Plan Review Details - Permit 15110375
Plan Review Stops For Permit 15110375
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-08 Cont ID  
Sent By shill Date 2016-03-08 Time 08:31 Rev Time 0.00
Received By shill Date 2016-03-08 Time 08:31 Sent To  
Notes
2016-03-08 08:32:49REVIEWED HAZARDOUS CHEMICAL INVENTORY/USE LETTER
 PROVIDED BY ARCHITECT, STEVEN E. MYOTT
 FORWARDED LETTER TO FIRE (PER PETER LEDUC, A REVIEW OF
 HAZARDOUS CHEMICAL REQUIREMENTS WILL BE PERFORMED AT
 INSPECTION)
 PROVISO; ORIGINAL SIGNED, SEALED LETTER TO BE SENT VIA
 MAIL FOR OUR RECORDS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By shill Date 2016-02-03 Time 12:55 Rev Time 0.00
Received By shill Date 2016-02-02 Time 18:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 15:01 Rev Time 0.00
Received By shill Date 2015-11-21 Time 15:01 Sent To  
Notes
2015-11-21 15:24:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLAN TO INCLUDE THE CHANGE OF OCCUPANCY FROM
 S2 (PERMIT 05020247) TO BUSINESS OCCUPANCY, FBC 107.
  
 2. FBC 2014 ACCESSIBILITY TABLE 404.2.4.1, 18IN
 MANEUVERING CLEARANCE REQUIRED FOR DOORS 01 AND 02,
 PULL SIDE.
  
 3. SEE PAGE A0.01 OF PERMIT #05020247. SHEET CVR
 SUBMITTED DECLARES A IIIB BUILDING TYPE, BUT THE
 BUILDING WAS CONSTRUCTED AS TYPE V. A TYPE IIIB
 REQUIRES 2 HOUR EXTERIOR WALLS.
  
 THE WEST WALL IS A 1 HOUR RATED WALL BASED ON DISTANCE
 TO ASSUMED PROPERTY LINE. PLEASE REVISE BUILDING TYPE
 TO TYPE V OR SHOW COMPLIANCE WITH TYPE IIIB BUILDING
 TYPE (TABLE 601, 602, 705.8).
  
 4. USE OF MEZZANINE IS NOT CLEAR. SEE FBC 2014
 ACCESSIBILITY 201.1.1 AND REVISE PLAN TO INCLUDE
 EXCEPTION TO VERTICAL ACCESSIBILITY (OR PROVIDE
 VERTICAL ACCESSIBILITY).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-22 Cont ID  
Sent By mvaldes Date 2016-02-22 Time 13:38 Rev Time 0.00
Received By mvaldes Date 2016-02-22 Time 13:38 Sent To  
Notes
2016-02-22 13:42:14REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - MISSING SUM ELECTRICAL SHEETS PLS CLARIFY.
 - EXIT & EMERGENCY LIGHTING LOCATIONS TO BE VERIFIED AT
 THE TIME OF INSPECTIONS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By mvaldes Date 2015-12-07 Time 11:18 Rev Time 0.00
Received By mvaldes Date 2015-12-07 Time 11:18 Sent To  
Notes
2015-12-07 13:19:281ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 THE ELECTRICAL REVIEW IN ENTIRETY IS RESERVED PENDING
 RESPONSES TO FIRE , BUILDING , AND MECHANICAL REVIEW
 COMMENTS REGARDING FIRE PENETRATIONS ON WALLS AND
 PARTITION.
 PLAN E 1 SHOWS 400 AMP PANEL AS EXISTING AND I BELIEVE
 ITS NEW ACCORDING TO THE SCOPE OF WORK.
 PLAN E 3 PLEASE SHOW EMERGENCY LIGHTING IN STAIRS FBC
 1006 NEC 700.16
 FBC 1006.1 MEANS OF EGRESS ILLUMINATION.
 FBC 1006.1.1 PER FBC-R, T-E3403
 ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE.
 700.16 EMERGENCY ILLUMINATION. EMERGENCY ILLUMINATION
 SHALL INCLUDE ALL REQUIRED MEANS OF EGRESS LIGHTING,
 ILLUMINATED
 EXIT SIGNS, AND ALL OTHER LIGHTS SPECIFIED AS NECESSARY
 TO PROVIDE REQUIRED ILLUMINATION.
 PROVIDE MANUFACTURE SPECS ON AC EQUIPMENT.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-27 Cont ID  
Sent By pleduc Date 2016-01-27 Time   Rev Time 0.00
Received By pleduc Date 2016-01-26 Time 14:45 Sent To  
Notes
2016-01-27 09:44:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET E 4 - EXIT AND EMERGECNY LIGHTS ARE NOT
 INDICATED ON THE SHEET. THEY ARE SHOWN AS EXISTING ON M
 1-1, 1-2. EXISTING EXIT AND EMERGENCY LIGHTS WILL BE
 VERIFIED AND CONFIRMED ON FINAL INSPECTION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By GJT Date 2015-11-20 Time   Rev Time  
Received By   Date 2015-11-20 Time   Sent To  
Notes
2015-11-20 11:50:091. PROVIDE RAILING DETAIL FOR MEZZANINE
 2. PROVIDE DOOR RATINGS FOR DOORS 04, 05, 06
 3. PROVIDE STAIR DETAIL
 4. PROVIDE RATING OF WAREHOUSE WALL THAT PROVIDES
 SEPARATION TO THE OFFICE SPACE
 5. PROVIDE RATING OF STORAGE ROOM WALL THAT PROVIDES
 SEPERATION FROM THE OFFICE SPACE
 6. REVIEW / REVISE FIRST FLOOR EGRESS PLAN (CAN NOT
 EGRESS FROM LOWER HAZARD THROUGH HIGHER HAZARD
 7. STORAGE SHOW UNDER STAIR. PROVIDE DETAIL OF
 PROTECTION (SPRINKLER, ETC..)
 8. SPRINKLER MODIFICATIONS MAY BE NEEDED. HAVE
 EVALUATED. IF NEEDED SUBMIT UNDER SEPERATE PERMIT.
 9. FIRE ALARM MODIFICATIONS MAY BE NEEDED TO MEET
 NOTIFICATION REQUIREMENTS, HAVE EVALUATED. IF NEEDED
 SUBMIT UNDER SEPERATE PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-08 Cont ID  
Sent By ccole Date 2016-03-08 Time 09:47 Rev Time 0.00
Received By ccole Date 2016-01-19 Time 13:48 Sent To  
Notes
2016-03-08 08:33:133/8/16 ROUTED PLAN TO CCOLE DESK
  
