Plan Review Details - Permit 15100606
Plan Review Stops For Permit 15100606
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-22 Cont ID  
Sent By jwitmer Date 2016-03-22 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2016-03-22 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-26 Cont ID  
Sent By jwitmer Date 2016-02-26 Time 07:26 Rev Time 0.00
Received By jwitmer Date 2016-02-26 Time 05:52 Sent To  
Notes
2016-02-26 07:25:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100606
 ADD: 6501 N. JOG RD.
 CONT: ANDREA CONSTRUCTION, INC.
 TEL: (561)358-4797
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB.26/ 2016
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) THE ORIGINAL SHEET A1.0 THE DEMOLITION SHEET VERSES
 THE SUBMITTED 2ND REVIEW OF THE SAME SHEET THE MENS
 RESTROOM HAS CHNGED.
 THE 2ND VERSION OF THE DEMOLITION SHEET SHOULD NOT
 CHANGE. 107.3. EXAMINATION OF DOCUMENTS. NOT
 CONSISTENT.
  
 4A) SHEET A1.1 LIFE SAFETY PLAN IS MISSING FROM BOTH
 SETS OF PLANS FOR THE 2ND REVIEW. 107.2.1.3 ADDITIONAL
 INFORMATION REQUIRED. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED. / 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA
 FOR COMMERCIAL BUILDINGS.
  
 4B) SHEET A1.2 THE NEW 2ND REVIEW SHEET DOES SHOW A NEW
 RESTROOM LAYOUT BUT THERE ARE NOTES THAT THE EXISITNG
 TOILETS ARE TO REMAIN, EXISITING TOLIET FIXTURES AND
 PARTITIONS ARE TO REMAIN, FURNISH AND INSTALL INSULATED
 JACKETS ON EACH SINK UNDER SIDE OF PIPING. THE LAYOUT
 IN BOTH RESTROOMS HAS CHANGED THE NOTE IS NOT ACCURATE.
 PLEASE UPDATE NOTES TO REFECT THE NEW LAYOUT AND WASTE
 AND VENT SYSTEM WHICH WILL ALSO NEED TO CHANGEE TO
 REFLECT THE NEW LAYOUT.
  
 4C) THE 2ND SUBMITTAL OF PLANS, IN TRYING TO SHOW
 COMPLIANCE WITH THE ACCESSIBILITY CODE THE RESTROOM
 DOORS 106 & 107 THE DOOR LOCATIONS HAVE CHANGED AND
 REVERSED THE DOOR SWING TO SWING AGAINST THE RESTROOM
 SIDEWALL. THIS PROVIDES AN ACCESSIBLE ROUTE TO WITHIN
 THE RESTROOM. THE ISSUE IS THE SWING OF THE CUBICAL
 DOOR ALSO NEEDS TO BE REVERSED. THIS IS NEW
 CONSTRUCTION SINCE THIS CONFIGURATION OF THE CUBICAL IS
 NEW. PLEASE REVIEW SECTION 604.8.1.2 DOORS LOCATED IN
 THE FRONT PARTITION, THE DOOR SHALL BE 4 INCHES MAXIMUM
 FROM THE SIDE WALL. THE DOOR SWING SHOULD BE TO ALLOW
 DIRECT ACCESS. THE DOOR SWING INTO THE CUBICAL NEEDS TO
 BE REVERED BUT NOT INTO THE THE ACCESSIBLE TOILET
 COMPARTMENT.
  
 SHOW COMPLIANCE WITH 202.4.1 DISPROPORTIONATE COST THE
 DESIGNER OF RECORD INDICATES THE REVERSING THE SWING ON
 THE RESTROOM DOOR TO AGAINST THE WALL. THERE IS STILL
 THE ISSUE WITH THE STALL DOOR NOT BEING ACCESSIBLE, IT
 ALSO NEEDS TO BE REVERSED. THE ORIGINAL PLANS SHOW THIS
 DESIGN IS NEW WORK
 SHEET A1.1 & A1.2 SHOW THE WORK TO BE PREFORMED BUT
 THERE ARE NOTES THAT NO NEW WORK IN THE RESTROOMS NOR
 THE BREAK AREA. THE CONTRACT VALUE IS $84500.00. 20%
 OF THAT DOLLAR VALUE IS $16,900.00. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 202.4 INDICATES WHAT
 TYPES OF WORK CAN BE BE DEDUCTED FROM THE CONTRACT
 VALUE THEN TAKEN TO SEE WHAT THE 20% DOLLAR VALUE WILL
 BE. THEN SHOW COMPLIANCE WITH 202.4.1 DISPROPORTIONATE
 COST. COSTS THAT MAY BE COUNTED AS EXPENDITURES
 REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY
 INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING AN
 ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN. ONCE THE
 DISPROPROTIONATE COST IS MET NO FURTHER ACCESSIBLE
 ELEMENTS WILL NEED TO BE UPGRADED UNDER THIS PERMIT.
 PLEASE SUPPLY A ITIMIZED COST BREAKDOWN FOR THE 20% OF
 PROPOSED WORK FOR ACCESSIBLE UPGRADES TO THIS BUILDING.
  
 5-6) COMPLIED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 10:54 Sent To  
Notes
2015-10-30 14:49:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100606
 ADD: 6501 N. JOG RD.
 CONT: ANDREA CONSTRUCTION, INC.
 TEL: (561)358-4797
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. OCT. 30/ 2014
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES IN THE NOTES THE STRUCTURAL
 MODIFICATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE
 2010 FBC. PLEASE BE AWARE THAT THE 2014 FBC, THE 5TH
 EDITION OF THE FLORIDA BUILDING CODE WENT INTO AFFECT
 STATEWIDE JUNE 30/ 2015.
  
 2) THE COVERSHEET ALSO INDICATES AS DEFINED BY THE 2014
 FBC-EXISITNG BUILDING CODE THIS IS TO BE A LEVEL 3
 ALTERATION. PLEASE SHOW COMPLIANCE WITH:
 2014 EXIST. BLDG CODE 907.4.1 EVALUATION AND ANALYSIS.
 AN ENGINEERING EVALUATION AND ANALYSIS THAT ESTABLISHES
 THE STRUCTURAL ADEQUACY OF THE ALTERED STRUCTURE SHALL
 BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE CODE OFFICIAL.
  
 3) THE COVERSHEET DOESN'T DECLARE IF THIS IS A LIMITED
 STRUCTURAL ALTERATION(B)907.4.3 OR SUBSTANTIAL
 STRUCTURAL ALTERATION (B) 907.2 SUBSSTANTIAL STRUCTURAL
 ALTERATION.
  
 4) SHEET A1.1 & A1.2 SHOW THE WORK TO BE PREFORMED BUT
 THERE ARE NOTES THAT NO NEW WORK IN THE RESTROOMS NOR
 THE BREAK AREA. THE CONTRACT VALUE IS $84500.00. 20%
 OF THAT DOLLAR VALUE IS $16,900.00. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 202.4 INDICATES WHAT
 TYPES OF WORK CAN BE BE DEDUCTED FROM THE CONTRACT
 VALUE THEN TAKEN TO SEE WHAT THE 20% DOLLAR VALUE WILL
 BE. THEN SHOW COMPLIANCE WITH 202.4.1 DISPROPORTIONATE
 COST. COSTS THAT MAY BE COUNTED AS EXPENDITURES
 REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF TRAVEL MAY
 INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING AN
 ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN. ONCE THE
 DISPROPROTIONATE COST IS MET NO FURTHER ACCESSIBLE
 ELEMENTS WILL NEED TO BE UPGRADED UNDER THIS PERMIT.
 PLEASE SUPPLY A ITIMIZED COST BREAKDOWN FOR THE 20% OF
 PROPOSED WORK FOR ACCESSIBLE UPGRADES TO THIS BUILDING.
  
 5A) SHEET A1.2 SHOWS NEW EXTERIOR WINDOWS (102 & 103)
 IN EXISITNG OPENINGS , THERE IS NO DETAILS IF WINDOW
 BUCKS ARE GOING TO BE INSTALLED OR IF THEY ARE GOING TO
 BE ANCHORED DIRECTLY TO THE CMU FILED UNITS? 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
 1710.10 WHERE THE WOOD BUCK THICKNESS IS 11/2 INCHES
 (38 MM) OR GREATER, THE BUCK SHALL BE SECURELY FASTENED
 TO TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 5B) SHEET A1.2 SHOWS NEW EXTERIOR WINDOWS (102 & 103)
 IN EXISITNG OPENINGS, THIS SUBMITTAL NO PRODUCT
 APPROVALS WERE SUBMITTED.
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31) (B) WINDOWS
  
 5C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5D) THE COVERSHEET INDICATES A VELOCITY PRESSURE OF
 35PSF. PLEASE PROVIDE THE PRESSURES POSITIVE AND
 NEGATIVE FOR 24 SQ. FT. EXPOSURE "C" AT FOR 14 FT MEAN
 ROOF HEIGHT, IN VASD SINCE THE PRODUCT APPROVALS ARE IN
 VASD. 2014 FBC-B 1603.1.4.
  
 6) UNDER THE LEVEL 3 ALTERATIONOF THE 2014 EXISITNG
 BUILDING CODE FOR ENERGY IT DIRECTS YOU TO THE 2014
 ENERGY CODE. PLEASE PROVIDE THE VALUE OF THE STRUCTURE
 BEFORE WORK IS STARTED UNDER THIS PERMIT. IF THE
 BUILDING MEETS THE DEFINITION OF RENOVATION UNDER THE
 ENERG CODE IT CLASSIFIES AS TO WHAT IS REQUIRED FOR
 CODE COMPLIANCE. 2014 FBC-ENERGY:
  
 DEFINITIONS : RENOVATED BUILDING. A RESIDENTIAL OR
 NONRESIDENTIAL BUILDING UNDERGOING ALTERATION THAT
 VARIES OR CHANGES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. PLEASE
 PROVIDE COMPLIANCE WITH 2014 ENERGY CODE C401.2.1 WHICH
 METHOD?
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-23 Cont ID  
Sent By albarran Date 2016-03-23 Time 19:38 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 18:59 Sent To  
Notes
2016-03-23 19:43:04PASSED ELECTRICAL REVIEW BUT MADE SEVERAL NOTES ON THE
 PLANS FOR FINAL INSPECTIONS.
 1. REVISED THE QUOTED EDITION OF THE NEC TO 2011
 2. MARKED FACP CKT ON BOTH PANEL SCHEDULE AND FIRE
 ALARM RISER TO REFERENCE NEC 760.121 (B) INDICATING THE
 BRANCH CIRCUIT REQUIREMENTS.
 3. MARKED THE PANEL SCHEDULE TO NOTE THAT THE EWC SHALL
 BE PROTECTED BY GFCI AS PER NEC 422.52
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 17:11 Rev Time 0.00
Received By albarran Date 2016-02-29 Time 16:26 Sent To  
Notes
2016-02-29 17:22:04THOUGH ALL PREVIOUSLY ADDRESSED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED, THE PLANS ARE INCOMPLETE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 13:00 Rev Time 0.00
Received By albarran Date 2015-11-19 Time 10:53 Sent To  
Notes
2015-11-19 13:01:08THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 FIRE ALARM WORK SHALL BE ON A SEPARATE PERMIT AND SHOP
 DRAWINGS.
 1. YOU HAVE A MYRIAD OF CODES REFERENCED ON THE PLANS.
 REVISE YOU PLANS TO REFLECT ONLY THE APPLICABLE CODES
 AND LET THEM BE CONSISTENT THROUGHOUT THE PLANS.
 2. FBC-E SECTION C402.4.8 REQUIRES THAT ALL RECESSED
 LIGHTING INSTALLED IN THE BUILDING?S THERMAL ENVELOPE
 BE IC RATED AND SEALED TO LIMIT THE LEAKAGE OF AIR
 BETWEEN CONDITIONED AND NONCONDITIONED SPACE.
 3. NEC 700.12 REQUIRES THAT ALL EMERGENCY LIGHTS AND
 EXIT LIGHTS BE ON THE LIGHTING CIRCUIT FOR THE AREA
 WHICH THEY OCCUPY.
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By pleduc Date 2016-03-29 Time 15:11 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-22 Cont ID  
Sent By pleduc Date 2016-02-22 Time   Rev Time 0.00
Received By pleduc Date 2016-02-22 Time 11:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By pleduc Date 2015-10-28 Time   Rev Time 0.00
Received By pleduc Date 2015-10-28 Time 10:07 Sent To  
Notes
2015-10-28 10:23:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1. SHEET A 1.1, INDICATES AN INCORRECT FIRE CODE
 REFERENCE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 IN ADDITION:
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By pleduc Date 2016-03-17 Time 11:34 Sent To  
Notes
2016-03-17 11:39:17B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 17:25 Rev Time 0.00
Received By albarran Date 2016-02-17 Time 09:57 Sent To  
Notes
2016-02-29 17:29:032/29/16 FAILED ELECTRICAL REVIEW DUE TO INCOMPLETE
 PLANS, OTHERWISE OK. FAILED BLDG AS WELL. CONTRACTOR
 NOTIFIED VIA VOICEMAIL TO CELL PHONE. SENT FILE TO
 LARGE DENIED BIN A. MA
2016-02-17 09:58:07B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 13:12 Rev Time 0.00
Received By albarran Date 2015-10-20 Time 14:14 Sent To  
Notes
2015-11-19 13:11:5511/19/15 FAILED THE ELECTRICAL REVIEW AS NOTED.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "A". MA
2015-10-20 14:14:23B24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 10:48 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By ccole Date 2015-11-03 Time 15:18 Rev Time 0.00
Received By ccole Date 2015-11-03 Time 15:18 Sent To  
Notes
2015-11-03 15:34:421ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #1510606
 11/3/15
  
 1) SHEET A1.1: PROVIDE THE LEVEL OF ALTERATION FOR THE
 PROPOSED PROJECT IN COMPLIANCE WITH SECTION 501.1
 FBC-14 EXISTING BUILDING
 2) M-1.1: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING: ALTERED EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62. PROVIDE CALCULATIONS ON THE
 PLAN VERIFYING COMPLIANCE.
 3) M-1.1: PROVIDE DUCT SIZES ON THE PLANS, AND HANGING
 AND SUPPORT DETAILS IN COMPLIANCE WITH THE CURRENT
 SMACNA STANDARDS.
 4) PROVIDE AN AIR DEVICE SCHEDULE FOR THE DIFFUSERS AND
 RETURN GRILLS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-26 Cont ID  
Sent By gjohnson Date 2016-02-26 Time 12:52 Rev Time 0.00
Received By gjohnson Date 2016-02-26 Time 12:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By gjohnson Date 2015-10-27 Time 09:17 Rev Time 0.00
Received By gjohnson Date 2015-10-27 Time 09:17 Sent To  
Notes
2015-10-27 09:17:441ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.ON THE COVER SHEET IN THE GENERAL NOTES THE SCOPE OF
 WORK STATES THAT THERE IS PLUMBING THE PLANS INDICATE
 THAT ALL THE PLUMBING IS EXISTING AND TO REMAIN PLEASE
 CLARIFY .
 PER WPB AMEND. TO FBC SEC 107.2.1
  