Plan Review Details - Permit 15100992
Plan Review Stops For Permit 15100992
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-10-13 Cont ID  
Sent By jwitmer Date 2016-10-13 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2016-10-13 Time 14:26 Sent To  
Notes
2016-10-13 14:29:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100992/ WAWA CANOPY
 ADD: 1520 BELVEDERE RD.
 CONT: ICONSTRUCTORS, LLC
 TEL: 813-287-9000
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 4TH REVIEW
 DATE: THURS. OCT. 13/ 2016
 ACTION: BUILDING PROVISO
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 2) COMPLIED. THE FRONT COVER SHEET LIST 6 PRODUCT
 APPROVALS SUBMITTED:
 2.1) ATAS DUTCH METAL ROOFING FL 3556R-5
 2.2) KAWNEER WINDOW NOA 14-02130.18
 2.3) KAWNEER DOOR NOA 14-0602.02
 2.4) JAMES HARDI NOA 15-0122.03
 2.5) BORAL STONE FL 1504.7 / 100378.05 R-3
 2.6) BASF PERMALATH 1000 GLASS FIBER LATH ERS-2429
  
 3) BUILDING PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS.2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS. METAL EXTERIOR DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP
 INSULATION, ASSEMBLIES FOR FLAT ROOF, ROOF TOP
 EXHAUST FANS
 (E) SHUTTERS- BAHAMA SHUTTERS
 (G) PRE-ENGINEERED ROOF TOP A/C STANDS
 (H) ROOF TOP LADDER( SHOP DRAWINGS)
  
 4) ROVISO: 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED
 BY DCA RULE 9N-3SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER/
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-08-26 Cont ID  
Sent By jwitmer Date 2016-08-26 Time 17:08 Rev Time 0.00
Received By jwitmer Date 2016-08-26 Time 17:08 Sent To  
Notes
2016-08-26 17:09:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100992 WAWA CANOPY
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED) NOT REGISTERED
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: FRI. AUGUST 26/2016
 ACTION: DENIED
  
 IMPORTANT!!!!!! PLEASE NOTE THIS LAST SUBMITTAL THE
 PERMIT RUNNER DID NOT LET THE PERMIT TECH KNOW THERE
 WERE PERMIT APPLICATIONS FROM THE CONTRACTOR IN THE
 PACKAGE. WE CAN NOT PROCESS THE APPLICATIONS SINCE
 THERE WERE NONE OF THE REQUIRED DOCUMENTS TO REGISTER
 THE CONTRACTOR, THE REQUIRED DOCUMENTS ARE:
 A) A CURRENT STATE LICENSE FOR THE QUALIFIER
 B) A CURRENT BUSINESS TAX LICENSE/ OCCUPATIONAL LICENSE
 FOR THEIR OFFICE
 C) CURRENT GENERAL LIABILITY
 D) CURRENT WORKERS COMP
  
 GENERAL LIBILITY & CORKERS COMP CERTIFICATE TO BE MADE
 OUT TO THE:
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, F 33401L
  
  
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS
  
 2) 4TH REQUEST. IMPORTANT!!!!!!!!!! NOTE 3 SET OF PAPER
 PLANS ARE REQUIRED. NOTE ONLY 2 SETS OF PLAN ARE
 SUBMITTED. ALL OTHER DOCUMENTS HAVE 3 SETS.
  
  
 6) COMPLIED. THE FRONT COVER SHEET LIST 6 PRODUCT
 APPROVALS SUBMITTED:
 1) ATAS DUTCH METAL ROOFING FL 3556R-5
 2) KAWNEER WINDOW NOA 14-02130.18
 3) KAWNEER DOOR NOA 14-0602.02
 4) JAMES HARDI NOA 15-0122.03
 5) BORAL STONE FL 1504.7 / 100378.05 R-3
 6) BASF PERMALATH 1000 GLASS FIBER LATH ERS-2429
  
 7A) BUILDING PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. METAL EXTERIOR DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES,R-40 ROOF TOP
 INSULATION, ASSEMBLIES FOR FLAT ROOF, ROOF TOP
 EXHAUST FANS
 (E) SHUTTERS- BAHAMA SHUTTERS
 (G) PRE-ENGINEERED ROOF TOP A/C STANDS
 (H) ROOF TOP LADDER( SHOP DRAWINGS)
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-05-14 Cont ID  
Sent By jwitmer Date 2016-05-14 Time 15:30 Rev Time 0.00
Received By jwitmer Date 2016-05-14 Time 15:01 Sent To  
Notes
2016-05-14 15:20:06BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100992 WAWA GAS CANOPY
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED)
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SAT. MAY 14/2016
 ACTION: DENIED
  
 1) COMPLIED. SITE PLAN SUBMITTED.
  
 2) 3RD REQUEST. ONLY 2 SOILS REPORTS WERE SUBMITTED AND
 PLANS FOR THE CONVENIENCE STORE, NONE FOR THE CANOPY. .
 IF THE CONVENIENCE STORE HAS A DIFFERENT CONTRACTOR
 THAN THE CANOPY 3 SETS OF PLANS AND SOILS REPORTS WILL
 BE NEEDED FOR EACH CONTRACTOR AS WELL AS FOR THE
 UNDERGROUND TANK CONTRACTOR.
  
 SEMI-COMPLIED. SUBMITTED SOILS REPORT FOR A
 QUESTIONABLE SOIL ZONE .SEE COMMENTS FROM 2ND REVIEW ON
 VARYING DEPTHS OF SUSPECTED BURIED DEBRIS.
  
 2A) 3RD. REQUEST. THE STRUCTURAL ENGINEER OF RECORD
 PLEASE RESPOND WHAT STEPS ARE GOING TO BE UNDERTAKEN TO
 MAKE THIS SITE A FOR A STABLE FOUNDATION AND BUILDABLE
 FOR THIS TYPE OF STRUCTURE.
 THE RESPONSE LETTER COMES FROM MOLLI LINDSEY NOT THE
 STRUCTURAL ENGINEER OF RECORD. PLEASE ALLOW THE
 STRUCTURAL ENGINEER TO WRITE THEIR OWN RESPONSE. TO
 DATE THE BUILDING DEPARTMENT HASN'T RECEIVED
 DOCUMENTATION THERE IS A SOILS ENGINEER INVOLVED IN THE
 MEDIATION OF THE SOILS NOR A CONTRACTOR HAS HIRED A
 GEOTECHNICAL FIRM.
  
  
 THE STRUCTURAL ENGINEER OF RECORD IT APPEARS HAS NOT
 SEEN THE SOILS REPORT WHICH REFERENCES THERE BEING A
 WASTE LANDFILL THICKNESS VARYING UP TO 23 FEET THICK
 WITH AN AVERAGE THICKNESS OF 10 FEET IN THICKNESS. THE
 STRUCTURAL SHEET S1 NOTE A INDICATES NO SOILS REPORT
 PROVIDED. PAGE 3 OF THE REPORT INDICATES USING A ERI
 TRANSECT FIGURE -1 SHOWS THE ESTIMATED THICKNESS OF THE
 SUSPECTED BURIED DEBRIS ON THE ERI TRANSECTS IN PLAN
 VIEW IN 5 FT. INCREMENTS FROM PURPLE (THINNEST AT 0
 FEET BLS) TO RED (THICKEST AT OVER 40 FEET BLS).
 THE ERI TRANSECT SCANS A1-A4 SHOW THAT THE A-1 SCAN HAS
 THE MOST SIGNIFICANT POTENTIAL FOR SETTLEMENT.
  
 THIS AREA IS ALSO IN A QUESTIONABLE SOILS ZONE SINCE
 THERE HAS BEEN MUCK FOUND ALONG THE CANAL JUST EAST OF
 THE SITE. THE SOILS TESTING BORING LOGS SHOW THE
 BORINGS HAVE ONLY WENT DOWN TEN FEET.
  
