Plan Review Details - Permit 15101064
Plan Review Stops For Permit 15101064
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-08-20 Cont ID  
Sent By jwitmer Date 2016-08-20 Time 09:10 Rev Time 0.00
Received By jwitmer Date 2016-08-17 Time 16:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-03-24 Cont ID  
Sent By jwitmer Date 2016-03-24 Time 12:15 Rev Time 0.00
Received By jwitmer Date 2016-03-24 Time 11:54 Sent To  
Notes
2016-03-24 11:59:53BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15101064
 ADD: 112 N. DIXIE HWY.
 CONT: THE PROTINUS CORP
 TEL: (561)214-0123
 E-MAIL: THE [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. MARCH 24/2016
 ACTION: DENIED
  
 NOTICE, ONLY ONE SET OF ARCHITECTURAL PLANS IN PACKAGE
 DATED 10/22/15. NO NARRATIVE OF CORRECTIONS!!!
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
 1) COMPLIED. INCREASED OCCUPANT LOAD.
  
 2) COMPLIED. WORK AREA METHOD LEVEL II.
  
 3) 3RD REQUEST. SHEET A-2 SHOWS THE BACK DOORS SWINGING
 OUT. PLEASE PROVIDE A SURVEY THAT SHOWS THE PROPERTY
 LINE.
 DOORS CANNOT SWING OUT OVER THE PROPERTY LINE. 2014
 FBC-B 3202.2.
  
 4) 3RD REQUEST. NEW COVERSHEET AND A1-A4 DRAWINGS. THE
 CONTRACTOR FAILED TO COLATE THE OLD PLANS WITH THE NEW
 PLANS SHEET A5-A8. SHEET A5 DOES SHOW A RECEPTION DESK,
 NO HEIGHT HAS BEEN ASSIGNED TO THE DIAGRAM, PLEASE
 PROVIDE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 904.4, 904.4.1 OR 904.4.2.
  
 5) 3RD REQUEST. SHEET A5 NO ELEVATIONS HAVE BEEN
 PROVIDED FOR THE BREAK ROOM SINK, PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE 606.2
 THROUGH 606.5.
  
 6) 3RD REQUEST, SHEET A5 NO ELEVATIONS HAVE BEEN
 PROVIDED FOR THE JUICE BAR. SHEET A2 SHOWS DETAILS ON
 A5 DETAILS K-M. PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 904.4, 904.4.1 OR 904.4.2. NOTE
 IF THERE WILL BE TABLES THEN COMPLIANCE WITH 902.3 WILL
 ALSO NEED TO COMPLIED WITH.
  
 7) 3RD REQUEST. SHEET A-7 THE FINISH SCHEDULE THE
 RESTROOMS WILL NEED TO SHOW COMPLIANCE WITH THE 2014
 FBC-B 1210.2.2.
  
 8) PROVISO: TO BE REVIEWED UNDER A SEPARATE PERMIT.
 PLEASE NOTE THERE WERE MECHANICAL PLANS PROVIDE, UNDER
 THE MECHANICAL REVIEW EXHAUST AIR AND MAKE UP AIR WILL
 NEED TO BE SUPPLIED TO THE MANICURE & PEDICURE
 STATIONS. NORMALLY THESE FANS ARE MOUNTED ON THE ROOF
 AND WILL NEED TO COMPLY WITH;
 8A) PROVISO: M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 8B) PROVISO:B-1609.6.4.4.1 COMPONENTS AND CLADDING.
 WIND PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT
 ARE TO BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 8C) PROVISO: 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31 ( C ) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 EXHAUST & INTAKE FANS
  
 8D) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) 3RD REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-24 Cont ID  
Sent By jwitmer Date 2016-02-24 Time 15:24 Rev Time 0.00
Received By jwitmer Date 2016-02-24 Time 07:30 Sent To  
Notes
2016-02-24 15:24:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15101064
 ADD: 112 N. DIXIE HWY.
 CONT: THE PROTINUS CORP
 TEL: (561)214-0123
 E-MAIL: THE [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 24/2016
 ACTION: DENIED
  
 1) COMPLIED. INCREASED OCCUPANT LOAD.
  
 2) COMPLIED. WORK AREA METHOD LEVEL II.
  
