Plan Review Details - Permit 15100876
Plan Review Stops For Permit 15100876
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By rmcdouga Date 2015-12-02 Time 18:36 Rev Time 0.00
Received By rmcdouga Date 2015-12-02 Time 18:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By rmcdouga Date 2015-11-09 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2015-11-09 Time 07:27 Sent To  
Notes
2015-11-09 08:08:59REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH FBC-R308.4.5 GLAZING AND WET
 SURFACES. GLAZING IN WALLS, ENCLOSURES OR FENCES
 CONTAINING OR FACING HOT TUBS, SPAS, WHIRLPOOLS,
 SAUNAS, STEAM ROOMS, BATHTUBS, SHOWERS AND INDOOR OR
 OUTDOOR SWIMMING POOLS WHERE THE BOTTOM EXPOSED EDGE OF
 THE GLAZING IS LESS THAN 60 INCHES (1524 MM) MEASURED
 VERTICALLY ABOVE ANY STANDING OR WALKING SURFACE SHALL
 BE CONSIDERED A HAZARDOUS LOCATION. THIS SHALL APPLY TO
 SINGLE GLAZING AND ALL PANES IN MULTIPLE GLAZING.
 EXCEPTION: GLAZING THAT IS MORE THAN 60 INCHES (1524
 MM), MEASURED HORIZONTALLY AND IN A STRAIGHT LINE, FROM
 THE WATER?S EDGE OF A BATHTUB, HOT TUB, SPA, WHIRLPOOL,
 OR SWIMMING POOL.
  
 2) SHOW COMPLIANCE WITH FBC-R303.3 BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET, ONE-HALF OF
 WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By rmcdouga Date 2015-12-02 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2015-12-02 Time 18:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By rmcdouga Date 2015-11-06 Time 19:40 Rev Time 0.00
Received By rmcdouga Date 2015-11-06 Time 19:40 Sent To  
Notes
2015-11-06 19:46:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO SETS OF AN ELECTRICAL FLOOR PLAN. SHOW
 LIGHTING AND RECEPTACLE OUTLETS AS REQUIRED BY NEC
 210.52.
  
 2) PROVIDE TWO COPIES OF A PANEL SCHEDULE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By rmcdouga Date 2015-12-02 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2015-12-01 Time 14:39 Sent To  
Notes
2015-12-01 14:39:49RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-09 Cont ID  
Sent By rmcdouga Date 2015-11-09 Time 08:09 Rev Time 0.00
Received By rmcdouga Date 2015-10-23 Time 11:19 Sent To  
Notes
2015-10-26 11:20:08R08

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By gjohnson Date 2015-12-02 Time 14:32 Rev Time 0.00
Received By gjohnson Date 2015-12-02 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-29 Cont ID  
Sent By gjohnson Date 2015-10-29 Time 17:16 Rev Time 0.00
Received By gjohnson Date 2015-10-29 Time 17:16 Sent To  
Notes
2015-10-29 17:22:591ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PROVIDE PLUMBING RISER DIAGRAM.PER WPB AMEND. TO FBC
 SEC 107.3.5.3(11)
 1. TOILET SHALL COMPLY WITH FBC P SEC405.3.1 WATER
 CLOSETS, SHALL NOT BE SET CLOSER THAN 15 INCHES (381
 MM) FROM ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY
 OR OTHER OBSTRUCTION ,WATER CLOSET COMPARTMENTS SHALL
 BE NOT LESS THAN 30 INCHES