 THE SOILS REPORT ALSO INDICATES THE LOT ELEVATION IS
 APPROXIMATELY 15 TO 20 FEET ABOVE THE STREET GRADE
 ELEVATION AND THIS LAYER OF SOILS WOULD NEED TO BE
 REMOVED FROM THE SITE TO OBTAIN A WORKING GRADE FOR THE
 SITE.
  
 2A) PLEASE ALSO PROVIDE DETAILED INFORMATION WHAT STEPS
 WILL ALSO NEED TO STABILIZE THE SOILS AND TO SECURE THE
 UNDERGROUND FUEL TANKS AND KEEP THEM SAFE FROM MOVEMENT
 AND SETTLEMENT, ONCE THE TANKS ARE FULL.
  
 3) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.)
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER
 STEEL IS WELDED OR BOLTED TOGETHER.
  
 3A) 3RD REQUEST. RESIDENT INSPECTOR FORMS MUST BE
 SIGNED BY ALL PARTIES NOTARIZED AND RETURNED TO THE
 BUILDING DEPARTMENT. FORMS WERE SENT TO:
 1) [email protected] MON. NOV. 23/2015 @ 08:14 AM.
 2) MOLLIL@C-P,COM SUN. FEB. 21/ 2016 @ 07:54 AM.
  
 3B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 3C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3D) 3RD REQUEST. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED.
  
 3E) NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM
 BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 4) COMPLIED, UNDERGROUND TANKS TO BE INSTALLED BEFORE
 CANOPY FOUNDATION CAN START.
  
 5)PROVIO: DEFERRED SUBMITTALS. BELOW IS A LIST OF
 COMPONENTS AND CLADDING FOR PRODUCT APPROVALS THAT CAN
 BE SUBMITTED NOW OR MAY BE CONSIDERED A DEFERRED
 SUBMITTAL (107.3.4.2.) 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010.
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 PRE-ENGINEERED METAL PANEL DECKING
 PRE-ENGINEERED LAMINATED PANEL DECKING
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) PROVISO; 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-21 Cont ID  
Sent By jwitmer Date 2016-02-21 Time 10:26 Rev Time 0.00
Received By jwitmer Date 2016-02-21 Time 10:01 Sent To  
Notes
2016-02-21 10:26:27BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100992 WAWA GAS CANOPY
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED)
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUN. FEB. 21/2016
 ACTION: DENIED
  
 1) COMPLIED. SITE PLAN SUBMITTED.
  
 2) ONLY 2 SOILS REPORTS WERE SUBMITTED AND PLANS. IF
 THE CONVENIENCE STORE HAS A DIFFERENT CONTRACTOR THAN
 THE CANOPY 3 SETS OF PLANS AND SOILS REPORTS WILL BE
 NEEDED FOR EACH CONTRACTOR AS WELL AS FOR THE
 UNDERGROUND TANK CONTRACTOR.
  
 SEMI-COMPLIED. SUBMITTED SOILS REPORT FOR A
 QUESTIONABLE SOIL ZONE .
  
 THE STRUCTURAL ENGINEER OF RECORD IT APPEARS HAS NOT
 SEEN THE SOILS REPORT WHICH REFERENCES THERE BEING A
 WASTE LANDFILL THICKNESS VARYING UP TO 23 FEET THICK
 WITH AN AVERAGE THICKNESS OF 10 FEET IN THICKNESS. THE
 STRUCTURAL SHEET S1 NOTE A INDICATES NO SOILS REPORT
 PROVIDED. PAGE 3 OF THE REPORT INDICATES USING A ERI
 TRANSECT FIGURE -1 SHOWS THE ESTIMATED THICKNESS OF THE
 SUSPECTED BURIED DEBRIS ON THE ERI TRANSECTS IN PLAN
 VIEW IN 5 FT. INCREMENTS FROM PURPLE (THINNEST AT 0
 FEET BLS) TO RED (THICKEST AT OVER 40 FEET BLS).
 THE ERI TRANSECT SCANS A1-A4 SHOW THAT THE A-1 SCAN HAS
 THE MOST SIGNIFICANT POTENTIAL FOR SETTLEMENT.
  
 THIS AREA IS ALSO IN A QUESTIONABLE SOILS ZONE SINCE
 THERE HAS BEEN MUCK FOUND ALONG THE CANAL JUST EAST OF
 THE SITE. THE SOILS TESTING BORING LOGS SHOW THE
 BORINGS HAVE ONLY WENT DOWN TEN FEET.
  
 THE SOILS REPORT ALSO INDICATES THE LOT ELEVATION IS
 APPROXIMATELY 15 TO 20 FEET ABOVE THE STREET GRADE
 ELEVATION AND THIS LAYER OF SOILS WOULD NEED TO BE
 REMOVED FROM THE SITE TO OBTAIN A WORKING GRADE FOR THE
 SITE.
  
 2A) THE STRUCTURAL ENGINEER OF RECORD PLEASE RESPOND
 WHAT STEPS ARE GOING TO BE UNDERTAKEN TO MAKE THIS SITE
 A FOR A STABLE FOUNDATION AND BUILDABLE FOR THIS TYPE
 OF STRUCTURE.
  
 2B) PLEASE ALSO PROVIDE DETAILED INFORMATION WHAT STEPS
 WILL ALSO NEED TO STABILIZE THE SOILS AND TO SECURE THE
 UNDERGROUND FUEL TANKS AND KEEP THEM SAFE FROM MOVEMENT
 AND SETTLEMENT, ONCE THE TANKS ARE FULL.
  
 3) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.)
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER
 STEEL IS WELDED OR BOLTED TOGETHER.
  
 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS WERE SENT TO:
 1) [email protected] MON. NOV. 23/2015 @ 08:14 AM.
 2) MOLLIL@C-P,COM SUN. FEB. 21/ 2016 @ 07:54 AM.
  
 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) COMPLIED, UNDERGROUND TANKS TO BE INSTALLED BEFORE
 CANOPY FOUNDATION CAN START.
  
 5)PROVIO: DEFERRED SUBMITTALS. BELOW IS A LIST OF
 COMPONENTS AND CLADDING FOR PRODUCT APPROVALS THAT CAN
 BE SUBMITTED NOW OR MAY BE CONSIDERED A DEFERRED
 SUBMITTAL (107.3.4.2.) 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010.
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 PRE-ENGINEERED METAL PANEL DECKING
 PRE-ENGINEERED LAMINATED PANEL DECKING
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 6) PROVISO; 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-23 Cont ID  
Sent By jwitmer Date 2015-11-23 Time 14:15 Rev Time  
Received By jwitmer Date 2015-11-23 Time 12:01 Sent To  
Notes
2015-11-23 14:14:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100992 WAWA GAS CANOPY
 ADD: 1520 BELVEDERE RD.
 CONT: TBD( TO BE DETERMINED)
 TEL: 407-661-9100 X2462
 E-MAIL: [email protected]
  
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 23/2015
 ACTION: DENIED
  
 1) MISSING FROM PLANS SITE PLAN. 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION. 107.2.5 SITE
 PLAN. / 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS.
 (1.) SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
  
 2) MISSING FROM PLAN REVIEW SOILS REPORT THE AREA IS IN
 A QUESTIONABLE SOIL ZONE . 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION. 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS.
 (8.) STRUCTURAL REQUIREMENTS SHALL INCLUDE: SOIL
 CONDITIONS/ANALYSIS
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: 7.)
 FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION STEEL STRUCTURE WHERE EITHER
 STEEL IS WELDED OR BOLTED TOGETHER.
 3A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS WERE SENT TO: : [email protected] MON.
 NOV. 23/2015 @ 08:14 AM.
  
 3B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT: KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 3D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 3E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 4) UNKNOWN ELEMENT IS THE LOCATION OF THE UNDERGROUND
 TANK LOCATION, AND CLOSENESS TO THE CANOPY FOUNDATIONS,
 WHICH WILL BE INSTALLED FIRST, UNDERMINING OF THE
 CANOPY FOUNDATIONS OR IS THERE GOING TO BE SHEET PILING
 INSTALLED TEMPORARILY TO STOP THE EFFECT OF UNDERMINING
 OF THE CANOPY FOUNDATION. 1808.7. FOUNDATIONS ON OR
 ADJACENT TO SLOPES.
  
 5) BELOW IS A LIST OF COMPONENTS AND CLADDING FOR
 PRODUCT APPROVALS THAT CAN BE SUBMITTED NOW OR MAY BE
 CONSIDERED A DEFERRED SUBMITTAL (107.3.4.2.) 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By albarran Date 2016-03-16 Time 15:53 Rev Time 0.00
Received By albarran Date 2016-03-16 Time 15:53 Sent To  
Notes
2016-03-16 15:54:05ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED. AT FIRST I HAD QUESTIONS
 ABOUT THE FIRST COMMENT DEALING WITH LIGHTING CONTROL
 FOR THE ILLUMINATION WITHIN THE TRASH COMPOUND, BUT
 AFTER DISCUSSING THE MATTER WITH THE DESIGN
 PROFESSIONAL, THEIR INTENT IS FOR THE AREA TO REMAIN
 LIT WHILE THE STORE IS OPEN DURING THE NIGHT TIME FOR
 SECURITY PURPOSES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By albarran Date 2015-12-29 Time 15:09 Rev Time 0.00
Received By albarran Date 2015-12-29 Time 09:14 Sent To POLICE
Notes
2015-12-29 15:11:48THIS PERMIT IS RUNNER TOGEETHER WITH PERMIT 15100991
 AND IS SHARING THE PLAN SET, THEREFORE THIS PERMIT WILL
 PASS AS SOON AS THE PRIMARY PERMIT IS APPROVED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-09 Cont ID  
Sent By pleduc Date 2016-02-09 Time   Rev Time 0.00
Received By pleduc Date 2016-02-09 Time 16:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By pleduc Date 2015-11-30 Time   Rev Time 0.00
Received By pleduc Date 2015-11-25 Time 14:23 Sent To  
Notes
2015-11-30 10:37:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS NO DETAIL SUBMITTED REGARDING THE GAS CANOPY
 TO COMPLETE A PROPER REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-10-13 Cont ID  
Sent By   Date 2016-10-13 Time   Rev Time 0.00
Received By lmarchan Date 2016-09-21 Time 13:05 Sent To  
Notes
2016-09-22 13:05:49C31

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-31 Cont ID  
Sent By cpuell Date 2016-08-31 Time 08:33 Rev Time 0.00
Received By cpuell Date 2016-08-12 Time 13:01 Sent To  
Notes
2016-08-12 13:01:33C35
 *TRAVELLING WITH 15100991*

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-01 Cont ID  
Sent By skennedy Date 2016-06-01 Time 11:35 Rev Time 0.00
Received By skennedy Date 2016-05-14 Time 15:10 Sent To  
Notes
2016-05-14 15:11:26THE PERMIT RUNNER NEVER TOLD THE PERMIT CLERK THERE
 WERE 2 PERMIT RE-SUBMITTALS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-16 Cont ID  
Sent By skennedy Date 2016-03-16 Time 16:54 Rev Time 0.00
Received By skennedy Date 2016-02-03 Time 07:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-04 Cont ID  
Sent By skennedy Date 2016-01-04 Time 15:02 Rev Time 0.00
Received By skennedy Date 2015-10-28 Time 14:15 Sent To  
Notes
2015-10-28 14:00:38C39
 TRAVELLING WITH 15100991

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By gjohnson Date 2016-03-16 Time 13:39 Rev Time 0.00
Received By gjohnson Date 2016-03-16 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By gjohnson Date 2015-11-09 Time 16:50 Rev Time 0.00
Received By gjohnson Date 2015-11-09 Time 16:50 Sent To  
Notes
2015-11-09 16:50:52 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS
  
