| 2015-11-03 18:26:15 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION |
| | OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION |
| | OF THE FBC, (FLORIDA BUILDING CODE) AS APPLICABLE AND |
| | BELOW ARE THE DEFICIENCIES NOTED. |
| | 1. FBC-ENERGY CONSERVATION CODE SECTION 402.4.8 |
| | RECESSED LIGHTING STATES THAT ALL RECESSED LIGHTING |
| | INSTALLED IN THE BLDG.?S THERMAL ENVELOPE SHALL BE |
| | EITHER IC RATED OR SEALED TO PREVENT AIR LEAKAGE |
| | BETWEEN CONDITIONED AND NON-CONDITIONED SPACES. |
| | 2. NEC 215.5 DIAGRAMS OF FEEDERS, A SITE SPECIFIC |
| | FEEDER DIAGRAM SHALL BE PROVIDED. THIS DIAGRAM SHALL |
| | INCLUDE LOAD CALCS AND CONDUCTOR SIZING SPECIFICALLY |
| | FOR THE PANEL OF THE AREAS COVERED WITHIN THE SCOPE OF |
| | THIS PERMIT. |
| | 3. NEC 220.16 REQUIRES THAT LOAD CALCS BE PROVIDED TO |
| | ASCERTAIN THAT THE EXISTING SERVICE CAN ABSORB THE |
| | ADDED LOAD. |
| | 4. THERE ARE SEVERAL ROOMS WITHOUT WINDOWS WHICH MAY |
| | REQUIRE ADDITIONAL EMERGENCY LIGHTING. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | |