Plan Review Details - Permit 15110135
Plan Review Stops For Permit 15110135
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-09 Cont ID  
Sent By rmcdouga Date 2015-11-09 Time 15:27 Rev Time 0.00
Received By rmcdouga Date 2015-11-09 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By rmcdouga Date 2015-11-05 Time 07:36 Rev Time 0.00
Received By rmcdouga Date 2015-11-05 Time 07:36 Sent To  
Notes
2015-11-05 07:36:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) TWO DIFFERENT PRODUCT APPROVALS FOR THE CERTAINTEED
 MODIFIED ROOFING WERE SUBMITTED. THEY EACH HAVE
 DIFFERENT REQUIREMENTS. THE MIAMI-DADE NOA REQUIRES
 SIGNED AND SEALED RAS 117 CALCULATIONS PER LIMTATION #7
 ON PAGE 16. REMOVE ONE OF THEM FROM YOUR SUBMITTAL.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-11-05 Cont ID  
Sent By fmittner Date 2015-11-05 Time 14:28 Rev Time 0.00
Received By fmittner Date 2015-11-05 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-05 Cont ID  
Sent By cpuell Date 2015-11-05 Time 15:45 Rev Time 0.00
Received By cpuell Date 2015-11-04 Time 15:05 Sent To  
Notes
2015-11-04 15:05:34RMCDOUGAL