 3) 2ND REQUEST. SHEET A-2 SHOWS THE BACK DOORS SWINGING
 OUT. PLEASE PROVIDE A SURVEY THAT SHOWS THE PROPERTY
 LINE.
 DOORS CANNOT SWING OUT OVER THE PROPERTY LINE. 2014
 FBC-B 3202.2.
  
 4) 2ND REQUEST. NEW COVERSHEET AND A1-A4 DRAWINGS. THE
 CONTRACTOR FAILED TO COLATE THE OLD PLANS WITH THE NEW
 PLANS SHEET A5-A8. SHEET A5 DOES SHOW A RECEPTION DESK,
 NO HEIGHT HAS BEEN ASSIGNED TO THE DIAGRAM, PLEASE
 PROVIDE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE
 904.4, 904.4.1 OR 904.4.2.
  
 5) 2ND REQUEST. SHEET A5 NO ELEVATIONS HAVE BEEN
 PROVIDED FOR THE BREAK ROOM SINK, PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE 606.2
 THROUGH 606.5.
  
 6) 2ND REQUEST, SHEET A5 NO ELEVATIONS HAVE BEEN
 PROVIDED FOR THE JUICE BAR. SHEET A2 SHOWS DETAILS ON
 A5 DETAILS K-M. PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 904.4, 904.4.1 OR 904.4.2. NOTE
 IF THERE WILL BE TABLES THEN COMPLIANCE WITH 902.3 WILL
 ALSO NEED TO COMPLIED WITH.
  
 7) 2ND REQUEST. SHEET A-7 THE FINISH SCHEDULE THE
 RESTROOMS WILL NEED TO SHOW COMPLIANCE WITH THE 2014
 FBC-B 1210.2.2.
  
 8) PROVISO: TO BE REVIEWED UNDER A SEPARATE PERMIT.
 PLEASE NOTE THERE WERE MECHANICAL PLANS PROVIDE, UNDER
 THE MECHANICAL REVIEW EXHAUST AIR AND MAKE UP AIR WILL
 NEED TO BE SUPPLIED TO THE MANICURE & PEDICURE
 STATIONS. NORMALLY THESE FANS ARE MOUNTED ON THE ROOF
 AND WILL NEED TO COMPLY WITH;
 8A) PROVISO: M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 8B) PROVISO:B-1609.6.4.4.1 COMPONENTS AND CLADDING.
 WIND PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT
 ARE TO BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 8C) PROVISO: 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31 ( C ) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 EXHAUST & INTAKE FANS
  
 8D) PROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By jwitmer Date 2015-11-09 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2015-11-09 Time 14:20 Sent To  
Notes
2015-11-09 15:22:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15101064
 ADD: 112 N. DIXIE HWY.
 CONT: THE PROTINUS CORP
 TEL: (561)214-0123
 E-MAIL: THE [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 09/2015
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THIS TENANT SPACE IS TO BE
 A BUSINESS OCCUPANCY. THE LEASABLE SQ. FOOTAGE IS 2685
 S. F. THE OCCUPANT LOAD IS NOT GIVEN AND APPEARS THAT
 IT WILL BE GREATER THAN 27 OCCUPANTS. THE DESIGNER OF
 RECORD CAN PROVIDE AN INCREASED OCCUPANT LOAD SEE 2014
 FBC-B 1004.2.
  
 2) THE COVERSHEET UNDER THE HEADING OF CODE COMPLIANCE
 THE DESIGNER OF RECORD HAS NOT PROVIDED TO WHICH METHOD
 OF DESIGN THE PLANS WERE DESIGN TO UNDER THE 2014
 EXISTING BUILDING CODE 301.1. APPLICATION OF A METHOD
 SHALL BE THE SOLE BASIS FOR ASSESSING THE COMPLIANCE OF
 WORK , SEE 301.1 THROUGH 301.1.3. THE DESIGNER IS TO
 PICK A COMPLIANCE METHOD OF HOW THE PLANS WERE DERIVED.
  
 3) SHEET A-2 SHOWS THE BACK DOORS SWINGING OUT. PLEASE
 PROVIDE A SURVEY THAT SHOWS THE PROPERTY LINE.
 DOORS CANNOT SWING OUT OVER THE PROPERTY LINE. 2014
 FBC-B 3202.2.
  
 4) SHEET A5 DOES SHOW A RECEPTION DESK, NO HEIGHT HAS
 BEEN ASSIGNED TO THE DIAGRAM, PLEASE PROVIDE COMPLIANCE
 WITH 2014 FBC-ACCESSIBILITY CODE 904.4, 904.4.1 OR
 904.4.2.
  
 5) SHEET A5 NO ELEVATIONS HAVE BEEN PROVIDED FOR THE
 BREAK ROOM SINK, PLEASE PROVIDE COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE 606.2 THROUGH 606.5.
  
 6)) SHEET A5 NO ELEVATIONS HAVE BEEN PROVIDED FOR THE
 JUICE BAR. SHEET A2 SHOWS DETAILS ON A5 DETAILS K-M.
 PLEASE PROVIDE COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE 904.4, 904.4.1 OR 904.4.2. NOTE
 IF THERE WILL BE TABLES THEN COMPLIANCE WITH 902.3 WILL
 ALSO NEED TO COMPLIED WITH.
  
 7) SHEET A-7 THE FINISH SCHEDULE THE RESTROOMS WILL
 NEED TO SHOW COMPLIANCE WITH THE 2014 FBC-B 1210.2.2.
  
 8) PLEASE NOTE THERE WERE MECHANICAL PLANS PROVIDE,
 UNDER THE MECHANICAL REVIEW EXHAUST AIR AND MAKE UP AIR
 WILL NEED TO BE SUPPLIED TO THE MANICURE & PEDICURE
 STATIONS. NORMALLY THESE FANS ARE MOUNTED ON THE ROOF
 AND WILL NEED TO COMPLY WITH;
 8A) M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
 8B) B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT ARE TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 8C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31 ( C ) WALL LOUVERS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 EXHAUST & INTAKE FANS
  
 8D) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-08-17 Cont ID  
Sent By mvaldes Date 2016-08-17 Time 11:11 Rev Time 0.00
Received By mvaldes Date 2016-08-17 Time 10:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-23 Cont ID  
Sent By mvaldes Date 2016-03-23 Time 18:50 Rev Time 0.00
Received By mvaldes Date 2016-03-23 Time 18:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-02 Cont ID  
Sent By mvaldes Date 2016-03-02 Time 19:11 Rev Time 0.00
Received By mvaldes Date 2016-03-02 Time 19:11 Sent To  
Notes
2016-03-02 19:15:17JOB PERMIT NUMBER: 15101064
 JOB ADDRESS: 112 N DIXIE HIGHWAY
 WEST PALM BEACH
 DATE: MARCH 2 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 - RISER DIAGRAM TO INCLUDE MAIN DISCONNECTING OF
 SERVICE & FEEDER CONDUCTORS, AIC RATING OF ELECTRICAL
 EQUIPMENT AND OCPD, GROUNDING DETAIL TO INCLUDE
 GROUNDING ELECTRODE CONDUCTOR SIZE , FURTHER MORE
 INTERSYSTEM BONDING REQUIRED. NEC 230.70 , 250.66 & 94
 , 215.5 , 110.9 & 10
 - ARC FLASH HAZARD WARNING LABEL REQUIRED AS WELL AS
 AVAILABLE FAULT CURRENT MARKING. NEC 110.16, 110.24
 - PROVIDE DISCONNECTS ON FLOOR PLAN FOR W/H & A/C
 EQUIPMENT WITHIN SIGHT. WBA 107. A SERVICE RECEPTACLE
 IS REQUIRED BY MECHANICAL UNIT FOR MAINTENANCE PURPOSES
 NEC 210.63
 - GFCI PROTECTION WITHIN 6 FT OF SINKS AND ALL KITCHEN
 COUNTERTOPS IN OTHER THAN DWELLING UNITS NEC 210.8 B.
 IN ADDITION MAKE SURE DRINKING FOUNTAIN IS ALSO GFCI
 PROTECTED NEC 422.52
 - PROVIDE SHOW WINDOW OUTLETS PER NEC 210.62 AS WELL
 AS DEDICATED SIGN CIRCUIT PER NEC 600.5
 - ALL ELECTRICAL APPARATUS SHALL BE PROPERLY MARKED AS
 TO INDICATE WERE IN THE BUILDING IS THE SOURCE OF
 SUPPLY AT ALL LOCATIONS IN THE SYSTEM. NEC 408.4 B
 - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED
 BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE
 LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON
 OWN CIRCUIT.
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 - COMPLY WITH FBC ? E C 405 FOR OCCUPANCY SENSORS IN
 BATHROOMS, DAYLIGHT ZONE CONTROLS BY FRONT WINDOWS ,
 DIMMER CONTROLS OR TANDEM WIRING LIGHTING REDUCTION TO
 50 %, TO ADD A FIXTURE SCHEDULE WITH MOUNTING DETAIL
 SHALL BE PROVIDED.
  
  
  
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2015-11-25 Time   Rev Time 0.00
Received By mvaldes Date 2015-11-25 Time 10:14 Sent To Z
Notes
2015-11-25 10:53:361ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 PLEASE PROVIDE ON PANEL SCHEDULE AND FLOOR PLAN
 EXIT/EMERGENCY LIGHTS AHEAD OF LIGHTING CIRCUITS PER
 ARTICLE 700 NEC 2011
 PLEASE PROVIDE AUTOMATIC LIGHTING SHUTOFF PER FBC
 ENERGY CODE SECTION C405.
 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLEPHASE,
 15- AND 20-AMPERE RECEPTACLES INSTALLED IN THE
 LOCATIONS
 SPECIFIED IN 210.8(B)(1) THROUGH (8) SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
 (1) BATHROOMS
 (2) KITCHENS
 (3) ROOFTOPS
 (4) OUTDOORS
 (B) LOAD EVENLY PROPORTIONED AMONG BRANCH CIRCUITS.
 WHERE THE LOAD IS CALCULATED ON THE BASIS OF
 VOLT-AMPERES
 PER SQUARE METER OR PER SQUARE FOOT, THE WIRING SYSTEM
 UP TO
 AND INCLUDING THE BRANCH-CIRCUIT PANELBOARD(S) SHALL BE
 PROVIDED
 TO SERVE NOT LESS THAN THE CALCULATED LOAD. THIS LOAD
 SHALL BE EVENLY PROPORTIONED AMONG MULTIOUTLET BRANCH
 CIRCUITS
 WITHIN THE PANELBOARD(S). BRANCH-CIRCUIT OVERCURRENT
 DEVICES AND CIRCUITS SHALL BE REQUIRED TO BE INSTALLED
 ONLY TO
 SERVE THE CONNECTED LOAD.
 ARTICLE 210?BRANCH CIRCUITS 210.11
 2011
 210.62 SHOW WINDOWS. AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A
 SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY
 AT ITS MAXIMUM WIDTH.
 .
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-23 Cont ID  
Sent By pleduc Date 2016-08-23 Time   Rev Time 0.00
Received By pleduc Date 2016-08-22 Time 14:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-18 Cont ID  
Sent By pleduc Date 2016-02-18 Time   Rev Time 0.00
Received By pleduc Date 2016-02-18 Time 10:09 Sent To  
Notes
2016-02-18 10:22:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. MOVE REAR EXIT SIGN INTO THE HALLWAY SO IT CAN BE
 SEEN FROM WITHIN THE SALON.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By wjolin Date 2015-11-04 Time 11:20 Rev Time 0.00
Received By wjolin Date 2015-11-04 Time 10:15 Sent To  
Notes
2015-11-04 11:20:21112 NORTH DIXIE HIGHWAY
 PERMIT #15101064
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 5TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 WHERE ARE ALL THE BUSINESS SUPPLIES TO BE LOCATED? PER
 SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE OF
 HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY
 (BUSINESS) OF THE BUILDING, SHALL BE SEPARATED FROM
 NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR
 BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS
 SHALL BE SELF CLOSING, POSITIVE LATCHING, AND
 FIRE-RATED FOR AT LEAST 45-MINUTES.
  
 PROVIDE AN OCCUPANT LOAD BREAKDOWN FOR EACH ROOM.
  
 FOR OCCUPANT LOADS OF 50 OR MORE PERSONS, DOORS SHALL
 SWING IN THE DIRECTION OF EGRESS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 THE ELECTRICAL PLAN DOES NOT INCLUDE THE EMERGENCY
 LIGHTING SHOWN ON THE LIFE SAFETY PLAN.
  
