Plan Review Details - Permit 15101067
Plan Review Stops For Permit 15101067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-05 Cont ID  
Sent By cthroop Date 2016-02-05 Time 11:20 Rev Time 0.00
Received By cthroop Date 2016-02-05 Time 11:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-14 Cont ID  
Sent By skennedy Date 2015-12-14 Time 12:20 Rev Time 0.00
Received By skennedy Date 2015-12-14 Time 12:20 Sent To  
Notes
2015-12-14 12:24:072ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 1. THE PLAN IS REDUCED AND TOO SMALL TO READ AND TOO
 SMALL FOR RECORD RETENTION. PLEASE PROVIDE AN ENLARGED
 PLAN. COMMENT IS SEMI COMPLIED, ADDITIONAL PLANS ARE
 REQUIRED.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 2. THE WIND DESIGN AND STRUCTURAL ATTACHMENT
 INFORMATION IS UNCLEAR AND APPEARS GENERIC. SUCH DESIGN
 MUST BE SITE SPECIFIC. PLEASE PROVIDE THE SPECIFIC
 APPLICABLE DESIGN PRESSURES AS DETERMINED USING THE
 METHODS IN FBC-R301.1.3 ENGINEERED DESIGN. PLEASE
 PROVIDE A SPECIFIC PLAN INDICATING THE LOCATION AND
 TYPE OF CONNECTORS TO BE INSTALLED. PROVIDE WIND DESIGN
 CRITERIA FOR THE SPECIFIC GEOGRAPHICAL LOCATION OF THE
 BUILDING AND CONSIDERING THE PROPOSED LOCATION OF THE
 SYSTEM ON THE BUILDING. IF DESIGN IS NOT TO BE PROVIDED
 BY A FLORIDA LICENSED ENGINEER, THEN PROVIDE STRUCTURAL
 CALCULATIONS TO JUSTIFY THE DESIGN. NOT COMPLIED
  
 YOU HAVE SUBMITTED A DESIGN USING SOFTWARE TO DEVELOP A
 LAYOUT FOR AN ARRAY WHICH SPECIFIES CERTAIN COMPONENTS
 OF A SYSTEM. THE INFORMATION IS NOT SITE SPECIFIC AND
 DOES NOT BEAR THE SEAL OF AN ENGINEER. ALTHOUGH CERTAIN
 DESIGN PARAMETERS ARE EVIDENT IN THE WIND LOAD ANALYSIS
 PLAN, SUCH AS WIND SPEED, EXPOSURE, AND BUILDING
 HEIGHT, YOU HAVE PROVIDED SOME PAGES RELATED TO SNOW
 LOADS RATHER THAN WIND LOADS FROM PART OF A GENERAL
 DESIGN ANALYSIS OF THE PRODUCT BY SML INC. PLEASE
 PROVIDE SPECIFIC WIND DESIGN PRESSURES. YOU MAY PROVIDE
 DESIGN LOADS FROM CHARTS BY THE MANUFACTURERS
 CONSULTANT ENGINEER, BUT DETERMINATION OF SYSTEM
 COMPONENTS SUCH AS CONNECTOR'S TO THE ROOF AND SPACING
 OF SUCH CONNECTOR'S SHOULD BE VERIFIED BY AN ENGINEER
 TO ASSURE THE SYSTEM DESIGN CAN WITHSTAND WIND
 PRESSURES. YOUR INCLUSION OF SNOW LOAD CHARTS IS NOT
 USEFUL. THE SPEC SHEETS PROVIDED FOR THE FLASHFOOT
 ANCHORS DO NOT SPECIFY THE LENGTH OF THE ANCHOR AND
 PROVIDES TWO POSSIBLE BOLT DIAMETERS. THE ANCHOR
 INDICATES IT IS FOR SHINGLED ROOF WHICH SUGGEST IT IS
 FOR SLOPED APPLICATIONS AND NOT FOR A FLAT ROOF AS
 PROPOSED. THE DOCUMENT FROM IRONRIDGE INDICATES THE
 2010 FBC IN IT'S CODE COMPLIANCE PAGE, THE VERSION IS
 INCORRECT.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-21 Cont ID  
Sent By skennedy Date 2015-11-21 Time 11:00 Rev Time 0.00
Received By skennedy Date 2015-11-21 Time 11:00 Sent To  
Notes
2015-11-21 11:12:531ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE PLAN IS REDUCED AND TOO SMALL TO READ AND TOO SMALL
 FOR RECORD RETENTION. PLEASE PROVIDE AN ENLARGED PLAN.
  
 FBC FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 THE WIND DESIGN AND STRUCTURAL ATTACHMENT INFORMATION
 IS UNCLEAR AND APPEARS GENERIC. SUCH DESIGN MUST BE
 SITE SPECIFIC. PLEASE PROVIDE THE SPECIFIC APPLICABLE
 DESIGN PRESSURES AS DETERMINED USING THE METHODS IN
 FBC-R301.1.3 ENGINEERED DESIGN. PLEASE PROVIDE A
 SPECIFIC PLAN INDICATING THE LOCATION AND TYPE OF
 CONNECTORS TO BE INSTALLED. PROVIDE WIND DESIGN
 CRITERIA FOR THE SPECIFIC GEOGRAPHICAL LOCATION OF THE
 BUILDING AND CONSIDERING THE PROPOSED LOCATION OF THE
 SYSTEM ON THE BUILDING. IF DESIGN IS NOT TO BE PROVIDED
 BY A FLORIDA LICENSED ENGINEER, THEN PROVIDE STRUCTURAL
 CALCULATIONS TO JUSTIFY THE DESIGN.
  
 NAMASTE'
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-07 Cont ID  
Sent By skennedy Date 2015-12-14 Time 14:34 Rev Time 0.00
Received By mvaldes Date 2015-12-07 Time 09:56 Sent To  
Notes
2015-12-07 09:56:51ROUTED TO BUILDING

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mvaldes Date 2015-11-25 Time 10:03 Sent To  
Notes
2015-11-25 10:06:501ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
  
 PLEASE PROVIDE RISER DIAGRAM WITH A SITE PLAN SHOWING
 EXACT LOCATIONS OF DEVICES AND EQUIPMENT TO COMPLY WITH
 LABELING AND WIRING METHOD REQUIREMENTS OF ARTICLE 690
 NEC 2011.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-05 Cont ID  
Sent By cthroop Date 2016-02-05 Time 11:20 Rev Time 0.00
Received By cthroop Date 2016-01-25 Time 15:09 Sent To  
Notes
2016-01-25 15:09:35RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-14 Cont ID  
Sent By skennedy Date 2015-12-14 Time 14:34 Rev Time 0.00
Received By skennedy Date 2015-12-04 Time 08:26 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-25 Cont ID  
Sent By cpuell Date 2015-11-25 Time 10:23 Rev Time 0.00
Received By cpuell Date 2015-10-29 Time 15:27 Sent To  
Notes
2015-11-02 18:29:12TO ELEC BOX
  
2015-10-30 15:27:57ROUTED TO ZONING