 1.PLEASE SUBMIT SIGNED AND SEALED CIVIL DRAWINGS
 SHOWING SANITARY SEWER ,WATER SERVICE,AND STORM.
 PER WPB AMEND.TO FBC SEC 107.2.1
 2. SHEET P-3 IT APPEARS THAT HALF THE ROOF IS BEING
 DRAINED BY A ROOF DRAIN AND HALF BY SCUPPERS PLEASE
 CLARIFY.
 3. PROVIDE SIZING CALCULATIONS FOR ALL GUTTERS
 ,SCUPPERS AND ROOF DRAINS.
 PER WPB AMEND.TO FBC SEC 107.2.1.3
 4.ALL DRAINS IN FOOD AND DRINK PREP AND SERVICE AREAS
 SHALL BE ON THE GREASE SYSTEM.
 PER FBC P SEC 1003.3.1
 5. PLEASE PROVIDE MANUFACTURE SPEC SHEETS AND
 INSTILLATION GUIDES FOR WATER SOFTENER, AND FILER
 SYSTEMS, PRESSURE WASHER, SANITIZER ,
 PER.WPB AMEND.TO FBC SEC 107.2.1
 6. SHEET P1 SHOW TRAP PRIMERS FOR ALL FLOOR DRAINS.
 PER.WPB AMEND.TO FBC SEC 107.2.1
  
 1111.4 MINIMUM NUMBER OF ROOF DRAINS.
 NOT LESS THAN TWO ROOF DRAINS SHALL BE INSTALLED IN
 ROOF AREAS 10,000 SQUARE FEET (929 M2) OR LESS AND NOT
 LESS THAN FOUR ROOF DRAINS SHALL BE INSTALLED IN ROOFS
 OVER 10,000 SQUARE FEET (929 M 2 ) IN AREA.
  
 A COMPLETE COMPREHENSIVE REVIEW CAN NOT BE COMPLETED AT
 THIS TIME DO TO LACK OF INFORMATION . THERE MAYBE
 ADDITIONAL COMMENTS ON SECOND REVIEW WHEN INFO IS
 PROVIDED.

Review Stop POLICE POLICE
Rev No 1 Status P Date 2016-06-01 Cont ID  
Sent By skennedy Date 2016-06-01 Time 11:34 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-10-13 Cont ID  
Sent By jwitmer Date 2016-10-13 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2016-10-13 Time 14:30 Sent To  
Notes
2016-10-13 14:30:401) PROVIO: DEFERRED SUBMITTALS. BELOW IS A LIST OF
 COMPONENTS AND CLADDING FOR PRODUCT APPROVALS THAT CAN
 BE SUBMITTED NOW OR MAY BE CONSIDERED A DEFERRED
 SUBMITTAL (107.3.4.2.) 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010.
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 PRE-ENGINEERED METAL PANEL DECKING
 PRE-ENGINEERED LAMINATED PANEL DECKING
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2) PROVISO; 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-02-21 Cont ID  
Sent By   Date 2016-02-21 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-21 Time 10:28 Sent To  
Notes
2016-02-21 10:29:401) PROVIO: DEFERRED SUBMITTALS. BELOW IS A LIST OF
 COMPONENTS AND CLADDING FOR PRODUCT APPROVALS THAT CAN
 BE SUBMITTED NOW OR MAY BE CONSIDERED A DEFERRED
 SUBMITTAL (107.3.4.2.) 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010.
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 PRE-ENGINEERED METAL PANEL DECKING
 PRE-ENGINEERED LAMINATED PANEL DECKING
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2) PROVISO; 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-02-21 Cont ID  
Sent By jwitmer Date 2015-11-23 Time   Rev Time 0.00
Received By jwitmer Date 2015-11-23 Time   Sent To  
Notes
2016-02-21 10:28:26NO ROOFING PRODUCT APPROVALS WERRE SUBMITTED.

