| 2015-11-09 11:28:23 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15100773 |
| | ADD: 328 FERN ST. |
| | CONT: L. J. SHEEHAN, INC. |
| | TEL: (561)223-2750 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. NOV.09/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A WRITTEN RESPONSE TO WHAT IS THE |
| | CORRECT ADDRESS. THE CITY OF WEST PALM BEACH AND THE P. |
| | B. C. PROPERTY APPRAISERS OFFICE BOTH LIST UNDER THE |
| | PCN 74-43-43-21-01-009-0070 AS 326 FERN ST. THE PLANS |
| | ALL HAVE THE ADDRESS AS 326 FERN ST. THE PERMIT |
| | APPLICATION HAS THE ADDRESS AS 328 FERN ST. THE CITY |
| | ALSO HAS A TENANT ADDRESS OF 328 FERN ST. IF THIS |
| | PROJECT IS GOING TO USE THE ADDRESS OF 328 FERN ST. THE |
| | PLANS WILL NEED TO BE REPRINTED TO THE CORRECT ADDRESS. |
| | IF THE 326 FERN ST. THEN A TENANT SUITE NUMBER WILL |
| | NEED TO BE DETERMINED. FOR A LIST OF EXISTING SUITE |
| | NUMBERS FOR THE 1ST FLOOR YOU WOULD NEED TO CONTACT |
| | SANDY WURAFTIC AT 561-805-6688. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED. |
| | |
| | 2) NOTICE, NO ACTION IS REQUIRED. THIS IS A RESTAURANT, |
| | A BUSINESS OCCUPANCY, OCCUPANT LOAD OF LESS THAN 50, NO |
| | IMPACT FEES ARE DUE, P. B. C. IMPACT FEES OFFICE. |
| | IMPACT FEES WERE PAID FOR RETAIL (MERCANTILE |
| | OCCUPANCY). TRACKING NUMBER MU-2013-023597-0000. |
| | |
| | 3) SHEET S-1 PROVIDES THE WIND DESIGN CRITERIA TO BE |
| | UNDER THE 2014 FBC-B, 5TH EDITION BUT THE PRESSURES |
| | SEEM A LITTLE LOW FOR A MEAN ROOF HEIGHT OF 87 FEET. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS & MULLIONS. |
| | |
| | 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 6) SHEET A-0.00 SHOWS DOOR TO RESTROOMS 106 & 107. |
| | SHEET A-6.01 THE DOOR SCHEDULE INDICATES THESE DOORS TO |
| | BE 2'-10" IN WIDTH. A 3'-0" DOOR WIDTH IS REQUIRED TO |
| | OBTAIN A 32 INCH CLEAR OPENING. 2014 FBC-B 1008.1.1 |
| | SIZE OF DOORS. |
| | THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE |
| | SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL |
| | PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR |
| | OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 7) SHEET A2.01 INDICATES A DETAIL 4 /A5.10 THE SERVICE |
| | COUNTER TO BE 40 INCHES TALL. PLEASE SHOW COMPLIANCE |
| | WITH THE 2014 ACCESSIBILITY CODE EITHER 904.4.1PARALLEL |
| | APPROACH OR 904.4.2 FRONTAL APPROACH. |
| | |
| | 8) SHEET A2.01 ALSO WILL NEED TO SHOW THE HEIGHT FOR |
| | ACCESSIBLE TABLES IN COMPLIANCE WITH 2014 ACCESSIBILITY |
| | CODE 902.3. PLEASE SHOW COMPLIANCE WITH 226.1 AND |
| | 226.2. |
| | |
| | 9) PLEASE NOTE SHEET M5.1 THE NEW ROOF TOP UNIT C-2 |
| | WIND DESIGN CRITERIA APPEARS TO BE FOR A BUILDING , |
| | THAN 60 FEET TALL. THIS BUILDING MEAN ROOF HEIGHT IS 87 |
| | FEET IN HEIGHT. ALSO NOTE SHEET M1.2 INDICATES THIS |
| | UNIT IS TO TIE DOWN TO A EXISTING ROOF RACK NOT A CURB |
| | AS INDICATED ON M5.1. |
| | M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| | APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| | BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |