Plan Review Details - Permit 15100677
Plan Review Stops For Permit 15100677
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-11-20 Cont ID  
Sent By cthroop Date 2015-11-20 Time 14:34 Rev Time 0.00
Received By cthroop Date 2015-11-20 Time 14:34 Sent To  
Notes
2015-11-20 14:34:45CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-22 Cont ID  
Sent By mvaldes Date 2016-02-22 Time 12:04 Rev Time 0.00
Received By mvaldes Date 2016-02-22 Time 12:04 Sent To  
Notes
2016-02-22 12:05:55SPOKED TO PROJECT MANAGER AND WE ADDRESSED THE ISSUE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 13:25 Rev Time 0.00
Received By mvaldes Date 2016-02-17 Time 13:25 Sent To  
Notes
2016-02-17 13:32:57FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 -PROVIDE VOLTAGE DROP CALCULATIONS FROM PANELBOARD
 LOCATION TO LAST SITE LIGHTING ON THE PARTICULAR
 CIRCUIT.FBC-E C405.7.3.1 FEEDERS AND CUSTOMER OWNED
 SERVICE CONDUCTORS.
 SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT
 AT DESIGN LOAD AND 3 % FOR BRANCH CIRCUITS.
  
 ( THIS WILL SHOW US IF ADEQUATE PROTECTION AND WIRE
 SIZES ARE CORRECT AS PER PLAN. ) PANEL C SHOWS ON THE
 4TH FLOOR ACCORDING TO RISER DIAGRAM.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By cthroop Date 2015-11-20 Time 14:34 Rev Time 0.00
Received By ppetty Date 2015-11-05 Time 10:29 Sent To Z
Notes
2015-11-05 10:36:471. PLEASE SHOW POWER SOURCE FOR ENTRY AND NORTH OLIVE
 AVE LIGHTS.
 2. NEED DISTANCE BETWEN FIXTURES, WIRE AND BREAKER SIZE
 FOR OVER CURRENT PROTECTION.
  
 REVIEWED BY; RICHARD JEFFERSON
 FOR COMMENTS PLEASE CONTACT P PETTY AT 561-805-6742
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 13:44 Rev Time 0.00
Received By mvaldes Date 2016-02-12 Time 16:27 Sent To  
Notes
2016-02-12 16:27:40RESUB ROUTED TO PPETTY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-20 Cont ID  
Sent By cthroop Date 2015-11-20 Time 14:33 Rev Time 0.00
Received By cthroop Date 2015-10-20 Time 13:03 Sent To E
Notes
2015-11-16 11:09:22TO MISC 2 BOX.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-11-16 Cont ID  
Sent By aaponte Date 2015-11-16 Time 11:08 Rev Time 0.00
Received By aaponte Date 2015-11-16 Time 11:08 Sent To  
Notes
2015-11-16 11:09:04LIGHTING FIXTURES FOR AREAS INSIDE THE PROPERTY LINE,
 NOT ALONG ROW OR PUBLIC SIDEWALK.