| 2015-11-05 17:34:26 | ****CORRECTIONS**** |
| | |
| | ART LANGE - BUILDING INSPECTOR |
| | 561-805-6667 [email protected] |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION |
| | |
| | |
| | 1. FBC-107.1 GENERAL - FAC 61G1-16.004 - A TITLE BLOCK |
| | MUST APPEAR ON ALL ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION IDENTIFICATION SHEETS THAT |
| | ARE REQUIRED TO BE SIGNED AND SEALED. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION |
| | NUMBER OF THE PERSON SEALING THE DOCUMENT. |
| | (7) THE DATE OF PLANS REVISION, IF THE PLANS ARE |
| | REVISED. |
| | (8) FOR THE PURPOSES OF THIS RULE, FIRM IS DEFINED TO |
| | BE A CORPORATION, LIMITED LIABILITY COMPANY, |
| | PARTNERSHIP, PERSON PRACTICING UNDER A FICTITIOUS NAME, |
| | OR PERSON PRACTICING ARCHITECTURE OR INTERIOR DESIGN IN |
| | HIS OR HER OWN NAME. |
| | |
| | FBC-107.1 GENERAL - FAC 61G15-23.002 - PROVIDE A TITLE |
| | BLOCK FOR THE ENGINEER OF RECORD CONSISTENT WITH THE |
| | REQUIREMENTS OF THIS SECTION, E.G.: FIRM NAME, LICENSE |
| | NUMBER, PHONE NUMBER...ETC. |
| | |
| | 2. PLEASE INCLUDE DESIGN CRITERIA ON PLANS. FOR EXAMPLE |
| | FBC CODE, NEC CODE, ASCE 7-10, WINDSPEED. |
| | |
| | 3. DETAIL 9 - PLEASE PROVIDE BOLT SIZING AND SPACING. |
| | |