Plan Review Details - Permit 15101045
Plan Review Stops For Permit 15101045
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-12-02 Cont ID  
Sent By shill Date 2015-12-02 Time 18:04 Rev Time 0.00
Received By shill Date 2015-12-02 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-01-15 Cont ID  
Sent By albarran Date 2016-01-15 Time 12:06 Rev Time 0.00
Received By albarran Date 2016-01-15 Time 8:25 Sent To I
Notes
2016-01-15 12:07:58RECEIVED VIA EMAIL SPEC SHEET FROM THE MANUFACTURER
 INDICATING THAT THE UNIT IS ASSEMBLED BY THE SHIPPER
 AND THE SCOPE OF THE EC IS ONLY TO PROVIDE AN
 ELECTRICAL CIRCUIT FOR THE MOTOR AND AN ELECTRICAL
 CIRCUIT FOR THE LIGHTING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-05 Cont ID  
Sent By albarran Date 2016-01-05 Time 18:31 Rev Time 0.00
Received By albarran Date 2016-01-05 Time 17:30 Sent To I
Notes
2016-01-05 18:31:36GREGG, PLEASE NOTE THAT I CORRECTED A COUPLE OF
 CLUSTERS WITH THE TWO PERMITS. PERMIT 15101055 IS
 STRICTLY FOR THE FIRE SUPPRESSION AND THEREFORE SHOULD
 NOT HAVE ANY ELECTRICAL PLAN REVIEW STOPS ATTACHED
 THERETO. THE ONLY ELECTRICAL REVIEW THAT SHOULD BE
 ASSOCIATED WITH THIS PERMIT WOULD BE IF THERE IS AN
 EXISTING FIRE ALARM SYSTEM TO WHICH THIS FIRE
 SUPPRESSION SYSTEM WITH TIE IN TO. THEN AND ONLY THEN A
 SEPARATE FIRE ALARM PERMIT WILL BE REQUIRED. I HAVE
 ENTERED A NOTE IN THE FRONT SCREEN AS WELL AS ON THE
 PLANS OF THE 15101055 PERMIT INDICATING THAT. THAT
 PERMIT IS READY FOR ISSUANCE PENDING PAYMENT OF THE
 BALANCE DUE OF $146.00. KEEP IN MIND THAT IT IS RUNNING
 TOGETHER WITH 15101045 AND THEY SHOULD BE PICKED UP
 TOGETHER. ALL OF THE ELECTRICAL REVIEW COMMENTS, BOTH
 OF MARIO VALDES AND MYSELF HAVE BEEN TRANSFERRED TO THE
 15101045 PERMIT.
 WITH REGARDS TO THE 15101045, PLEASE READ BELOW.
 1. IN MY REVIEW COMMENTS OF 15101055 I ASKED THAT THE
 SCOPE OF WORK BE DEFINED ON THE PLANS AND PERMIT. THE
 PERMIT CALLS FOR THE INSTALLATION OF A PAINT BOOTH. YOU
