANICAL. PLEASE NOTE THAT THE
 COLDZONE SUBMITTAL DOES NOT PROVIDE WIND LOAD DESIGN
 CRITERIA OR STRUCTURAL DETAILS.
 4) THE SUBMITTED COLDZONE SPECS SHOW A 6" HIGH CURB
 BASE FOR SUPPORT OF THE MINI-PAK ON THE ROOF. PLEASE
 SEE SECTION 1509.7 FBC-10 BUILDING- CURBS SHALL BE
 RAISED MINIMUM 8" ABOVE THE ROOF SURFACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-11-18 Cont ID  
Sent By tlarge Date 2015-11-18 Time 09:03 Rev Time 0.00
Received By tklarge Date 2015-11-18 Time 08:56 Sent To  
Notes
2015-11-18 09:03:34NO CHANGES TO PLUMBING SYSTEM ON THIS REVISION.