| 2015-11-19 09:35:02 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/ |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6700 |
| | [email protected] |
| | |
| | |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEME |
| | |
| | 1 PLEASE PROVIDE PHTOMETRIC LIGHTING PLANS ( MAKE SURE |
| | THE PLANS DON'T DEPRECIATE ACCESSIBILITY CONTRAST |
| | LIGHTING IN AREAS THAT APPLY ) |
| | 2 PLEASE PROVIDE ENERGY CALCULATIONS PER FBC SECTION |
| | C405 ENERGY CODE |
| | 3 PLEASE PROVIDE LIGHT POLES WIND CACULATIONS PER |
| | CHAPTER 16 FBC |
| | 4 PLEASE CONTACT PUBLIC SAFETY DEPARTMENT FOR SECURIY |
| | REASONS |
| | 5 PLEASE MAKE SURE ALL LIGHTING IS UL LISTED. |