 SHALL INDICATE: A) IF THIS IS A LISTED UNIT, ALL THE
 ELECTRICAL CONTRACTOR WILL BE DOING IS TO PROVIDE
 ELECTRICAL POWER FROM THE ELECTRICAL PANEL TO A
 DISCONNECT AND NOTHING ELSE. IN SUCH A CASE THE DATA
 PROVIDED FOR THE EQUIPMENT SHALL INDICATE THAT B) IF
 THE ELECTRICAL CONTRACTOR WILL BE ASSISTING IN THE
 ASSEMBLY OF THE UNIT, INDICATE SUCH. THIS WOULD ENTAIL
 INSPECTIONS OF THE WORK PERFORMED IN THE FIELD.
 FURTHERMORE, THE PLAN NOTES ON SHEET E1 OF THE
 SUBMITTED PLANS CALL FOR UPGRADING OR WORKING ON THE
 ELECTRICAL SERVICE; THIS IS NOT STATED ON ANY OF THE
 PERMITS (AN ELECTRICAL SUB PERMIT HAS NOT YET BEEN
 SECURED).
 2. ON TO MY SECOND COMMENT, WHICH WE HAVE DISCUSSED
 OVER AND OVER AND STILL I FAIL TO SEE ANYTHING
 INDICATING THAT A SINGLE PHASE MOTOR WILL DO THE TRICK.
 THE SINGLE SHEET WHICH YOU SENT ME DOES INCLUDE A
 SINGLE PHASE MOTOR. THE PROBLEM WITH THAT IS THAT I
 HAVE NO IDEA WHERE THAT CAME FROM AND IT IS AN OLD
 (2011) REVISION TO SOMETHING. THE CURRENT ONE WHICH
 ACCOMPANIES THE SUBMITTAL IS DATED DEC. 11, 2013. THE
 LATEST REVISION DOES NOT ADDRESS THE SINGLE PHASE MOTOR
 FOR A REASON. I WILL NEED SOMETHING FROM THE
 MANUFACTURER OR THE LISTING AGENT INDICATING THAT
 REPLACING THE MOTORS WILL NOT AFFECT THE LISTING.
 3. TO SETTLE THE MATTER WITH REGARDS TO THE THIRD
 COMMENT, THE ONE INQUIRING ON THE AMPS AS MENTIONED ON
 THE LITERATURE, I WILL NEED SOMETHING REFLECTING THE
 ACTUAL MOTORS WHICH WILL BE USED AND THE RESPECTIVE
 LOAD CALCS. THOUGHT I RECEIVED A LETTER FROM GARMART
 USA IT DOES NOT SPECIFY WHAT I AM ASKING FOR. THE SPEC
 SHEETS PROVIDE SEVERAL OPTIONS ALL OF WHICH HAVE
 DIFFERENT ELECTRICAL REQUIREMENTS. YOU SHALL INDICATE
 WHICH OF THOSE OPTIONS YOU WILL BE APPLYING AND PROVIDE
 THE PROPER LOAD CALCS FOR THAT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME; I WILL GLADLY HELP YO UNDERSTAND WHAT I
 NEED. BY THE WAY, I SPOKE W/CHRIS OF XTREME ELECTRICAL
 SERVICES AND HE WAS ABLE TO UNDERSTAND EVERYTHING I WAS
 SAYING.
  
 THANK YOU,
2016-01-05 17:31:29DUE TO THE CONFUSION BETWEEN THIS PERMIT AND PERMIT
 15101055 THIS PERMIT GOT INADVERTENTLY PASSED. THIS
 REVIEW WILL ENCOMPASS ALL REQUIRED CORRECTIONS FOR THIS
 PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-23 Cont ID  
Sent By ccole Date 2015-12-28 Time 10:06 Rev Time 0.00
Received By mvaldes Date 2015-12-23 Time 15:52 Sent To M
Notes
2016-01-06 09:18:30 
 1ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 GREGG, PLEASE NOTE THAT I CORRECTED A COUPLE OF
 CLUSTERS WITH THE TWO PERMITS. PERMIT 15101055 IS
 STRICTLY FOR THE FIRE SUPPRESSION AND THEREFORE SHOULD
 NOT HAVE ANY ELECTRICAL PLAN REVIEW STOPS ATTACHED
 THERETO. THE ONLY ELECTRICAL REVIEW THAT SHOULD BE
 ASSOCIATED WITH THIS PERMIT WOULD BE IF THERE IS AN
 EXISTING FIRE ALARM SYSTEM TO WHICH THIS FIRE
 SUPPRESSION SYSTEM WITH TIE IN TO. THEN AND ONLY THEN A
 SEPARATE FIRE ALARM PERMIT WILL BE REQUIRED. I HAVE
 ENTERED A NOTE IN THE FRONT SCREEN AS WELL AS ON THE
 PLANS OF THE 15101055 PERMIT INDICATING THAT. THAT
 PERMIT IS READY FOR ISSUANCE PENDING PAYMENT OF THE
 BALANCE DUE OF $146.00. KEEP IN MIND THAT IT IS RUNNING
 TOGETHER WITH 15101045 AND THEY SHOULD BE PICKED UP
 TOGETHER. ALL OF THE ELECTRICAL REVIEW COMMENTS, BOTH
 OF MARIO VALDES AND MYSELF HAVE BEEN TRANSFERRED TO THE
 15101045 PERMIT.
 WITH REGARDS TO THE 15101045, PLEASE READ BELOW.
 1. IN MY REVIEW COMMENTS OF 15101055 I ASKED THAT THE
 SCOPE OF WORK BE DEFINED ON THE PLANS AND PERMIT. THE
 PERMIT CALLS FOR THE INSTALLATION OF A PAINT BOOTH. YOU
 SHALL INDICATE: A) IF THIS IS A LISTED UNIT, ALL THE
 ELECTRICAL CONTRACTOR WILL BE DOING IS TO PROVIDE
 ELECTRICAL POWER FROM THE ELECTRICAL PANEL TO A
 DISCONNECT AND NOTHING ELSE. IN SUCH A CASE THE DATA
 PROVIDED FOR THE EQUIPMENT SHALL INDICATE THAT B) IF
 THE ELECTRICAL CONTRACTOR WILL BE ASSISTING IN THE
 ASSEMBLY OF THE UNIT, INDICATE SUCH. THIS WOULD ENTAIL
 INSPECTIONS OF THE WORK PERFORMED IN THE FIELD.
 FURTHERMORE, THE PLAN NOTES ON SHEET E1 OF THE
 SUBMITTED PLANS CALL FOR UPGRADING OR WORKING ON THE
 ELECTRICAL SERVICE; THIS IS NOT STATED ON ANY OF THE
 PERMITS (AN ELECTRICAL SUB PERMIT HAS NOT YET BEEN
 SECURED).
 2. ON TO MY SECOND COMMENT, WHICH WE HAVE DISCUSSED
 OVER AND OVER AND STILL I FAIL TO SEE ANYTHING
 INDICATING THAT A SINGLE PHASE MOTOR WILL DO THE TRICK.
 THE SINGLE SHEET WHICH YOU SENT ME DOES INCLUDE A
 SINGLE PHASE MOTOR. THE PROBLEM WITH THAT IS THAT I
 HAVE NO IDEA WHERE THAT CAME FROM AND IT IS AN OLD
 (2011) REVISION TO SOMETHING. THE CURRENT ONE WHICH
 ACCOMPANIES THE SUBMITTAL IS DATED DEC. 11, 2013. THE
 LATEST REVISION DOES NOT ADDRESS THE SINGLE PHASE MOTOR
 FOR A REASON. I WILL NEED SOMETHING FROM THE
 MANUFACTURER OR THE LISTING AGENT INDICATING THAT
 REPLACING THE MOTORS WILL NOT AFFECT THE LISTING.
 3. TO SETTLE THE MATTER WITH REGARDS TO THE THIRD
 COMMENT, THE ONE INQUIRING ON THE AMPS AS MENTIONED ON
 THE LITERATURE, I WILL NEED SOMETHING REFLECTING THE
 ACTUAL MOTORS WHICH WILL BE USED AND THE RESPECTIVE
 LOAD CALCS. THOUGHT I RECEIVED A LETTER FROM GARMART
 USA IT DOES NOT SPECIFY WHAT I AM ASKING FOR. THE SPEC
 SHEETS PROVIDE SEVERAL OPTIONS ALL OF WHICH HAVE
 DIFFERENT ELECTRICAL REQUIREMENTS. YOU SHALL INDICATE
 WHICH OF THOSE OPTIONS YOU WILL BE APPLYING AND PROVIDE
 THE PROPER LOAD CALCS FOR THAT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME; I WILL GLADLY HELP YO UNDERSTAND WHAT I
 NEED. BY THE WAY, I SPOKE W/CHRIS OF XTREME ELECTRICAL
 SERVICES AND HE WAS ABLE TO UNDERSTAND EVERYTHING I WAS
 SAYING.
  