Review Stop Z ZONING
Rev No 5 Status P Date 2016-09-27 Cont ID  
Sent By ajones Date 2016-09-27 Time 16:02 Rev Time 0.00
Received By ajones Date 2016-09-27 Time 16:02 Sent To  
Notes
2016-09-27 16:03:379/27/16- APPROVED WITH THE FOLLOWING:9/27/16- WITH THE
 FOLLOWING PROVISO:
  
 * THE DEVELOPER SHALL PROVIDE A WRITTEN STATEMENT FROM
 THE PALM BEACH COUNTY TRAFFIC DIVISION
 CONFIRMING THAT ALL APPLICABLE PROPORTIONATE SHARE
 PAYMENTS FOR THE IMPROVEMENTS AT THE
 INTERSECTION OF BELVEDERE ROAD AND AUSTRALIAN AVENUE
 HAVE BEEN MADE PRIOR TO FIRST INSPECTION. A
 COPY OF THE WRITTEN STATEMENT SHALL BE PROVIDED TO THE
 DEVELOPMENT SERVICES DEPARTMENT
 ?PLANNING DIVISION.
  
 ADDITIONAL NOTES:
  
 * SEPARATE PERMIT APPLICATIONS REQUIRED FOR:
 LANDSCAPING, SITE LIGHTING AND SIGNAGE.
  
 * ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $750,000.00 IS SUBJECT TO
 THE ART IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINE IN
 CHAPTER 78, ARTICLE V, OF THE CITY?S CODE
 OF ORDINANCES. PLEASE CONTACT SYBILLE WELTER, A PP
 COORDINATOR @ (561)
 822?1521 FOR INFORMATION.

Review Stop Z ZONING
Rev No 4 Status F Date 2016-08-30 Cont ID  
Sent By llouie Date 2016-08-30 Time   Rev Time 0.00
Received By llouie Date 2016-08-30 Time   Sent To  
Notes
2016-08-30 17:20:58** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SITE PLAN FOR THE WAWA DOES NOT REFLECT THE LATEST
 CHANGES MADE TO THE SITE. LATEST APPROVED PLANS BY THE
 PLANNING DIVISION MUST BE INCORPORATED AS PART OF THE
 BUILDING PERMIT SET. (REFERENCE: PLANNING BOARD CASE
 NO. 1670C, APPROVAL ISSUED ON 8/16/16)
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  
  
 PROVISO:
  
 * THE DEVELOPER SHALL PROVIDE A WRITTEN STATEMENT FROM
 THE PALM BEACH COUNTY TRAFFIC DIVISION CONFIRMING THAT
 ALL APPLICABLE PROPORTIONATE SHARE PAYMENTS FOR THE
 IMPROVEMENTS AT THE INTERSECTION OF BELVEDERE ROAD AND
 AUSTRALIAN AVENUE HAVE BEEN MADE PRIOR TO FIRST
 INSPECTION. A COPY OF THE WRITTEN STATEMENT SHALL BE
 PROVIDED TO THE DEVELOPMENT SERVICES DEPARTMENT
 -PLANNING DIVISION.
  
  
 ADDITIONAL NOTES:
  
 * SEPARATE PERMIT APPLICATIONS REQUIRED FOR:
 LANDSCAPING, SITE LIGHTING AND SIGNAGE.
  
 * ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $750,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINE IN CHAPTER
 78, ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. PLEASE
 CONTACT SYBILLE WELTER, AIPP COORDINATOR @ (561)
 822-1521 FOR INFORMATION.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2016-05-23 Cont ID  
Sent By llouie Date 2016-05-23 Time   Rev Time 0.00
Received By llouie Date 2016-05-23 Time   Sent To  
Notes
2016-05-23 11:43:37** FAILED **
  
 1.) 11/16/15 & 3/16/16 REPEAT COMMENT: CONDITION #2 IN
 THE SITE PLAN APPROVAL LETTER ISSUED BY THE PLANNING
 DIVISION ON 10/16/2015 HAS NOT BEEN ADDRESSED. PER THE
 SITE PLAN APPROVAL LETTER, CONDITION #2 MUST BE
 ADDRESSED PRIOR TO BUILDING PERMIT APPROVAL.
  
 ADDITIONAL NOTES:
  
 * SEPARATE PERMIT APPLICATIONS REQUIRED FOR:
 LANDSCAPING, SITE LIGHTING AND SIGNAGE.
  
 * ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $500,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINE IN CHAPTER
 78, ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. PLEASE
 CONTACT SYBILLE WELTER, AIPP COORDINATOR @ (561)
 822-1521 FOR INFORMATION.
  
 * PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-16 Cont ID  
Sent By llouie Date 2016-03-16 Time 08:59 Rev Time 0.00
Received By llouie Date 2016-03-16 Time 08:59 Sent To  
Notes
2016-03-16 08:59:38** FAILED **
  
 1.) 11/16/15 REPEAT COMMENT CONDITION #2 IN THE SITE
 PLAN APPROVAL LETTER ISSUED BY THE PLANNING DIVISION ON
 10/16/2015 HAS NOT BEEN ADDRESSED. PER THE SITE PLAN
 APPROVAL LETTER, CONDITION #2 MUST BE ADDRESSED PRIOR
 TO BUILDING PERMIT APPROVAL.
  
 ADDITIONAL NOTES:
  
 * SEPARATE PERMIT APPLICATIONS REQUIRED FOR:
 LANDSCAPING, SITE LIGHTING AND SIGNAGE.
  
 * ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $500,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINE IN CHAPTER
 78, ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. PLEASE
 CONTACT SYBILLE WELTER, AIPP COORDINATOR @ (561)
 822-1521 FOR INFORMATION.
  
 * PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU
 HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By llouie Date 2015-11-16 Time 11:02 Rev Time 0.00
Received By llouie Date 2015-11-16 Time 11:02 Sent To  
Notes
2015-11-16 11:03:50** FAILED **
  
 1.) SITE PLAN SHOWING THE GENERAL CIRCULATION, LOCATION
 OF PARKING, BUILDING ORIENTATION ON THE SITE, SITE DATA
 INFORMATION, ETC., IS AN INTEGRAL PART OF PERMIT
 SUBMITTAL; HOWEVER, THE PLAN SEEMS TO BE MISSING FROM
 THE PERMIT APPLICATION. PLEASE PROVIDE.
  
 2.) CONDITION #2 IN THE SITE PLAN APPROVAL LETTER
 ISSUED BY THE PLANNING DIVISION ON 10/16/2015 HAS NOT
 BEEN ADDRESSED. PER THE SITE PLAN APPROVAL LETTER,
 CONDITION #2 MUST BE ADDRESSED PRIOR TO BUILDING PERMIT
 APPROVAL.
  
 3.) LABEL ALL ELEVATIONS WITH DIRECTIONS (I.E. NORTH,
 SOUTH, EAST AND WEST).
  
 4.) SEPARATE PERMIT APPLICATIONS REQUIRED FOR:
 LANDSCAPING, SITE LIGHTING AND SIGNAGE.
  
 5..) THE CITY OF WEST PALM BEACH POLICE DEPARTMENT -
 CRIME PREVENTION UNIT SHALL REVIEW AND APPROVE ALL
 CONSTRUCTION DRAWINGS TO ENSURE ADHERENCE TO
 GENERALLY-ACCEPTED CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN PRINCIPALS, AS WELL AS COMPLIANCE
 WITH ALL LOCAL AND STATE REGULATIONS PERTAINING TO THE
 PROPOSED USE. SUCH SUBMITTAL SHALL INCLUDE A
 CONSTRUCTION SITE SECURITY AND MANAGEMENT PLAN.
  
 6.) ALL NEW PRIVATE DEVELOPMENT, NEW CONSTRUCTION,
 RENOVATION OR REMODELING, WHERE THE TOTAL VERTICAL
 CONSTRUCTION OF ALL BUILDINGS ON A PROJECT SITE ARE
 EQUAL OR GREATER THAN $500,000.00 IS SUBJECT TO THE ART
 IN PUBLIC PLACES (AIPP) REQUIREMENTS OUTLINE IN CHAPTER
 78, ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. PLEASE
 CONTACT SYBILLE WELTER, AIPP COORDINATOR @ (561)
 822-1521 FOR INFORMATION.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF YOU HAVE
 QUESTIONS.