Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By shill Date 2015-10-22 Time 08:05 Rev Time 0.00
Received By shill Date 2015-10-22 Time 08:05 Sent To  
Notes
2015-10-22 08:24:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. INSTALLATION SCHEDULE FOR PANELS, SPECIFY THE
 SHUTTER CONNECTION MOUNTING TYPE (NAMING CONVENTION C1,
 C2, C3, ETC. - SHOULD CORRELATE WITH ANCHOR CHARTS ON
 PP 7-8).
  
 2. INSTALLATION SCHEDULE FOR PANELS, SPECIFY THE
 FASTENER. "TAPCON" IS NOT SPECIFIC ENOUGH, SEE PAGES
 7-8. REVISE TO STATE WHICH TYPE OF TAPCON.
  
 3. INSTALLATION SCHEDULE FOR ACCORDIONS, SPECIFY THE
 SHUTTER CONNECTION MOUNTING TYPE (NAMING CONVENTION IS
 1, 2, 3, ETC. - SHOULD CORRELATE WITH ANCHOR CHARTS).
 SEVERAL DIFFERENT OPTIONS WERE CIRCLED; NOT CLEAR WHICH
 IS PROPOSED.
  
 4. INSTALLATION SCHEDULE FOR ACCORDIONS, PROPOSED
 ANCHOR SPACING COLUMN IS BLANK, PLEASE COMPLETE.
  
 5. INSTALLATION SCHEDULE FOR ACCORDIONS, SPECIFY THE
 FASTENER. THIS SHOULD BE CONSISTENT WITH THE FASTENER
 TYPE IN THE ANCHOR CHART.
  
 6. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4.
 INCLUDE THE ROOM DESIGNATION.
  
 7. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL
 BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE. FBC R301, FBC1609, FBC*106.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-22 Cont ID  
Sent By shill Date 2015-10-22 Time 08:24 Rev Time 0.00
Received By shill Date 2015-10-15 Time 10:46 Sent To  
Notes
2015-10-15 10:47:06BLDG <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved