Plan Review Details - Permit 15101053
Plan Review Stops For Permit 15101053
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-01 Cont ID  
Sent By rmcdouga Date 2015-12-01 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2015-12-01 Time 14:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By mcdougal Date 2015-11-06 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2015-11-06 Time 07:13 Sent To  
Notes
2015-11-06 08:50:43PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PLANS SHOW WOOD SHEATHING AND STUCCO EXTENDING TO
 GRADE. THIS IS NOT ALLOWED BY THE BUILDING CODE.
 FBC-R317.1 REQUIRES PROTECTION OF WOOD AND WOOD BASED
 PRODUCTS FROM DECAY SHALL BE PROVIDED IN THE FOLLOWING
 LOCATIONS BY THE USE OF NATURALLY DURABLE WOOD OR WOOD
 THAT IS PRESERVATIVE-TREATED IN ACCORDANCE WITH AWPA U1
 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND END USE.
 PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF AWPA U1.
 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE
 EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN
 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES
 (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH
 SLABS, PATIO SLABS, AND SIMILAR HORIZONTAL SURFACES
 EXPOSED TO THE WEATHER.
  
 2) SHOW COMPLIANCE WITH SECTION R704 INSPECTION FOR
 TERMITES. IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM).
 EXCEPTIONS:
 3. A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO AND
 GARAGE SLABS AND ENTRY AREAS.
  
 3) SHOW COMPLIANCE WITH ASTM C 926 AND ASTM C 1063 FOR
 THE STUCCO WEEP SCREED THAT IS REQUIRED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS.
  
 4) R318.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES, IRRIGATION/SPRINKLER SYSTEM RISERS
 FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 5) SECTIONS 1A AND 2 ON S-43 DO NOT SPECIFY WALL TO
 WALL OR TRUSS TO WALL CONNECTORS FOR UPLIFT. THE
 SIMPSON HGA10 THAT IS SHOWN IS FOR LATERAL WIND
 RESISTANCE. FBC-R301.1 & FBC-R802.1.6.5
  
 6) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE WOOD FRAME PARAPET WALL TO PROVIDE A CONTINUOUS
 LOAD PATH. FBC-R301.1
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-11-04 Cont ID  
Sent By fmittner Date 2015-11-04 Time 09:56 Rev Time 0.00
Received By fmittner Date 2015-11-04 Time 09:56 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-01 Cont ID  
Sent By rmcdouga Date 2015-12-01 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2015-11-19 Time 12:35 Sent To  
Notes
2015-11-20 12:35:31RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-06 Cont ID  
Sent By rmcdouga Date 2015-11-06 Time 07:52 Rev Time 0.00
Received By rmcdouga Date 2015-10-29 Time 13:31 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-11-04 Cont ID  
Sent By rmcdouga Date 2015-11-06 Time 07:52 Rev Time 0.00
Received By fmittner Date 2015-11-04 Time 09:56 Sent To  
Notes
***NONE***