Plan Review Details - Permit 15110258
Plan Review Stops For Permit 15110258
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-11-20 Cont ID  
Sent By jgomez Date 2015-11-20 Time 17:42 Rev Time 0.00
Received By jgomez Date 2015-11-20 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-11-13 Cont ID  
Sent By rmcdouga Date 2015-11-13 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2015-11-13 Time 18:47 Sent To  
Notes
2015-11-13 18:47:10PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RAS 117 CALCULATIONS ARE INCORRECT. THE VULT
 WINDSPEED FOR RISK CATEGORY IV FOR THIS BUILDING IS
 GREATER THAN 170MPH. SEE WIND SPEED MAP FIGURE 1609B IN
 THE FBC-BUILDING, 5TH EDITION (2014). THE FASTER WIND
 SPEED WILL CREATE INCREASED DESIGN PRESSURES. THE THREE
 ENHANCED FASTENING DOCUMENTS THAT WERE SUBMITTED ALL
 HAVE THE SAME ROOF ZONE PRESSURES SPECIFIED, HOWEVER,
 THE LAP SPACING WAS DECREASED. PLEASE REVISE THE
 DOCUMENTS TO COMPLY WITH THE 2014 FBC.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-12 Cont ID  
Sent By jgomez Date 2015-11-12 Time 13:17 Rev Time 0.00
Received By jgomez Date 2015-11-12 Time 13:17 Sent To  
Notes
2015-11-12 13:29:47RE-ROOF SECOND BUILDING REVIEW CHECKLIST.COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF
 FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS
 REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY.
 RESPONSE: THE SELECTED RISK CATEGORY IS INCORRECT
 AGAIN. THIS IS A HOSPITAL. THIS IS NOT RISK CATEGORY
 III. THE WIND VELOCITY AND DESIGN DESIGN PRESSURES NEED
 TO BE REVISED ACCORDINGLY ALSO. ENGINEER TO REVIEW
 FIGURE 1609B OF FBC-BUILDING, 5TH EDITION (2014) AND
 REVISE ULTIMATE DESIGN WIND SPEED AND DESIGN PRESSURES
 ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By jgomez Date 2015-11-09 Time 18:40 Rev Time 0.00
Received By jgomez Date 2015-11-09 Time 17:59 Sent To  
Notes
2015-11-09 18:40:59RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- ENGINEER TO REVISE THE RAS 117 CALCULATIONS
 SUBMITTED:
 A) THE RISK CATEGORY IS INCORRECT. SEE TABLE 1604.5 OF
 FBC-BUILDING, 5TH EDITION (2014) AND REVISE AS
 REQUIRED. REVISE DESIGN PRESSURES ACCORDINGLY
  
 B) THE FASTENER SPACING SPECIFIED DOESN'T MATCH
 SELECTED SYSTEM W-39. REVISE AS REQUIRED TO MATCH.
 ALSO, REVISE FASTENER SPACING FOR ROOF ZONES 2 AND 3
 ACCORDINGLY. SEC. 1609 FBC BUILDING, 5TH EDITION
 (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-20 Cont ID  
Sent By jgomez Date 2015-11-20 Time 15:51 Rev Time 0.00
Received By jgomez Date 2015-11-20 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-13 Cont ID  
Sent By rmcdouga Date 2015-11-13 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2015-11-13 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-09 Cont ID  
Sent By jgomez Date 2015-11-09 Time 18:08 Rev Time 0.00
Received By jgomez Date 2015-11-09 Time 15:23 Sent To  
Notes
2015-11-09 15:23:30JGOMEZ