Plan Review Details - Permit 15100960
Plan Review Stops For Permit 15100960
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-16 Cont ID  
Sent By pleduc Date 2015-11-16 Time   Rev Time 0.00
Received By pleduc Date 2015-11-16 Time 15:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-29 Cont ID  
Sent By pleduc Date 2015-10-29 Time   Rev Time 0.00
Received By pleduc Date 2015-10-29 Time 13:40 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-17 Cont ID  
Sent By tklarge Date 2015-11-17 Time 04:54 Rev Time 0.00
Received By tklarge Date 2015-11-03 Time 11:17 Sent To  
Notes
2015-11-04 11:18:06RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-02 Cont ID  
Sent By tklarge Date 2015-11-02 Time 06:57 Rev Time 0.00
Received By tklarge Date 2015-10-27 Time 09:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By tklarge Date 2015-11-13 Time 04:54 Rev Time 0.00
Received By tklarge Date 2015-11-13 Time 03:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-02 Cont ID  
Sent By tklarge Date 2015-11-02 Time 06:57 Rev Time 0.00
Received By tklarge Date 2015-11-02 Time 05:29 Sent To  
Notes
2015-11-02 06:21:581) INDICATE ON THE SUBMITTED PLAN IF THE BOILERS ARE
 LOCATED ON THE INTERIOR OR THE EXTERIOR OF THE
 STRUCTURE. A SPECIFICATION SHEET THAT WAS SUBMITTED IS
 FOR AN OUTDOOR WATER HEATER. CLARIFY.
 2) THE PLAN SHEET FROM LOCHINVAR NOTES (2) AWN 200 AND
 (2) RJA 200 TYPES OF EQUIPMENT. SUBMIT TWO COPIES OF
 THE MANUFACTURER'S SPECIFICATION SHEETS FOR THE AWN 200
 PIECE OF EQUIPMENT IF IT IS BEING INSTALLED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) THERE ARE FIVE DIFFERENT PIECES OF EQUIPMENT THAT
 ARE REFERENCED IN HTIS SUBMITTAL: AWN 200, RJA 200, OAN
 151-286, OAN 400-801, AND A WRITTEN MODEL OF AWN 501
 PM. I HAVE NO IDEA WHAT IS BEING INSTALLED/REPLACED
 UNDER THIS PERMIT. IF THERE IS ADDITIONAL EQUIPMENT
 BEING INSTALLED, REVISE THE SCOPE OF WORK ON THE PERMIT
 APPLICATION AND ALSO THE VALUE. WPB AMEND. TO FBC SEC.
 107.2.1.
 4) THE SHEET SUBMITTED FOR THE LOCK-TEMP RJA 200 IS
 ILLEGIBLE. SUBMIT TWO LEGIBLE COPIES OF THE
 MANUFACTURER'S SPECS FOR THIS PIECE OF EQUIPMENT. THE
 SHEET THAT WAS SUBMITTED IS NOT THE MANUFACTURER'S
 SPECIFICATIONS, IT IS A SALS SHEET FROM THE INTERNET
 AND IS UNACCEPTABLE.
 5) THE BOILERS SHALL HAVE A THERMAL EFFICIENCY OF 80 %
 IN ACCORDANCE WITH ANSI Z21.10.3 ( GAS WATER HEATERS
 WITH INPUT TATINGS ABOVE 75,000 BTU/HR.) & THE 2014
 FBC-ENERGY, SEC.C404.2 7 TABLE C404.2.
 6) IDENTIFY ALL PIECES OF EQIPMENT ON THE PLAN VIEW
 DRAWING.IDENTIFY ANY EXISTING EQUIPMENT THAT IS NOT
 BEING REPLACED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  