Plan Review Details - Permit 15110071
Plan Review Stops For Permit 15110071
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By jgomez Date 2015-11-24 Time 14:11 Rev Time 0.00
Received By jgomez Date 2015-11-24 Time 11:13 Sent To  
Notes
2015-11-24 11:27:53RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 *************COMMENTS FOR MAIN HOUSE PLANS SUBMITTED:
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- DESIGN PARAMETERS ON SHEET A-1 AND A-2: CLARIFY WHY
 THE DOORS AND WINDOWS POSITIVE DESIGN PRESSURES ARE
 HIGHER THAN THE NEGATIVE DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) NEW WINDOWS AS SHOWN ON PLANS.
  
 C) HURRICANE SHUTTERS IF GLAZING IN DOORS AND WINDOWS
 IS NOT IMPACT GLAZING. AND, PROVIDE SHUTTERS COMPLETE
 INSTALLATION SCHEDULE. SEE SHUTTERS INSTALLATION CITY
 SAMPLE OR PROVIDE COMPLETE SHUTTERS INFORMATION ON A
 DIFFERENT FORMAT.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 4- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ***************COMMENTS FOR DETACHED LAUNDRY ROOM:
 1- PROVIDE 2 SETS OF PLANS SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. ONLY ONE SET OF PLANS WAS
 SUBMITTED. SEC. 107.1 CITY AMENDMENTS.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW AWNINGS SHOWN ON FRONT AND RIGHT ELEVATIONS. OR
 PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT. .
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- DESIGN PARAMETERS ON SHEET A-1: CLARIFY WHY THE
 DOORS AND WINDOWS POSITIVE DESIGN PRESSURES ARE HIGHER
 THAN THE NEGATIVE DESIGN PRESSURES. SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW EXTERIOR DOORS AS SHOWN ON PLANS.
  
 B) HURRICANE SHUTTERS IF GLAZING IN DOORS IS NOT IMPACT
 GLAZING. AND, PROVIDE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. SEE SHUTTERS INSTALLATION CITY SAMPLE OR
 PROVIDE COMPLETE SHUTTERS INFORMATION ON A DIFFERENT
 FORMAT.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER OF RECORD TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 4- ENGINEER OF RECORD TO APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- REVISE DESIGN PARAMETERS ON SHEET A-1. THIS IS NOT
 ALTERATION LEVEL 1. THIS IS ALTERATION LEVEL 3. SEC.
 505 OF FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 ***PLEASE PROVIDE A RESPONSE LETTER SHOWING HOW EACH
 ITEM WAS ADDRESSED TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. SUBMIT OLD DRAWINGS
 FOR REFERENCE, BUT DON'T STAPLE THEM TO THE NEW SET OF
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By mvaldes Date 2015-11-30 Time 09:29 Rev Time 0.00
Received By mvaldes Date 2015-11-30 Time 09:29 Sent To  
Notes
2015-11-30 10:06:221ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
 NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH THAT
 OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT OCCUPANTS
 SHALL HAVE ACCESS TO OCP DEVICES.
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 (B) BRANCH CIRCUIT EXTENSIONS OR MODIFICATIONS ?
 DWELLING
 UNITS. IN ANY OF THE AREAS SPECIFIED IN 210.12(A),
 WHERE
 BRANCH-CIRCUIT WIRING IS MODIFIED, REPLACED, OR
 EXTENDED, THE
 BRANCH CIRCUIT SHALL BE PROTECTED BY ONE OF THE
 FOLLOWING:
 (1) A LISTED COMBINATION-TYPE AFCI LOCATED AT THE
 ORIGIN OF
 THE BRANCH CIRCUIT
 (2) A LISTED OUTLET BRANCH-CIRCUIT TYPE AFCI LOCATED AT
 THE
 FIRST RECEPTACLE OUTLET OF THE EXISTING BRANCH CIRCUIT
 (2) ISLAND COUNTERTOP SPACES. AT LEAST ONE RECEPTACLE
 SHALL BE INSTALLED AT EACH ISLAND COUNTERTOP SPACE WITH
 A
 LONG DIMENSION OF 600 MM (24 IN.) OR GREATER AND A
 SHORT
 DIMENSION OF 300 MM (12 IN.) OR GREATER.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 09:21 Rev Time 0.00
Received By tklarge Date 2015-11-16 Time 09:19 Sent To  
Notes
2015-11-16 09:21:40GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECTS THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
  
  
 THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-30 Cont ID  
Sent By cpuell Date 2015-11-30 Time 10:33 Rev Time 0.00
Received By cpuell Date 2015-11-03 Time 16:24 Sent To  
Notes
2015-11-04 16:24:52R13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By jgomez Date 2015-11-24 Time 17:11 Rev Time 0.00
Received By jgomez Date 2015-11-24 Time 17:10 Sent To  
Notes
2015-11-24 17:16:37RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PERMIT APPLICATION CALLS FOR "UPGRADE A/C". THERE IS
 NO INFORMATION SUBMITTED FOR A/C WORK. PROVIDE COMPLETE
 SET OF PLANS AND EQUIPMENT SIZING CALCULATIONS. SEC.
 107.3.5.3(10) CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 06:34 Rev Time 0.00
Received By tklarge Date 2015-11-16 Time 06:16 Sent To  
Notes
2015-11-16 06:34:201) SUBMIT A SANITARY RISER DIAGRAM FOR CHANGES BEING
 MADE TO THE PLUMBING SYSTEM. WPB AMEND. TO FBC
 SEC.107.3.5.3.
 2) SUBMIT 2 SETS OF PLANS FOR THE LAUNDRY ROOM
 RENOVATION. WPB AMEND. TO FBC SEC.107.1.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-23 Cont ID  
Sent By sgraham Date 2015-11-23 Time 12:49 Rev Time 0.00
Received By sgraham Date 2015-11-23 Time 12:48 Sent To  
Notes
2015-11-23 13:04:1711/23/15 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY OF THE
 PROPERTY.