 NO MECHANICAL VENTILATION PLAN PROVIDED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-11-28 Cont ID  
Sent By ccole Date 2016-11-28 Time 09:40 Rev Time 0.00
Received By ccole Date 2016-11-22 Time 08:17 Sent To  
Notes
2016-11-23 08:17:17RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-11-18 Cont ID  
Sent By ccole Date 2016-11-18 Time 12:18 Rev Time 0.00
Received By ccole Date 2016-11-14 Time 11:43 Sent To  
Notes
2016-11-16 11:44:11RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-09-16 Cont ID  
Sent By cpuell Date 2016-09-16 Time 15:04 Rev Time 0.00
Received By cpuell Date 2016-08-16 Time 16:18 Sent To  
Notes
2016-09-16 14:56:19TO LAURA MERCHANT
2016-08-16 16:19:02B34

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 12:49 Rev Time 0.00
Received By gjohnson Date 2016-03-22 Time 13:22 Sent To  
Notes
2016-03-22 13:22:46B08

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-17 Cont ID  
Sent By lmarchan Date 2016-03-17 Time 09:26 Rev Time 0.00
Received By lmarchan Date 2016-02-12 Time 09:11 Sent To  
Notes
2016-03-16 16:28:58TO CAROLINE FOR PROCESSING
2016-02-16 09:12:10B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-04 Cont ID  
Sent By aaponte Date 2015-12-04 Time 14:01 Rev Time 0.00
Received By aaponte Date 2015-10-29 Time 15:33 Sent To  
Notes
2015-12-04 14:03:22PERMIT FAILED- JOHN GAFFNEY CONTACTED BY PHONE ON
 12-4-15.
2015-10-30 15:35:02B13

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2016-11-28 Cont ID  
Sent By ccole Date 2016-11-28 Time 09:39 Rev Time 0.00
Received By ccole Date 2016-11-28 Time 09:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-11-18 Cont ID  
Sent By ccole Date 2016-11-18 Time 12:19 Rev Time 0.00
Received By ccole Date 2016-11-18 Time 12:19 Sent To  
Notes
2016-11-18 12:26:174TH REVIEW FBC-2014 MECHANICAL
 PERMIT #15101064
 11/18/16
  
 1) THE NEW 5-TON RTU REQUIRES INSTALLATION OF A DUCT
 SMOKE DETECTOR IN THE RETURN AIR SYSTEM IN COMPLIANCE
 WITH SECTION 606.2.1. PLEASE REVISE THE PLAN TO SHOW
 THE LOCATION OF THE DEVICE AND TEST STATION, AND
 PROVIDE NOTES TO INDICATE THE SEQUENCE OF OPERATION.
  
 2) ALL REVISED PLAN SHEETS MUST BE PERMANENTLY ATTACHED
 INTO THE PLAN SETS AND ALL SHEETS BEING REPLACED MUST
 BE REMOVED FROM THE SETS, VOIDED, AND RETAINED IN THE
 PERMIT PACKAGE FOR REFERENCE ONLY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-08-24 Cont ID  
Sent By ccole Date 2016-08-24 Time 08:50 Rev Time 0.00
Received By ccole Date 2016-08-24 Time 08:50 Sent To  
Notes
2016-08-24 09:02:594TH REVIEW FBC-2014 MECHANICAL
 PERMIT #15101064
 8/24/16
  
 1) AS PREVIOUSLY REQUESTED, PROVIDE A SEQUENCE OF
 OPERATION FOR THE SALON EXHAUST FANS. CLARIFY IF THE
 FANS WILL BE ON SWITCHES, OR LINKED TO THE LIGHTS OR AC
 SYSTEMS.
  
 2) PROVIDE MAKE UP AIR AND A SEQUENCE OF OPERATION FOR
 EF-1 IN THE STORAGE ROOM. CLARIFY THE PURPOSE OF THE
 FAN AND PROVIDE A LIST OF MATERIALS AND QUANTITIES OF
 MATERIALS TO BE STORED IN THE ROOM. PROVIDE MSDS SHEETS
 FOR ANY HAZARDOUS TYPE MATERIALS, AND PROVIDE AN
 EXHAUST VENTILATION CALCULATION- REFER TO SECTION 414
 FBC-14 BUILDING FOR APPLICABLE REQUIREMENTS.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR ANCHORAGE OF THE
 EXHAUST FANS AND CURBS TO THE ROOF STRUCTURE- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-28 Cont ID  
Sent By ccole Date 2016-03-28 Time 08:33 Rev Time 0.00
Received By ccole Date 2016-03-28 Time 08:33 Sent To  
Notes
2016-03-28 08:49:283RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #151201064
 3/28/16
  