2016-02-29 07:40:092/29 ON SH DESK PENDING RECEIPT OF EMAIL FROM ARCHITECT
  
  
2016-01-20 13:48:13B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-07 Cont ID  
Sent By cpuell Date 2015-12-07 Time 14:42 Rev Time 0.00
Received By cpuell Date 2015-11-09 Time 09:23 Sent To  
Notes
2015-11-10 09:23:40B03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-08 Cont ID  
Sent By ccole Date 2016-03-08 Time 09:47 Rev Time 0.00
Received By ccole Date 2016-03-08 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By ccole Date 2015-11-20 Time 14:51 Rev Time 0.00
Received By ccole Date 2015-11-20 Time 14:51 Sent To  
Notes
2015-12-07 12:06:54C
2015-11-20 15:36:361ST REVIEW 2014 MECHANICAL
 PERMIT #15110375
 11/20/15
  
 1) THE MECHANICAL REVIEW IN ENTIRETY IS RESERVED
 PENDING RESPONSES TO FIRE AND BUILDING PLAN REVIEWS
 COMMENTS REGARDING FIRE-RATED WALLS AND PARTITIONS.
 PLEASE NOTE THAT FIRE DAMPERS MAY BE REQUIRED FOR AC
 DUCTS PENETRATING THESE WALLS AND PARTITIONS, ALONG
 WITH OTHER CODE COMPLIANCES.
 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC-2 MINI-SPLIT SYSTEM IN THE STORAGE ROOM- SEE
 SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 3) PROVIDE ENERGY CALCULATIONS- REFER TO SECTION C101.2
 FBC-14 ENERGY CONSERVATION
 4) M1-1: PROVIDE WIND LOAD ENGINEERING AND DESIGN
 CRITERIA FOR INSTALLATION OF THE NEW CONDENSER AND
 EXHAUST FAN ON THE ROOF- SECTION 301.15 FBC-14
 MECHANICAL
 5) M1-1 & M1-3: EF-2 IS INDICATED AS SERVICING THE
 WAREHOUSE IN THE EQUIPMENT SCHEDULE BUT APPEARS TO BE
 OVER THE LAB IN THE ROOF DRAWING: PLEASE CLARIFY OR
 CORRECT.
 6) M1-1 & M1-2: SHOW THE LOCATIONS OF KEY NOTES 6, 8, &
 16.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-24 Cont ID  
Sent By tklarge Date 2016-01-24 Time 03:49 Rev Time 0.00
Received By tklarge Date 2016-01-24 Time 03:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-21 Cont ID  
Sent By tklarge Date 2015-11-21 Time 05:04 Rev Time 0.00
Received By tklarge Date 2015-11-21 Time 04:28 Sent To  
Notes
2015-11-21 04:59:361) SHT. P-1 SHOWS THE SANITARY TO THE SINKS AS 4 INCH
 AND SHT. P-2 SHOW 3 INCH. CLARIFY.
 2) SHT. P-1 SHOWS THE SANITARY TO THE EDF AS 3 INCH AND
 SHT. P-2 SHOWS 2 INCH. CLARIFY.
 3) SHT. P-2 - PART OF THE WATER RISER IS CUT OFF.
 SUBMIT A COMPLETE WATER RISER DIAGRAM FOR REVIEW THAT
 SHOWS ALL THE PLUMBING FIXTURES. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 4) A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQD.ON AN
 ACCESSIBLE LEVEL PER THE 2014 FBC-ACCESSIBILITY SEC.
 211.2.
 5) HOT WATER SHALL BE SUPPLIED TO THE HAND SINK, BREAK
 ROOM SINK AND THE JANITOR SINK PERR THE 2014
 FBC-PLUMBING SEC.607.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR