Plan Review Details - Permit 15100627
Plan Review Stops For Permit 15100627
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By cthroop Date 2015-12-21 Time 09:48 Rev Time 0.00
Received By cthroop Date 2015-12-21 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-17 Cont ID  
Sent By cthroop Date 2015-11-17 Time 15:53 Rev Time 0.00
Received By cthroop Date 2015-11-17 Time 15:53 Sent To E
Notes
2015-11-17 16:01:33CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
  
 IDENTIFY WALLS TO BE REMOVED - LOAD BEARING/NON-LOAD
 BEARING.
 IDENTIFY SUB-FLOORING TO BE INSTALLED AND FASTENER
 SCHEDULE AT LIVING ROOM.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-17 Cont ID  
Sent By mvaldes Date 2015-12-17 Time 14:43 Rev Time 0.00
Received By mvaldes Date 2015-12-17 Time 14:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-18 Cont ID  
Sent By mvaldes Date 2015-11-18 Time 08:38 Rev Time 0.00
Received By mvaldes Date 2015-11-18 Time 09:06 Sent To  
Notes
2015-11-18 09:17:40E3901.2.1 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
 E3901.2 GENERAL PURPOSE RECEPTACLE DISTRIBUTION.
 IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING
 ROOM, PARLOR, LIBRARY, DEN, SUN ROOM, BEDROOM,
 RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING
 UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN
 SECTIONS E3901.2.1 THROUGH E3901.2.3 (SEE FIGURE
 E3901.2).
  
  
  
  
 MARIO VALDES
 ELECTRICAL PLANS EXAMINER
 561-805-6700
 ALERNATE CONTACT
 PHIL PETTY
 561-805-6742

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 09:48 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 09:48 Sent To  
Notes
2015-12-12 09:52:441ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GAS HAS NOT BEEN REVIEWED UNDER THIS PERMIT A
 SEPARATE APPLICATION REQUIRED FOR GAS.
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By fmittner Date 2015-12-15 Time 13:06 Rev Time 0.00
Received By fmittner Date 2015-12-15 Time 13:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-11-17 Cont ID  
Sent By fmittner Date 2015-11-17 Time 14:14 Rev Time 0.00
Received By fmittner Date 2015-11-17 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-21 Cont ID  
Sent By cthroop Date 2015-12-21 Time 09:48 Rev Time 0.00
Received By cthroop Date 2015-12-07 Time 10:31 Sent To  
Notes
2015-12-09 10:31:24R17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-18 Cont ID  
Sent By ccole Date 2015-11-18 Time 14:32 Rev Time 0.00
Received By ccole Date 2015-10-19 Time 10:32 Sent To  
Notes
2015-10-21 10:33:10R28

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By ccole Date 2015-12-15 Time 12:05 Rev Time 0.00
Received By ccole Date 2015-12-15 Time 11:38 Sent To  
Notes
2015-12-15 12:09:22PROVISO:
  
 THE OWNER OR OWNER'S ARCHITECT SHALL SIGN THE ENERGY
 COMPLIANCE FORM R405-2014 PRIOR TO PERMIT ISSUANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-18 Cont ID  
Sent By ccole Date 2015-11-18 Time 14:10 Rev Time 0.00
Received By ccole Date 2015-11-18 Time 12:35 Sent To  
Notes
2015-11-18 14:30:351ST REVIEW: FBC 2014 RESIDENTIAL
 PERMIT #15100627
 11/18/15
  
 1) THE MANUAL J WORKSHEETS INDICATE 195 CFM'S OF
 COOLING AND 224 CFM'S OF HEATING ARE REQUIRED FOR THE
 DEN. PLEASE CLARIFY HOW SUPPLY AIR AND RETURN AIR ARE
 BEING PROVIDED TO AND FROM THE ROOM- WILL THERE BE TWO
 TRANSFER GRILLS?
 2) REFER TO SECTION M1305.1.3 FBC-14 RESIDENTIAL
 ANDR403.2.4 FBC-14 ENERGY CONSERVATION AND PROVIDE THE
 DIMENSIONS OF THE ATTIC ACCESS, AND CONSTRUCTION
 DETAILS AND NOTES INDICATING COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 09:47 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 09:46 Sent To  
Notes
2015-12-12 09:48:04SEPARATE GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By gjohnson Date 2015-10-26 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2015-10-26 Time 16:32 Sent To  
Notes
2015-10-26 16:36:29 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. NO WATER HEATER SHOWN PROVIDE LOCATION AND
 SPECIFICATIONS FOR WATER HEATER. PEWR WPB AMEND. TO FBC
 SEC 107.2.1 AND 107.2.1.3