| Plan Review Stops For Permit 15110054 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2016-01-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-01-11 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-01-11 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-01-08 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-01-08 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2016-01-08 10:54:12 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | INFORMATION REQUESTED FROM 1ST REVIEW NOT PROVIDED. | | | PROVIDE FOUNDATION DETAIL. | | | | | | CONSTRUCTION DOCUMENTS TO BE SIGNED BY DESIGNER. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-11-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-11-24 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-25 |
Time |
15:09 |
Sent To |
E |
|
| Notes |
| 2015-11-25 15:11:31 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PROVIDE FOUNDATION PLAN AND SECTIONAL VIEW OF | | | STRUCTURE. | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-01-07 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-01-07 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2016-01-07 14:44:18 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | ELECRTICAL PERMIT NOT REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-11-25 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2015-11-25 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2015-11-25 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2015-11-25 15:51:20 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | PHIL PETTY | | | 561-805-6742 | | | [email protected] | | | | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | FBC-EC 505.2.4 - PROVIDE A TIME CLOCK OR ASTRONOMICAL | | | SWITCH TO TURN OFF DURING DAYLIGHT HOURS. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-01-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-01-08 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-12-17 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2015-12-18 09:36:59 | RESUB ROUTED ESCHNEIDER VIA SGRAHAM'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-11-25 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-11-25 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2015-11-03 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2015-11-03 09:41:24 | ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2016-01-07 |
Time |
08:45 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2016-01-07 |
Time |
08:45 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-11-24 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2015-11-24 |
Time |
10:42 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2015-11-24 |
Time |
10:42 |
Sent To |
B |
|
| Notes |
| 2015-11-24 10:49:03 | FAILED | | | | | | 1) IN ACCORDANCE WITH SECTION 94-407(3)E OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, THE SIGN IS REQUIRED | | | TO BE LOCATED A MINIMUM OF 15 FEET FROM THE PROPERTY | | | LINE. THIS SHALL BE CLEARLY INDICATED ON THE PLANS. | | | | | | 2) PROVIDE THE CALCULATIONS TO VERIFY THAT THE SIGN | | | DOES NOT EXCEED 20 SQUARE FEET. | | | | | | 3) INCLUDE A NOTE ON THE SIGN ELEVATION PLAN THAT THAT | | | LANDSCAPE PLANTINGS SHALL BE INSTALLED AND MAINTAINED | | | AT THE BASE OF THE SIGN. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|