Plan Review Details - Permit 15101027
Plan Review Stops For Permit 15101027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-30 Cont ID  
Sent By jwitmer Date 2015-12-30 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2015-12-30 Time 09:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-12 Cont ID  
Sent By jwitmer Date 2015-11-12 Time 13:10 Rev Time 0.00
Received By jwitmer Date 2015-11-12 Time 11:43 Sent To  
Notes
2015-11-12 12:56:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15101027
 ADD: 1700 PALM BEACH LAKES BLVD. # 150
 CONT: HOLT LEE
 TEL: (954)725-4881
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 12/2015
 ACTION: DENIED
  
 1) SHEET A0.01 AND SHEET A0.02. SHEET A0.01 SHOWS THIS
 PROJECT TO BE A BUSINESS OCCUPANCY. SHEET A0.02 SHOWS
 THE FLOOR PLAN WITH A LARGE PORTION OF THE SUITE TO BE
 A SHOWROOM. BUSINESS OCCUPANCIES ARE USSALLY OFFICES
 THAT OFFER PROFESSIONAL OR SERVICE-TYPE TRANACTIONS,
 INCLUDING STORAGE OF RECORDS AND ACCOUNTS. THE LARGE
 AREA THAT IS INDICATED AS A SHOW ROOM MAKES THIS
 OCCUPNCY SOUND AS IF A MERCANTILE OCCUPANCY. 2014 FBC-B
 304.1 BUSINESS VERSES SECTION 309.1 MERCANTILE?
  
 2) SHEET A0.02 AND A1.11 BOTH SHOW THE FRONT ENTRY
 WALL. SHEET A0.02 SHOWS THE WALL A SOLID WALL INTHE
 WALL INDEX THIS SHEET, THAT WALL TYPE IS NOT
 IDENTIFIED. SHEET A1.11 DOES HAVE WALL TAG IDENTIFYING
 TAGS, BUT THIS WALL IS MISSING A WALL TAG TYPE.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A0.02 SHOWS THE CONFERENCE ROOM WITH 16
 CHAIRS, WHICH MAKES A OCCUPANT LOAD OF 16. THE ISSUE
 WITH THIS ROOM THERE ARE 2 DOORS INTO THIS SPACE, ONE A
 SWING DOOR THE OTHER A SLIDER. UNDER THE 2014 FBC-B
 SECTION 1008.1.2 EXCEPTION # 9 ALLOWS MANUALLY OPERATED
 HORIZONTAL SLIDING DOORS ARE PERMITTED IN A MEANS OF
 EGRESS FROM A SPACE WITHIN AN OCCUPANT LOAD OF 10 OR
 LESS. PLEASE IDENTIFY THE SWING DOOR AS THE MEANS OF
 EGRESS WITH A DIRECTIONAL FBC-B 1006.1.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-28 Cont ID  
Sent By albarran Date 2016-01-28 Time 17:03 Rev Time 0.00
Received By albarran Date 2016-01-28 Time 16:40 Sent To  
Notes
2016-01-28 17:06:57AFTER DISCUSSING MY COMMENTS WITH DWAYNE OF KAMM
 CONSULTING WE CONCUR ON THE RESPONSE TO THE COMMENTS.
 HE WILL SUBMIT A RESPONSE AS PER OUR DISCUSSION; UPON
 RECEIPT I WILL RELEASE THE PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-27 Cont ID  
Sent By albarran Date 2016-01-27 Time 15:47 Rev Time 0.00
Received By albarran Date 2016-01-27 Time 13:28 Sent To I
Notes
2016-01-27 15:48:08YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL.
  
 PER THE NOTES ON THE FIRST ELECTRICAL REVIEW, YOU WERE
 INSTRUCTED TO SUBMIT A NARRATIVE INDICATING THE ACTION
 TAKEN TO ADDRESS EACH COMMENT NOTED. BELOW IS THE
 RESULT OF THE FAILED SECOND REVIEW.
  
 COMMENT 1. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 18? OF THE TOP OF A SHOW
 WINDOW FOR EACH 12 LINEAR FT. OR MAJOR PORTION THEREOF
 OF SHOW WINDOW AREA MEASURED HORIZONTALLY.
 REVIEW RESULT: THERE IS NO INDICATION ON THE PLANS THAT
 THIS HAS BEEN ADDRESSED. I DO NOT SEE SHOW WINDOW
 OUTLETS ON THE PLANS.
  
