Plan Review Details - Permit 15100682
Plan Review Stops For Permit 15100682
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-01-28 Cont ID  
Sent By jwitmer Date 2016-01-28 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2016-01-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-11 Cont ID  
Sent By jwitmer Date 2016-01-11 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2016-01-11 Time 11:43 Sent To  
Notes
2016-01-11 16:50:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100682
 ADD: 5827 CORPORATE WAY
 CONT: SHIFF
 TEL: (954)524-2575
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 08/2016
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST. RESPONSE INDICATES PLEASE SEE ENCLOSED
 FIRE ALARM SHOP DRAWINGS. THE COVERSHEET A-0.0
 INDICATES THE OCCUPANT LOAD OF ON BOTH THE 1ST FLOOR
 AND 2ND FLOOR AS 90+ WHEREAS THE SQUARE FOOTAGE IS
 10,040 SQ. FT./ 100= 101 OCCUPANTS. THE 2014 EXISTING
 BUILDING CODE 904.2.1 WILL REFER YOU FOR A MANUAL FIRE
 ALARM TO THE FBC-BUILDING 907.2.2 SINCE THE BUSINESS
 OCCUPANCY ON THE 2 ND FLOOR IS OVER 100 IN GROUP B
 OCCUPANCY.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By jwitmer Date 2015-11-03 Time 12:31 Rev Time 0.00
Received By jwitmer Date 2015-11-03 Time 07:00 Sent To  
Notes
2015-11-03 12:31:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100682
 ADD: 5827 CORPORATE WAY
 CONT: SHIFF
 TEL: (954)524-2575
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 08/2016
 ACTION: DENIED
  
 1-5) COMPLIED.
  
 6) 2ND REQUEST. RESPONSE INDICATES PLEASE SEE ENCLOSED
 FIRE ALARM SHOP DRAWINGS. THE COVERSHEET A-0.0
 INDICATES THE OCCUPANT LOAD OF ON BOTH THE 1ST FLOOR
 AND 2ND FLOOR AS 90+ WHEREAS THE SQUARE FOOTAGE IS
 10,040 SQ. FT./ 100= 101 OCCUPANTS. THE 2014 EXISTING
 BUILDING CODE 904.2.1 WILL REFER YOU FOR A MANUAL FIRE
 ALARM TO THE FBC-BUILDING 907.2.2 SINCE THE BUSINESS
 OCCUPANCY ON THE 2 ND FLOOR IS OVER 100 IN GROUP B
 OCCUPANCY.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-05 Cont ID  
Sent By albarran Date 2016-02-05 Time 09:22 Rev Time 0.00
Received By albarran Date 2016-02-05 Time 08:50 Sent To I
Notes
2016-02-05 09:23:04ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 08:58 Rev Time 0.00
Received By albarran Date 2016-01-13 Time 17:02 Sent To I
Notes
2016-01-14 09:02:54YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
 ALL OF THE PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED EXCEPT THE ONE MENTIONED
 BELOW.
 COMMENT #2: NEC 215.5 REQUIRES A FEEDER DIAGRAM WITH
 LOAD CALCS AND CONDUCTOR SIZING. THE FEEDER DIAGRAM
 PROVIDED FAILS TO INCLUDE ALL THE PANELS INCLUDED
 WITHIN THE AREA OF THE SCOPE OF WORK.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 15:36 Rev Time 0.00
Received By albarran Date 2015-11-19 Time 13:24 Sent To I
Notes
2015-11-19 15:36:55THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. DUE TO THE CONFLICT BETWEEN NEW & EXISTING
 LUMINAIRES IT IS IMPRACTICAL TO DETERMINE FROM THE
 SUBMITTED DRAWINGS THE ACTUAL LOCATION OF EMERGENCY AND
 EXIT LIGHTING. THEREFORE, IT WILL BE UP TO THE FIELD
 INSPECTOR TO DETERMINE COMPLIANCE.
 2. NEC 215.5 REQUIRES A FEEDER DIAGRAM WITH LOAD CALCS
 AND CONDUCTOR SIZING. THE FEEDER DIAGRAM PROVIDED FAILS
 TO INCLUDE ALL THE PANELS INCLUDED WITHIN THE AREA OF
 THE SCOPE OF WORK.
 3. NEC 408.4(B) REQUIRES THAT ALL PANELS BE MARKED TO
 INDICATED THE LOCATION OF THEIR SOURCE OF POWER AND
 DISCONNECT.
 4. NEC 410.30 REQUIRES THAT LUMINARIES WEIGHING GREATER
 THAN 6 LBS OR EXCEED 16 IN. BE SUPPORTED BY OTHER THAN
 THE OUTLET BOX.
 5. NEC 410.36(B) REQUIRES THAT LUMINAIRES IN SUSPENDED
 CEILINGS BE SECURELY FASTENED TO THE CEILING MEMBERS BY
 MECHANICAL MEANS.
 6. FBC-E SECTION C402.4.8 STATES THAT ALL RECESSED
 LIGHTING INSTALLED IN THE BUILDING?S THERMAL ENVELOPE
 BE IC RATED AND BE SEALED TO LIMIT THE LEAKAGE OF AIR
 BETWEEN THE CONDITIONED AND NON-CONDITIONED SPACE.
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-07 Cont ID  
Sent By pleduc Date 2016-01-07 Time   Rev Time 0.00
Received By pleduc Date 2016-01-07 Time 15:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-29 Cont ID  
Sent By pleduc Date 2015-10-29 Time   Rev Time 0.00
Received By pleduc Date 2015-10-29 Time 09:20 Sent To  
Notes
2015-10-29 09:54:53THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. SHEET A 0.0, INDICATES AN INCORRECT REFERENCE TO THE
 FIRE CODE,
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 2. SHEET E 1, DOES NOT INDICATE AN EXIT SIGN AT THE NEW
 DOOR FROM THE CORRIDOR TO THE IT ROOM. INSTALL AN EXIT
 SIGN INSIDE THE CORRIDOR AT THE IT ROOM DOOR.
  
 3. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 ANY FIRE ALARM SYSTEM EQUIPMENT FOR CODE COVERAGE AND
 COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS
 REQUIRE AN EVALUATION OF THE EXISTING EQUIPMENT.
 IF EXISTING, THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEM, EXCEEDS 4
 HOURS, A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED
 UNTIL FULL AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-05 Cont ID  
Sent By albarran Date 2016-02-05 Time 09:25 Rev Time 0.00
Received By albarran Date 2016-01-20 Time 13:49 Sent To  
Notes
2016-02-05 09:26:432/5/16 PASSED THE LAST OF ALL TRADE REVIEWS AND IS
 READY FOR ISSUANCE. CONTRACTOR NOTIFIED VIA EMAIL. SENT
 FILE TO LARGE READY BIN "S". MA
2016-01-21 13:50:05C27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 09:09 Rev Time 0.00
Received By albarran Date 2015-12-29 Time 11:07 Sent To  
Notes
2016-01-14 09:10:381/14/16 FAILED THE LAST OF THE TRADE REVIEWS. DESIGN
 PROFESSIONAL ADVISED VIA EMAIL. SENT TO LARGE DENIED
 BIN "S". MA
2016-01-04 13:21:18C34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 15:39 Rev Time 0.00
Received By albarran Date 2015-10-20 Time 12:53 Sent To  
Notes
2015-11-19 15:38:5911/19/15 FAILED THE ELECTRICAL REVIEW AS NOTED.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "S". MA
2015-10-20 12:53:27B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-04 Cont ID  
Sent By skennedy Date 2016-01-04 Time 11:07 Rev Time 0.00
Received By skennedy Date 2015-12-29 Time 10:24 Sent To  
Notes
2015-12-30 10:24:39B25

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-01-29 Cont ID  
Sent By ccole Date 2016-01-29 Time 07:18 Rev Time 0.00
Received By ccole Date 2016-01-29 Time 07:18 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By ccole Date 2016-01-05 Time 10:11 Rev Time 0.00
Received By ccole Date 2016-01-05 Time 10:11 Sent To  
Notes
2016-01-05 10:15:252ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100682
 01/05/16
  
 1) SHEET M-1: THE LOCATION OF THE OUTDOOR AIR INTAKE ON
 THE WEST SIDE OF THE FIRST FLOOR APPEARS TO BE NOT IN
 COMPLIANCE WITH SECTION 401.4 ITEM #2 WHIC REQUIRES A
 10' CLEARANCE TO THE PARKING LOT OR DRIVE LANE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By ccole Date 2015-11-04 Time 07:40 Rev Time 0.00
Received By ccole Date 2015-11-04 Time 10:32 Sent To  
Notes
2015-11-04 08:08:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100682
 11/4/2015
  
 1) SHEET D-2.0: THE DEMO NOTES SHOWN ON THE 2ND FLOOR
 RCP DO NOT MAKE SENSE WITH THE DRAWING: PLEASE REVISE.
 2) M-1: THE PLANS ARE VERY VAGUE AND SHOW ONLY TWO DUCT
 RELOCATIONS IN THE EXPANDED IT ROOM. PLEASE SHOW ALL
 RELOCATED DUCTS, DIIFFUSERS, AND RETURN GRILLS ON THE
 PLAN BASED ON THE NEW CEILING AND LIGHTING LAYOUTS,
 INCLUDING THE WAREHOUSE WHERE THE SUSPENDED CEILING
 WILL BE REMOVED ENTIRELY.
 3) PROVIDE AN AIR DEVICE SCHEDULE.
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUIILDING
 CODE- ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PLEASE PROVIDE CALCULATIONS ON
 THE PLAN TO INDICATE COMPLIANCE.
 5) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.4.3 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-08 Cont ID  
Sent By gjohnson Date 2016-01-08 Time 15:21 Rev Time 0.00
Received By gjohnson Date 2016-01-08 Time 15:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-23 Cont ID  
Sent By gjohnson Date 2015-10-23 Time 17:22 Rev Time 0.00
Received By gjohnson Date 2015-10-23 Time 17:22 Sent To  
Notes
2015-10-23 17:29:221ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.SHEET A-2.2 IT APPEARS THAT YOU ARE ELIMINATING
 RESTROOM 208 AND LEAVING 209 AN ACCESSIBLE BATHROOM CAN
 NOT BE ACCESSED THROUGH A PRIVATE OFFICE.