Plan Review Details - Permit 15100709
| Plan Review Stops For Permit 15100709 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-01 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-30 |
Time |
10:54 |
Sent To |
|
|
| Notes |
| 2015-10-30 10:55:09 | RESUB ROUTED TO TKLARGE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-26 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-20 |
Time |
14:14 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2015-11-03 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-03 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-03 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2015-11-03 08:38:26 | APPROVED AFTER DISCUSSION WITH MR. PUPO FROM CREDO ENG. | | | TKL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2015-11-01 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-11-01 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-11-01 |
Time |
07:19 |
Sent To |
|
|
| Notes |
| 2015-10-31 06:06:49 | THE DISCHARGE FROM THE EVAPORATORS IN COOLERS WHERE | | | FOOD IS BEING STORED TO A CONDENSATE WELL RAISES | | | CONCERNS. PLEASE REFER TO 2010 FBC-PLUMBING, SEC. 801.2 | | | - PROTECTION. ALSO, REFER TO SECS.802.1.1, 802.2, | | | 802.3.I CANNOT APPROVE THIS METHOD OF DISCHARGE. THE | | | EVAPOEATORS SHALL DRAIN TO THE SANITARY SYSTEM PER THE | | | ABOVE NOTED CODE SECTIONS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2015-10-26 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-10-26 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-26 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2015-10-26 12:04:55 | THE EVAPORATOR DRAINS CANNOT DISCHARGE TO THE GREASY | | | WASTE SYSTEM PER THE FBC-PLUMBING SEC. 1003.2.WASTES | | | THAT DO NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT | | | BE DISCHARGED INTO ANY INTERCEPTOR OR SEPARATOR. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-10-21 |
Time |
03:40 |
Sent To |
|
|
| Notes |
| 2015-10-21 12:59:36 | THE DRAINS FROM THE EVAPORATORS SHALL NOT DRAIN TO THE | | | GREASY WASTE SYSTEM. WASTES THAT DO NOT REQUIRE | | | TREATMENT |
|
|
|