 THANK YOU,

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By mvaldes Date 2015-11-30 Time 09:06 Rev Time 0.00
Received By mvaldes Date 2015-11-30 Time 09:06 Sent To  
Notes
2015-11-30 09:21:311ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 . CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES
  
 (B) ELECTRICAL EQUIPMENT INSTALLED ABOVE CLASS I
 LOCATIONS.
 (1) FIXED ELECTRICAL EQUIPMENT. ELECTRICAL EQUIPMENT IN
 A
 FIXED POSITION SHALL BE LOCATED ABOVE THE LEVEL OF ANY
 DEFINED
 CLASS I LOCATION OR SHALL BE IDENTIFIED FOR THE
 LOCATION.
 (A) ARCING EQUIPMENT. EQUIPMENT THAT IS LESS THAN 3.7 M
 (12 FT) ABOVE THE FLOOR LEVEL AND THAT MAY PRODUCE
 ARCS, SPARKS,
 OR PARTICLES OF HOT METAL, SUCH AS CUTOUTS, SWITCHES,
 CHARGING
 PANELS, GENERATORS, MOTORS, OR OTHER EQUIPMENT
 (EXCLUDING RECEPTACLES,
 LAMPS, AND LAMPHOLDERS) HAVING MAKE-AND-BREAK OR
 SLIDING CONTACTS, SHALL BE OF THE TOTALLY ENCLOSED TYPE
 OR CONSTRUCTED
 SO AS TO PREVENT THE ESCAPE OF SPARKS OR HOT METAL
 PARTICLES.
 (B) FIXED LIGHTING. LAMPS AND LAMPHOLDERS FOR FIXED
 LIGHTING THAT IS LOCATED OVER LANES THROUGH WHICH
 VEHICLES
 ARE COMMONLY DRIVEN OR THAT MAY OTHERWISE BE EXPOSED TO
 PHYSICAL DAMAGE SHALL BE LOCATED NOT LESS THAN 3.7 M
 (12 FT)
 ABOVE FLOOR LEVEL, UNLESS OF THE TOTALLY ENCLOSED TYPE
 OR
 CONSTRUCTED SO AS TO PREVENT ESCAPE OF SPARKS OR HOT
 METAL
 PARTICLES.
  
 SHOW ELECTRICAL EQUIPMENT ON SITE PLAN TO SEE IF
 LOCATIONS COMPLY WITH NEC HAZARDOUS REQUIREMENTS.
  
 NO GROUNDING DETAIL IN RISER DIAGRAM PER ARTICLE 250.66
 NEC
  
 PLEASE PROVIDE WIRE GUTTER SIZE MAKE SURE IT COMPLIES
 WITH NEC 366.22
  
 PLEASE PROVIDE AIC CACULATION FOR SERVICE FUSES
 DISCONNECT.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-28 Cont ID  
Sent By pleduc Date 2015-12-28 Time   Rev Time 0.00
Received By pleduc Date 2015-12-28 Time 14:01 Sent To PC
Notes
2015-12-28 14:03:02PASSED FOR BOOTH ONLY
  
 SUPPRESSION SYSTEM SHALL BE UNDER SEPARATE SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-15 Cont ID  
Sent By albarran Date 2016-01-15 Time 12:08 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2016-01-15 12:10:201/15/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT FILE TO SMALL READY BIN "F". MA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-05 Cont ID  
Sent By albarran Date 2016-01-05 Time 18:35 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2016-01-05 18:36:341/5/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. RUNNING TOGETHER WITH 15101055.
 SENT FILE TO SMALL DENIED BIN "F". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 10:06 Rev Time 0.00
Received By ccole Date 2015-12-23 Time 15:23 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-16 Cont ID  
Sent By lmarchan Date 2015-12-16 Time 14:36 Rev Time 0.00
Received By lmarchan Date 2015-10-29 Time 09:47 Sent To  
Notes
2015-11-30 09:49:02B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-28 Cont ID  
Sent By ccole Date 2015-12-28 Time 10:12 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 10:06 Sent To  
Notes
2015-12-28 10:23:18MECHANICAL PROVIS0S
 PERMIT #15101045
 12/28/15
  
 1) EXPLOSION VENTING FOR THE SPRAY BOOTH SHALL BE
 PROVIDED IN ACCORDANCE WITH MANUFACTURER'S
 SPECIFICATIONS- SEE PAGES 3, 8, & 16.
 2) SEPARATE PERMIT REQUIRED FOR GAS PIPING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 12:08 Rev Time 0.00
Received By ccole Date 2015-11-13 Time 12:08 Sent To  
Notes
2015-11-13 12:10:041ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101045
 11/13/15
  
 1) THERE IS A DISCREPANCY IN THE PLANS AND
 SPECIFICATIONS FOR THE CHINOOK II PAINT SPRAY BOOTH:
 TWO DIFFERENT MODEL NUMBERS ARE LISTED ON SHEET A-
 (#42106X IN THE DRAWING, AND #99830X IN THE NOTES). SEE
 PAGE 3 OF THE SUBMITTED BOOTH SPECS- MODEL #42106X AS
 SPECIFIED ON THE PLANS DOES NOT COME WITH A HEATER,
 HOWEVER AN 840,000 BTUH GAS FIRED BURNER IS LISTED IN
 THE NOTES ON SHEET A AND ON SHEET M-1. PLEASE CLARIFY
 WHICH BOOTH IS TO BE INSTALLED AND IF A GAS-FIRED
 HEATER IS INCLUDED. IN ACCORDANCE WITH THE BOOTH SPECS,
 EXPLOSION VENTING IS REQUIRED IF HEATING IS PROVIDED
 (PAGES 3, 8, & 16), AND IN NOTE #14 ON SHEET
 UNOBSTRUCTED EXPLOSION RELIEF IS REQUIRED. PLEASE
 PROVIDE DETAILS.
 2) PROVIDE DETAILS FOR THE COMPRESSED AIR SYSTEM:
 EQUIPMENT SCHEDULE FOR THE COMPRESSOR, LOCATION OF THE
 COMPRESSOR, TYPE AND DIAMETER OF COMPRESSED AIR PIPING,
 LAYOUT OF PIPING RUNS, AND PIPE HANGING AND SUPPORT
 DETAILS.
 3) PLEASE CLARIFY OR CORRECT: PAGE 18 OF THE SPECS
 INDICATES SINGLE WALL PANELS AT 16 MSG, HOWEVER
 STRUCTURAL PANELS ARE LISTED AT 16 GAUGE STEEL ON M-1.
 4) PROVIDE AN AIR VELOCITY CALCULATION FOR THE BOOTH IN
 COMPLIANCE WITH SECTION 502.7.3.3 FBC-14 MECHANICAL.
 5) SHEET M-1: THE LOCATION OF THE AIR INTAKE SHALL BE
 LOCATED NOT LESS THAN 10' HORIZONTALLY FROM THE EXHAUST
 OUTLET- REFER TO SECTION 401.4 FBC-14 MECHANICAL.
 6) M-1 & M2: PLEASE INDICATE THE CLEARANCE DISTANCE
 MEASUREMENTS FROM THE EXHAUST OUTLET TO THE PROPERTY
 LINES: SEE SECTION 501.3.1 ITEM #1- 30' CLEARANCE
 REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-14 Cont ID  
Sent By sgraham Date 2015-12-14 Time 14:29 Rev Time 0.00
Received By sgraham Date 2015-12-14 Time 14:29 Sent To M
Notes
***NONE***