| 2015-11-05 15:21:18 | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | ELEVATION CERTIFICATE REVIEW |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE AS BUILT CONDITIONS ARE NOT CONSISTENT WITH THE |
| | LATEST APPROVED REVISION TO THE ISSUED PERMIT. BASED ON |
| | THE ELEVATION CERTIFICATE, THERE ARE FOUR (4) |
| | NON-ENGINEERED FLOOD OPENINGS WITHIN 1.0 FOOT ABOVE |
| | ADJACENT GRADE IN THE ATTACHED GARAGE. PER THE |
| | ELEVATION CERTIFICATE THERE IS A TOTAL NET AREA OF |
| | FLOOD OPENINGS OF 548 SQIN. THE REVISED PLANS SHOW SIX |
| | (6) "SMART VENT" ENGINEERED FLOOD VENTS ON THREE |
| | DIFFERENT WALLS. SUBMIT REVISED DRAWINGS THAT SHOW THE |
| | AS BUILT CONDITIONS AND ARE CONSISTENT WITH THE |
| | ELEVATION CERTIFICATE. |
| | |
| | ONLY MATERIALS THAT ARE RESISTANT TO FLOOD DAMAGE ARE |
| | PERMITTED BELOW THE DFE (DESIGN FLOOD ELEVATION). THE |
| | DFE FOR THIS PROJECT IS 7.5' NGVD 1929. |
| | |
| | 2) REGARDING THE ELEVATION CERTIFICATE PREPARED BY |
| | CLYDE O. MCNEAL, PLEASE ADDRESS THE FOLLOWING: |
| | |
| | A. THE OWNER'S NAME IS NOT CORRECT. THE OWNERS ARE |
| | JESUS J. AZQUETA JR. AND RACHEL AZQUETA. |
| | |
| | B. THE TWO LETTER STATE ABBREVIATION SHOULD BE ENTERED |
| | AT B3. |
| | |
| | C. THE SURVEYOR'S ORIGINAL HANDWRITTEN SIGNATURE IS |
| | REQUIRED ON THE CERTIFICATE. |
| | |
| | D. THE LATITUDE AND LONGITUDE THAT IS LISTED, PLACES |
| | THE POINT ON THE LOT TO THE NORTH OF THE PROJECT |
| | PROPERTY. THE LATITUDE FOR THIS LOT AT 105 GREGORY ROAD |
| | IS 26 DEGREES 38 MINUTES AND 45.86 SECONDS. |
| | |
| | E. PER THE FEMA 2012 EDITION OF THE ELEVATION |
| | CERTIFICATE INSTRUCTIONS, THE METHOD USED TO DETERMINE |
| | THE LATITUDE AND LONGITUDE IS REQUIRED TO BE INDICATED |
| | IN THE SECTION D COMMENT AREA. |
| | |
| | F. UNDER C2 THE ELEVATION DATUM USED FOR THE ELEVATIONS |
| | IN ITEMS A) THROUGH H) HAVE BOTH THE NGVD 1929 AND THE |
| | NAVD 1988 BOXES MARKED. THE INSTRUCTIONS REQUIRE THAT |
| | ALL ELEVATIONS MUST USE THE SAME DATUM ON WHICH THE BFE |
| | IS BASED, WHICH IS NGVD 1929 FOR THIS PROJECT. YOU ARE |
| | REQUIRED TO SHOW THE CONVERSION FROM THE FIELD SURVEY |
| | DATUM USED IF IT DIFFERS FROM THE DATUM USED FOR THE |
| | BFE AND INDICATE THE CONVERSION SOFTWARE USED IN THE |
| | COMMENTS AREA OF SECTION D. |
| | |
| | G) THE INSTRUCTIONS REQUIRE 3" X 3" COLOR PHOTOS OF ALL |
| | SIDES OF THE STRUCTURE THAT ARE IDENTIFIED AS "FRONT |
| | VIEW" , "REAR VIEW", "RIGHT SIDE VIEW" AND "LEFT SIDE |
| | VIEW". PHOTOGRAPHS OF THE FLOOD OPENINGS OR VENTS ARE |
| | REQUIRED. |
| | |
| | H) SUBMIT PHOTOGRAPHS OF ALL MECHANICAL AND UTILITY |
| | EQUIPMENT LOCATED OUTSIDE THE BUILDING SHOWING (1) ITS |
| | RELATION TO THE BUILDING AND GROUND AND (2) ITS |
| | REQUIRED ANCHORING. |
| | |
| | |
| | |