Plan Review Details - Permit 15101055
Plan Review Stops For Permit 15101055
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2016-01-05 Cont ID  
Sent By albarran Date 2016-01-05 Time 15:51 Rev Time 0.00
Received By albarran Date 2016-01-05 Time 15:51 Sent To I
Notes
2016-01-05 16:27:57ELECTRICAL STOPS WERE INADVERTENTLY ADDED TO THIS
 PERMIT. SHOULD THERE BE A CONNECTION OF THIS SYSTEM TO
 AN EXISTING FIRE ALARM SYSTEM, A SEPARATE PERMIT FOR
 THAT CONNECTION WILL BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-30 Cont ID  
Sent By pleduc Date 2015-12-31 Time 11:25 Rev Time 0.00
Received By albarran Date 2015-12-30 Time 18:07 Sent To I
Notes
2015-12-30 19:22:49THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. YOU SHALL DEFINE YOUR SCOPE OF WORK AND INCLUDE IT
 ON THE PLANS. I CAN?T DETERMINE IF THIS IS PREFAB UNIT
 WITH A SINGLE POINT OF CONNECTION TO A FIELD PROVIDED
 DISCONNECT, OR IF THIS IS A SITE BUILT UNIT IN WHICH
 CASE FURTHER DETAILS SHALL BE PROVIDED.
 2. ACCORDING TO THE MANUFACTURERS SPEC SHEET, BOTH THE
 EXHAUST AND SUPPLY FANS ARE 3 PHASE AND THE SERVICE TO
 THE PREMISES ARE INDICATED ON THE RISER DIAGRAM IS
 SINGLE PHASE.
 3. PROVIDE LITERATURE OR MANUFACTURERS SPEC SHEETS FOR
 THE MOTORS, OR PROVIDE SOMETHING INDICATING WHETHER THE
 VALUES EXPRESSED ON PAGE 3 ARE MOTOR FLC, OR OCP.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH.: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-11-30 Cont ID  
Sent By mvaldes Date 2015-11-30 Time 10:09 Rev Time 0.00
Received By mvaldes Date 2015-11-30 Time 10:09 Sent To  
Notes
2015-11-30 10:27:091ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
 . CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-31 Cont ID  
Sent By albarran Date 2015-12-31 Time   Rev Time 0.00
Received By pleduc Date 2015-12-28 Time 14:11 Sent To  
Notes
2015-12-28 14:13:13INSUFFICIENT DETAIL ON RESUBMITTAL THAT WAS ATTACHED TO
 15101045
  
 CONCERNS ADDRESSED AND PASSED 12/31/15. PML

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-04 Cont ID  
Sent By pleduc Date 2015-11-04 Time   Rev Time 0.00
Received By pleduc Date 2015-11-04 Time 10:15 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-05 Cont ID  
Sent By albarran Date 2016-01-05 Time 16:29 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2016-01-05 16:31:301/5/16 THOUGH THIS PERMIT IS READY TO BE ISSUED, IT IS
 RUNNING WITH 15101045 FOR THE SPRAY BOOTH AND THEY WILL
 GO OUT TOGETHER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-30 Cont ID  
Sent By albarran Date 2015-12-30 Time 19:25 Rev Time 0.00
Received By albarran Date 2015-10-29 Time 15:16 Sent To  
Notes
2015-12-30 19:26:4512/30/15 FAILED THE LAST OF THE TRADE REVIEWS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN
 "F". MA
2015-11-13 12:04:44B10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-31 Cont ID  
Sent By ccole Date 2015-12-31 Time 10:35 Rev Time 0.00
Received By ccole Date 2015-12-31 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 10:41 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 10:41 Sent To  
Notes
2015-12-28 10:53:012ND REVIEW 2014 MECHANICAL
 PERMIT #15101055
 12/28/15
  
 1) THE DIMENSIONS OF THE SPRAY BOOTH SHOWN ON THE FIRE
 SUPPRESSION PLAN DOES NOT MATCH THE DIMENSIONS SHOWN ON
 THE SPRAY BOOTH PLANS. PLEASE REVISE AND INCLUDE THE
 MAKE AND MODEL NUMBER OF THE BOOTH ON THE SUPPRESSION
 PLAN.
 2) THE FIRE SUPPRESSION PLAN HAS ILLEGIBLE PRINT EITHER
 TOO SMALL OR FAINT TO READ AND SCAN FOR PUBLIC RECORD.
 PROVIDE ENLARGED LEGIBLE PLANS IN ACCORDANCE WITH
 SECTION 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE
 COMPATIBLE WITH THE ARCHIVE REQUIREMENTS OF FLORIDA
 STATUTES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 11:06 Rev Time 0.00
Received By ccole Date 2015-11-13 Time 10:08 Sent To  
Notes
2015-11-13 11:38:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101055
 11/13/15
  
 1) THERE IS A DISCREPANCY IN THE PLANS AND
 SPECIFICATIONS FOR THE CHINOOK II PAINT SPRAY BOOTH:
 TWO DIFFERENT MODEL NUMBERS ARE LISTED ON SHEET A-
 (#42106X IN THE DRAWING, AND #99830X IN THE NOTES). SEE
 PAGE 3 OF THE SUBMITTED BOOTH SPECS- MODEL #42106X AS
 SPECIFIED ON THE PLANS DOES NOT COME WITH A HEATER,
 HOWEVER AN 840,000 BTUH GAS FIRED BURNER IS LISTED IN
 THE NOTES ON SHEET A AND ON SHEET M-1. PLEASE CLARIFY
 WHICH BOOTH IS TO BE INSTALLED AND IF A GAS-FIRED
 HEATER IS INCLUDED. IN ACCORDANCE WITH THE BOOTH SPECS,
 EXPLOSION VENTING IS REQUIRED IF HEATING IS PROVIDED
 (PAGES 3, 8, & 16), AND IN NOTE #14 ON SHEET
 UNOBSTRUCTED EXPLOSION RELIEF IS REQUIRED. PLEASE
 PROVIDE DETAILS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  