Plan Review Details - Permit 15100422
Plan Review Stops For Permit 15100422
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By mvaldes Date 2015-12-21 Time 17:52 Rev Time 0.00
Received By mvaldes Date 2015-12-21 Time 17:51 Sent To  
Notes
2015-12-21 17:53:481ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 COMMENTS WERE PROPERLY ADRESSED AND MASTER PERMIT
 NUMBER 15060045 WAS USED IN ORDER TO DO SO.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By albarran Date 2015-10-26 Time 19:58 Rev Time 0.00
Received By albarran Date 2015-10-26 Time 19:39 Sent To I
Notes
2015-10-26 20:03:22THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. YOU SHALL SUBMIT ELECTRICAL SPECIFICATIONS FOR THE
 PROPOSED UNIT.
 2. YOU SHALL PROVIDE A FEEDER DIAGRAM AS REQUIRED IN
 NEC 215.5. THIS SHALL INCLUDE SITE SPECIFIC LOAD CALCS
 AND CONDUCTOR SIZING AS PER NEC 440.
 3. YOU SHALL PROVIDE A SITE PLAN SHOWING THE LOCATION
 OF THE VARIOUS ELECTRICAL COMPONENTS OF THE UNITS.
 4. KEEP IN MIND THAT NEC 210.63 REQUIRES THAT THERE BE
 A 15 -20 AMP GFI OUTLET WITHIN 25? OF THE CONDENSING
 UNIT.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By hmoser Date 2015-12-28 Time 08:19 Rev Time 0.00
Received By pleduc Date 2015-12-11 Time   Sent To PC
Notes
2015-12-11 16:06:02PASSED WITH PROVISO: IF BLDG IS SPRINKLED AND/OR
 ALARMED, SPRINKLERS AND NOTIFICATION APPLIANCES MAY BE
 REQUIRED IN COOLERS. (EVALUATE)
 GJT

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-23 Cont ID  
Sent By albarran Date 2015-10-26 Time 20:11 Rev Time 0.00
Received By pleduc Date   Time   Sent To  
Notes
2015-10-20 15:41:06PASSED WITH PROVISO: "IF BLDG IS SPRINKLERED AND/OR
 ALARMED, SPRINKLERS AND/OR NOTIFICATION APPLIANCES MAY
 BE REQUIRED IN FREEZER. (EVALUATE) GJT
  
 SENT TO MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-23 Cont ID  
Sent By hmoser Date 2015-12-23 Time 08:19 Rev Time 0.00
Received By hmoser Date 2015-12-23 Time 08:19 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-22 Cont ID  
Sent By ccole Date 2015-10-22 Time 10:01 Rev Time 0.00
Received By albarran Date 2015-10-13 Time 15:17 Sent To  
Notes
2015-10-26 20:08:3710/26/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-23 Cont ID  
Sent By hmoser Date 2015-12-23 Time 07:22 Rev Time 0.00
Received By hmoser Date 2015-12-23 Time 07:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By ccole Date 2015-10-22 Time 10:01 Rev Time 0.00
Received By ccole Date 2015-10-22 Time 10:01 Sent To  
Notes
2015-10-22 10:12:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100422
 10/22/15
  
 1) THE COOLER AND FREEZER DIMENSIONS SHOWN IN THE PLAN
 VIEW ARE INCORRECT: PLEASE PROVIDE CORRECT DIMENSIONS.
 2) PROVIDE COMPLETE EQUIPMENT SCHEDULES FOR THE
 CONDENSERS AND EVAPORATOR INDICATING MAKES AND MODELS,
 REFRIGERANT TYPES AND QUANTITIES, PHYSICAL AND
 ELECTRICAL DATA ETC.
 3) PROVIDE WIND LOAD TIE DOWN ENGINEERING FOR THE
 CONDENSERS AND ROOF TOP STANDS- SECTION 301.15 FBC-14
 MECHANICAL.
 4) REFRIGERANT PIPING: INDICATE TYPES AND SIZES OF
 PIPING AND PIPE INSULATIONS, SHOW THE PIPING RUNS, AND
 TRHU PENETRATION FIRESTOPPING DETAILS.
 5) SHOW THE DISCHARGE LOCATIONS OF THE EVAPORATOR
 CONDENSATE LINES.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WALK-IN
 BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  