 1) PROVIDE DRAWINGS AND DETAILS FOR THE NEW EXHAUST
 SYSTEMS INDICATING THE LOCATIONS OF THE EXHAUST INLETS,
 GRILL SIZES, GAGE OF METAL EXHAUST DUCT, AND FAN
 SCHEDULES. PLEASE NOTE THAT THE ARCHITECTURAL PLANS
 NEED TO BE REVISDED TO SHOW THE LOCATIONS OF, AND
 CONSTRUCTION DETAILS FOR THE NEW KNEE WALLS AT THE NAIL
 STATIONS.
 2) PROVIDE AN AIR BALANCE CALCULATION, AND A SEQUENCE
 OF OPERATION FOR THE EXHAUST SYSTEM.
 3) PROVIDE A MECHANIOCAL ROOF PLAN INDICATING THE
 LOCATIONS OF ALL ROOF TOP EQUIPMENT: SHOW CLEARANCE
 DISTANCE MEASUREMENTS FOR AIR INTAKES TO EXHAUST AND
 VENT OUTLETS, EQUIPMENT CLEARANC DISTANCES TO RROF
 EDGES, AND THE NEW RTU CONDENSATE PIPING RUN.
 4) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE RTU, AND PROVIDE DETAILS FOR
 INSTALLATION OF THE NEW EXHAUST FANS. PLEASE SUBMIT
 MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR THE
 FANS AND CURBS WITH APPROVAL SIGNATURES BY THE ENGINEER
 OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By ccole Date 2016-02-24 Time 18:00 Rev Time 0.00
Received By ccole Date 2016-02-24 Time 18:00 Sent To  
Notes
2016-02-24 18:03:33MECHANICAL NOTE
 PERMIT #15101064
 2/24/15
  
 1) THE PLANS WERE RE-SUBMITTED A SECOND TIME WITHOUT
 MECHANICAL PLANS. PER HAROLD MOSER THE PLANS WILL BE
 SUBMITTED UNDER A SEPARATE PERMIT. I AM PLACING A HOLD
 ON HE CO FOR THIS OCCUPANCY PENDING APPROVAL OF
 MECHANICAL PLANS, AND COMPLETE INSPECTIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By ccole Date 2015-11-06 Time 12:55 Rev Time 0.00
Received By ccole Date 2015-11-06 Time 12:55 Sent To  
Notes
2015-11-06 13:05:401ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101064
 11/6/15
  
 1) NO MECHANICAL PLANS WERE INCLUDED WITH THE SUBMITTED
 PLAN SETS FOR THE PROJECT. IN AN EFFORT TO EXPEDITE THE
 PERMITTING PROCESS, I CALLED THE ENGINEER OF RECORD-
 MR. KARL LEDERER WHO ACKNOWLEDGED THAT THERE WERE NO
 PLANS AT THE PRESENT TIME TO BE SUBMITTED. I ADVISED
 HIM TO REVIEW THE APPLICABLE CODE SECTIONS FOR NAIL
 SALONS IN THE FBC-2014 MECHANICAL CODE AND SUBMIT PLANS
 ACCORDINGLY. PLEASE REFER TO TABLE 403.3
 FBC-MECHANICAL- FOR THE MINIMUM VENTILATION RATES
 INCLUDING FOOTNOTES B & H AND SECTION 403.2.1 ITEM #3-
 ALL OF WHICH ARE APPLICABLE TO NAIL SALONS. PLEASE
 PROVIDE COMPLETE HVAC PLANS, EQUIPMENT SCHEDULES,
 INSTALLATION DETAILS, AND CALCULATIONS FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2016-09-10 Cont ID  
Sent By tklarge Date 2016-09-10 Time 08:20 Rev Time 0.00
Received By tklarge Date 2016-09-10 Time 07:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-04-11 Cont ID  
Sent By gjohnson Date 2016-04-11 Time 12:48 Rev Time 0.00
Received By gjohnson Date 2016-04-11 Time 12:48 Sent To  
Notes
2016-04-11 12:48:25PLUMBING COMMENTS;
  
 1) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO FBC SEC. 107.2.1. 2ND REQUEST
 2) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014
 FBC-ACCESSIBILITY SEC. 212, 212.3. 2ND REQUEST
 3) SHT. A-2 INDICATES ELEVATION 11 K11 ON SHT. A-5 FOR
 THE BREAKROOM ELEVATIONS. THERE IS NO ELEVATION 11 K11
 ON SHT. A-5. CLARIFY. 2ND REQUEST
 4) SHT. A-7 - FINISH SCHEDULE - THE WALLS IN THE MEN?S
 & WOMEN?S TOILET ROOMS SHALL COMPLY WITH 2014 FBC
 SEC.1210.2.2. 2ND REQUEST
 5) WATER FOUNTAIN IS REQUIRED PER FBC PL SEC. 403.1
 TABLE 403.1 WATER FOUNTAINS SHALL COMPLY WITH FBC ACC.
 SEC. 307 AND 602.
 6) SUBMIT AN OCCUPANT LOAD FOR THIS SPACE IN ACCORDANCE
 WITH 2014 FBC TABLE 1004.1.2. 2ND REQUEST
 7) INDICATE ON THE PLAN WHAT TYPE OF
 PRODUCTS/PREPARATION WILL BE DONE AT THE JUICE BAR .WPB
 AMEND . TO FBC SEC. 107 .2.1. 2ND REQUEST
 8) A SERVICE SINK IS REQUIRED PER FBC PL SEC. 403.1
 TABLE 403.1
 9) THE VENTING FOR PEDICURE CHAIRS SHALL COMPLY WITH
 FBC PL SEC. 914.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 IT APPEARS THAT ONLY THE NEW MEP PAGES WERE RESUBMITED
 PLEASE CLARIFY
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 08:26 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 07:50 Sent To  
Notes
2016-02-20 08:08:381) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO FBC SEC. 107.2.1.2ND REQUEST.
 2) SUBMIT A WATER RISER DIAGRAM FOR REVIEW.SHOW ALL
 PIPE SIZES ON THE SANITARY AND WATER RISER DIAGRAMS.WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 3) NOW THAT AN OCCUPANT LOAD HAS BEEN GIVEN, THE
 FOLLOWING PLUMBING FIXTURES ARE REQUIRED PER 2014 FPC
 TABLE 403.1:
 A) A DRINKING FOUNTAIN IS REQUIRED. 2014 FPC TABLE
 403.1. A MINIMUM OF 2 DRINKING FOUNTAINS ARE REQUIRED
 PER 2014 FAC SEC.211.2 & FPC TABLE 403.1 FOOTNOTE (E).
 B) A SERVICE SINK IS REQUIRED PER 2014 FPC TABLE 403.1.
 4) PROVIDE A COST BREAKDOWN SHOWING THE PROPORTION OF
 EXPENDITURES USED TO COMPLY WITH THE FBC-ACCESSIBILITY
 FOR THE AMOUNT DEDICATED TO PROVIDING HANDICAP
 ACCESSIBILITY. SEE FAC SECS.202.4.1 & 202.4.2.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By tklarge Date 2015-11-05 Time 11:21 Rev Time 0.00
Received By tklarge Date 2015-11-05 Time 05:27 Sent To  
Notes
2015-11-05 10:44:441) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS &
 INSTALLATION MANUAL FOR THE PEDICURE CHAIRS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) THE BREAK ROOM SINK SHALL CCOMPLY WITH THE 2014
 FBC-ACCESSIBILITY SEC. 212, 212.3.
 3) SHT. A-2 INDICATES ELEVATION "K" ON SHT. A-5 FOR THE
 BREAKROOM ELEVATIONS. THERE IS NO ELEVATION "K" ON SHT.
 A-5. CLARIFY.
 4) SHT. A-7 - FINISH SCHEDULE - THE WALLS IN THE MEN'S
 & WOMEN'S TOILET ROOMS SHALL COMPLY WITH 2014 FBC
 SEC.1210.2.2.
 5) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR
 REVIEW.SHOW ALL PIPE SIZES ON THE RISER DIAGRAMS.WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 6) SUBMIT AN OCCUPANT LOAD FOR THIS SPACE IN ACCORDANCE
 WITH 2014 FBC TABLE 1004.1.2.
 7) INDICATE ON THE PLAN WHAT TYPE OF
 PRODUCTS/PREPARATION WILL BE DONE AT THE JUICE BAR.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-09-16 Cont ID  
Sent By aaponte Date 2016-09-16 Time 14:51 Rev Time 0.00
Received By aaponte Date 2016-09-16 Time 14:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By aaponte Date 2016-03-16 Time 16:28 Rev Time 0.00
Received By aaponte Date 2016-03-16 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-04 Cont ID  
Sent By aaponte Date 2015-12-04 Time 13:59 Rev Time 0.00
Received By aaponte Date 2015-12-04 Time 13:59 Sent To  
Notes
***NONE***