 COMMENT 2. NEC 215.5: A DIAGRAM SHALL BE PROVIDED
 SHOWING FEEDER DETAILS. THIS DIAGRAM SHALL INCLUDE LOAD
 CALCULATIONS, CONDUCTOR SIZING AND TYPE OF INSULATION
 USED.
 REVIEW RESULT: YOU WERE ASKED FOR A RISER DIAGRAM WITH
 LOAD CALCS AND CONDUCTOR SIZING AND RATING. ON THE
 SUBMITTED DIAGRAM YOU FAIL TO INCLUDE THE SOURCE OF
 PANEL H. YOU SHALL INCLUDE THE CONDUCTOR SIZING FOR THE
 PANELS. FURTHERMORE, AS A RESULT OF THE NEW RISER YOU
 INCLUDED PANEL L1 WITH A CONNECTED LOAD OF 81 AMP (29.2
 KVA*1000/360=81) AND AN OCPD OF 60 AMP. IS THIS PANEL
 WIRED FOR THE 60 AMP PER THE OCPD, 80 AMPS PER THE
 CONNECTED LOAD OR THE 150 AMP FOR THE BUS?
  
 COMMENT 3. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT
 ACCESSIBLE TO PEDESTRIANS SHALL HAVE AT LEAST ONE
 OUTLET IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE FOR
 SIGN OR OUTLINE LIGHTING SYSTEM.
 REVIEW RESULT: THE CODE SECTION CLEARLY STATES A SIGN
 OUTLET IS REQUIRED AT EACH PEDESTRIAN ENTRY. YOU HAVE
 PROVIDED THE REQUIRED OUTLET AT THE MAIN ENTRY ONLY.
 COMMENT 4. FBC?E C402.4.8: RECESSED LIGHTING INSTALLED
 IN THE BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT THE TRANSFER OF AIR BETWEEN CONDITIONED
 AND UNCONDITIONED SPACE.
 REVIEW RESULT: NOW THAT A FIXTURE SCHEDULE HAS BEEN
 SUBMITTED, IT IS INDICATED THAT RECESSED LIGHTING WILL
 NOT BE USED.
  
 COMMENT 5. FBC?EC405.5: SHOW COMPLIANCE WITH INTERIOR
 LIGHTING POWER REQUIREMENTS AS INDICATED BY SECTIONS
 C405.5.1 & C405.5.2.
 REVIEW RESULT: LIGHT DENSITY CALCULATIONS SHALL BE
 CORRECTED AND THE LIGHTING DESIGNED TO COMPLY. LIGHTING
 POWER ALLOWANCES BUILDING AREA METHOD, WHICH IS WHAT
 YOU APPEAR TO HAVE USED, INDICATES THAT THE ALLOWABLE
 W/FT2 FOR AN OFFICE IS 0.9. THE OCCUPANCY ANALYSIS
 REFLECTS THE AREA TO BE 5843 FT2. THEREFORE THE
 ALLOWABLE LIGHT DENSITY IS 5258.7 WATTS. THE 33
 FLUORESCENTS AT 28 W/EA. ALONG WITH THE 77 DOWN LIGHTS
 AT 19 W/EA. PUTS YOU BEYOND THE ALLOWABLE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-25 Cont ID  
Sent By albarran Date 2015-11-25 Time 11:09 Rev Time 0.00
Received By albarran Date 2015-11-25 Time 10:29 Sent To I
Notes
2015-11-25 11:10:18THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. NEC 210.62: AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED WITHIN 18? OF THE TOP OF A SHOW WINDOW FOR
 EACH 12 LINEAR FT. OR MAJOR PORTION THEREOF OF SHOW
 WINDOW AREA MEASURED HORIZONTALLY.
 2. NEC 215.5: A DIAGRAM SHALL BE PROVIDED SHOWING
 FEEDER DETAILS. THIS DIAGRAM SHALL INCLUDE LOAD
 CALCULATIONS, CONDUCTOR SIZING AND TYPE OF INSULATION
 USED.
 3. NEC 600.5: EACH COMMERCIAL ESTABLISHMENT ACCESSIBLE
 TO PEDESTRIANS SHALL HAVE AT LEAST ONE OUTLET IN AN
 ACCESSIBLE LOCATION AT EACH ENTRANCE FOR SIGN OR
 OUTLINE LIGHTING SYSTEM.
 4. FBC-E C402.4.8: RECESSED LIGHTING INSTALLED IN THE
 BUILDING THERMAL ENVELOPE SHALL BE IC RATED AND SEALED
 TO LIMIT THE TRANSFER OF AIR BETWEEN CONDITIONED AND
 UNCONDITIONED SPACE.
 5. FBC-EC405.5: SHOW COMPLIANCE WITH INTERIOR LIGHTING
 POWER REQUIREMENTS AS INDICATED BY SECTIONS C405.5.1 &
 C405.5.2
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-30 Cont ID  
Sent By scaldero Date 2015-12-30 Time 13:39 Rev Time 0.00
Received By scaldero Date 2015-12-30 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By scaldero Date 2015-11-03 Time 14:56 Rev Time 0.00
Received By scaldero Date 2015-11-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-27 Cont ID  
Sent By albarran Date 2016-02-02 Time 09:09 Rev Time 0.00
Received By albarran Date 2015-12-11 Time 09:27 Sent To  
Notes
2016-02-02 09:13:082/2/16 RECEIVED THE RESPONSE LETTER FROM DUANE AND
 RELEASED PLANS. DUANE CONTACTED VIA EMAIL. SENT FILE TO
 LARGE "H" BIN . MA
2016-01-27 16:10:181/27/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "H". MA
2015-12-16 09:28:01C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-25 Cont ID  
Sent By albarran Date 2015-11-25 Time 11:13 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 13:55 Sent To  
Notes
2015-11-25 11:14:5211/25/15 FAILED MULTIPLE TRADE REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "H". MA
2015-11-02 13:55:21C33

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By ccole Date 2015-12-21 Time 15:22 Rev Time 0.00
Received By ccole Date 2015-12-21 Time 15:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By ccole Date 2015-11-06 Time 10:27 Rev Time 0.00
Received By ccole Date 2015-11-06 Time 10:27 Sent To  
Notes
2015-11-06 11:04:311ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15101027
 11/6/15
  
 1) SHEET NOTE #6 ON A1.01 INDICATES REMOVAL OF ALL HVAC
 EQUIPMENT ETC., HOWEVER THE HEAT PUMPS ARE SHOWN AS
 EXISTING ON SHEET M2.1. PLEASE CLARIFY THE SCOPE OF
 MECHANICAL WORK FOR THE PROPOSED PROJECT AND INCLUDE
 ADDITIONAL KEY NOTES ON M2.1 FOR DUCTWORK AND DEVICES.
 2) M2.1: INDICATE THE TERMINATION LOCATION OF THE NEW
 TOILET ROOM EXHAUST DUCT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-20 Cont ID  
Sent By tklarge Date 2015-12-20 Time 06:13 Rev Time 0.00
Received By tklarge Date 2015-12-20 Time 05:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 11:50 Rev Time 0.00
Received By tklarge Date 2015-11-16 Time 10:28 Sent To  
Notes
2015-11-23 14:03:2311/23/15 ON MALBARRAN'S DESK. CP
2015-11-16 12:52:301) FOR A BUSINESS OCCUPANCY WITH AN OCCUPANT LOAD OF 59
 PERSONS A TOTAL OF 2 WATER CLOSETS ARE REQUIRED FOR THE
 MALES AND 2 WATER CLOSETS ARE REQUIRED FOR THE FEMALES
 PER TABLE 403.1 OF THE 2014 FBC-PLUMBING.
 2) A DRINKING FOUNTAIN IS REQUIRED PER 2014
 FBC-PLUMBING TABLE 403.1. A MINIMUM OF 2 DRINKING
 FOUNTAINS ARE REQUIRED PER TABLE 403.1 FOOTNOTE (E) AND
 THE 2014 FBC-ACCESSIBILITY SEC.211.2.
 3) SEE BUILDING PLAN REVIEW COMMENT REGARDING THE
 OCCUPANCY TYPE OF THIS SPACE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy