| Plan Review Stops For Permit 15100556 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2016-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-06-27 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-06-27 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2016-06-27 09:14:32 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 3RD REVIEW | | | DATE: 6/27/16 | | | ACTION: DENIED | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS. | | | SEE PLAN PG. A100, CONSTRUCTION NOTES C2 AND C5. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW AND | | | DOOR SUBMITTALS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-01-07 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-01-07 |
Time |
13:29 |
Sent To |
E |
|
| Notes |
| 2016-01-07 13:36:30 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOOR. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND | | | DOOR SUBMITTALS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-11-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-04 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-11-04 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2015-11-04 13:36:01 | CHRISTOPHER S. THROOP, C.B.O. | | | BLDG. PLANS EXAMINER ? PX3169 | | | (561) 805-6718 | | | [email protected] | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY | | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND | | | DOOR SUBMITTALS. | | | | | | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. | | | | | | FBC - R301.2.1.2 PROTECTION OF OPENINGS. | | | WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS | | | REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM | | | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR | | | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE | | | LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 | | | OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. | | | GARAGE DOOR GLAZED OPENING PROTECTION FOR WINDBORNE | | | DEBRIS SHALL MEET THE REQUIREMENTS OF AN APPROVED | | | IMPACT RESISTING STANDARD OR ANSI/DASMA 115. | | | | | | PROVIDE FLOOR PLAN AND SECTIONAL VIEW OF WALL DETAILING | | | INTERIOR FINISH AND EXTERIOR WALL SYSTEM. | | | | | | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY | | | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR | | | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL | | | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 | | | & FBC 117. | | | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A | | | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY | | | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK | | | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | | PURPOSES UNTIL APPROVED. | | | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2016-06-17 |
|
|
Cont ID |
|
| Sent By |
vperez |
Date |
2016-06-17 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
vperez |
Date |
2016-06-17 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-01-07 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-01-07 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2016-02-23 08:33:33 | CREATED STOP BY ACCIDENT. CLOSED STOP. CST |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2016-01-07 |
|
|
Cont ID |
|
| Sent By |
mvaldes |
Date |
2016-01-07 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
mvaldes |
Date |
2016-01-07 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2016-01-07 14:36:57 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON | | | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. | | | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, | | | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO | | | RECORDS MANAGEMENT. | | | | | | FOLLOW UP ON PREVIOUS COMMENTS BY SK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-11-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-11-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-11-04 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2015-11-04 13:53:19 | 1ST REVIEW: FBC 2014 5TH ED. & RESIDENTIAL | | | | | | FBC 107 - PROVIDE AN ELECTRICAL PLAN TO DEMONSTRATE ANY | | | PROPOSED ELECTRICAL IMPROVEMENTS. | | | | | | FBC 107 - PROVIDE A FLOOR PLAN TO SHOW THE USE OF THE | | | SPACE AND THE ADJACENT SPACE WHICH COMMUNICATES WITH | | | THE AREA. SHOW LIGHT & SWITCH AND RECEPTACLE LOCATIONS | | | | | | E3903.3 ADDITIONAL LOCATIONS. | | | AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED | | | GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER. AT | | | LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET SHALL | | | BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR | | | SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE LEVEL | | | ACCESS, INCLUDING OUTDOOR EGRESS DOORS FOR ATTACHED | | | GARAGES AND DETACHED GARAGES WITH ELECTRIC POWER. | | | | | | E3903.4 STORAGE OR EQUIPMENT SPACES. | | | IN ATTICS, UNDER-FLOOR SPACES, UTILITY ROOMS AND | | | BASEMENTS, AT LEAST ONE LIGHTING OUTLET SHALL BE | | | INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR | | | CONTAIN EQUIPMENT REQUIRING SERVICING. SUCH LIGHTING | | | OUTLET SHALL BE CONTROLLED BY A WALL SWITCH OR SHALL | | | HAVE AN INTEGRAL SWITCH. AT LEAST ONE POINT OF CONTROL | | | SHALL BE AT THE USUAL POINT OF ENTRY TO THESE SPACES. | | | THE LIGHTING OUTLET SHALL BE PROVIDED AT OR NEAR THE | | | EQUIPMENT REQUIRING SERVICING. | | | | | | E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES. | | | ALL 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE | | | RECEPTACLES INSTALLED IN GARAGES AND GRADE-LEVEL | | | PORTIONS OF UNFINISHED ACCESSORY BUILDINGS USED FOR | | | STORAGE OR WORK AREAS SHALL HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. | | | | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS | | | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | | FEET OF EACH SLEEPING ROOM IF APPLICABLE. | | | | | | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY | | | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR | | | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL | | | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 | | | & FBC 117. | | | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A | | | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY | | | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK | | | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | | PURPOSES UNTIL APPROVED. | | | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2016-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-06-27 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-05-27 |
Time |
11:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2016-01-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2016-01-08 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-11-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-04 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2015-10-16 |
Time |
07:01 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2016-06-27 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2016-06-27 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2016-06-27 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2016-06-27 08:58:08 | BUILDING PLAN REVIEW | | | 2014 FLORIDA BUILDING CODE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER ? PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2016-06-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2016-06-06 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2016-06-06 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2016-06-06 14:34:29 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100556 | | | 6/6/16 | | | | | | 1) INDICATE HOW MINIMUM VENTILATION (OUTDOOR AIR) WILL | | | BE PROVIDED TO THE NEW SPACE- SEE SECTION 401.2. PLEASE | | | NOTE THAT THE AC SCHEDULE INDICATES THE AREA SERVED AS | | | AN "OFFICE" BUT THE PLAN INDICATES "UTILITY ROOM". | | | | | | 2) THE 150 MPH WIND SHOWN IN THE "EQUIPMENT MOUNTING | | | DETAIL" ON M-1 IS INCORRECT, THE WIND SPEED IN WEST | | | PALM BEACH IS 170. PLEASE NOTE THAT THE ARCHITECT OF | | | RECORD HAS NOT PROVIDED COMPLETE WIND LOAD DESIGN | | | CRITERIA FOR ANY OF THE EXTERIOR IMPROVEMENTS- REFER TO | | | SECTION 1609.1.1 FBC-14 BUILDING- DETERMINATION OF WIND | | | LOADS. | | | | | | 3) M-1: THE CONDENSATE FROM THE INDOOR UNIT SHALL NOT | | | DRAIN INTO THE CITY SANITARY SYSTEM PER SEC. 90-126 WPB | | | CODE OR ORDINANCES. | | | | | | 4) M-1: THE RESCHECK COMPLIANCE CERTIFICATE LISTS THE | | | AC SYSTEM AT 19.2 SEER, HOWEVER THE AC SCHEDULE | | | INDICATES 17.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2016-06-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2016-06-09 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2016-06-09 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2016-06-09 14:50:27 | REVIEW APPROVED BY GEORGE EARL 0013-B |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2016-06-14 |
|
|
Cont ID |
|
| Sent By |
nwier |
Date |
2016-06-14 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
njwira |
Date |
2016-06-14 |
Time |
16:26 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2016-01-05 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2016-01-05 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2016-01-05 |
Time |
10:58 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-10-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2015-11-04 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-10-20 |
Time |
12:29 |
Sent To |
B |
|
| Notes |
| 2015-10-20 12:30:19 | 10/20/15 ZONING FAILED | | | | | | 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY SHOWING | | | THE LOCATION OF THE GARAGE |
|
|