| Plan Review Stops For Permit 15100419 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2015-11-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-18 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-17 |
Time |
19:55 |
Sent To |
M |
|
| Notes |
| 2015-11-17 20:01:54 | THIS PERMIT WAS APPROVED ON 11/10/15, NO ADDITIONAL | | | ELECTRICAL REVIEW REQUIRED. SENT TO MECHANICAL FOR HIS | | | REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2015-11-10 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-11-10 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-11-10 |
Time |
09:00 |
Sent To |
I |
|
| Notes |
| 2015-11-10 09:29:10 | THE PREVIOUSLY REQUESTED ELECTRICAL DATA HAD BEEN | | | REVIEWED WITH THE MASTER PERMIT (15050045) ALREADY IN | | | FILE NET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-10-26 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-26 |
Time |
20:35 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-26 |
Time |
20:20 |
Sent To |
I |
|
| Notes |
| 2015-10-26 20:35:39 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION | | | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011 | | | EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH | | | EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS | | | APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED. | | | 1. YOU SHALL PROVIDE ELECTRICAL DATA FOR EACH OF THE | | | UNITS BEING INSTALLED. | | | 2. YOU SHALL SUBMIT A FEEDER DIAGRAM AS DESCRIBED IN | | | NEC 215.5. THE SHALL INCLUDE LOAD CALCS AND CONDUCTOR | | | SIZING. | | | THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN | | | MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED | | | FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED | | | TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG | | | WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE, | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY | | | APPRECIATED. | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2015-11-30 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-10-26 |
Time |
20:41 |
Rev Time |
|
| Received By |
andrian |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2015-11-30 16:46:59 | FIRED HAS NOTE 10/10/6/15 THAT REVIEW WAS PASSED AND | | | ALSO STAMPED ON THE PLANS | | 2015-10-20 15:46:12 | PASSED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-18 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-10 |
Time |
08:45 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-22 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-10-13 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2015-11-10 09:31:51 | 11/10/15 MOSER ADVISED ME THAT THE ELECTRICAL DATA | | | REQUESTED IN MY PREVIOUS REVIEW HAD BEEN REVIEWED AS | | | PART OF THE MASTER PERMIT. I WENT BACK INTO FILE-NET TO | | | CONFIRM AND SUBSEQUENTLY PASSED THE ELECTRICAL REVIEW. | | | I DID NOT MOVE THE FILE. | | 2015-10-26 20:41:24 | 10/26/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | | VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2015-11-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-18 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-18 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2015-11-18 11:49:56 | MECHANICAL PROVISOS | | | PERMIT #15100419 | | | 11/18/15 | | | | | | 1) A NON-COMBUSTIBLE BACKING MATERIAL SHALL BE | | | INSTALLED A MINIMUM OF 18 INCHES IN ALL DIRECTIONS | | | AROUND THE TYPE 1 HOODS. | | | 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | | INSTRUCTIONS FOR THE UNIFRAX FYREWAP SHALL BE ON-SITE | | | AT TIME OF INSPECTION. | | | 3) MIAMI-DADE NOA'S OR SITE SPECIFIC ENGINEERING FOR | | | TIE DOWN OF THE EXHAUST AND SUPPLY FANS SHALL BE | | | ON-SITE AT TIME OF INSPECTION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-22 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-22 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2015-10-22 09:27:05 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #15100419 | | | 10/22/15 | | | | | | 1) PLEASE REFER TO SECTION 508.1.1 FBC-14 MECHANICAL | | | AND SHOW COMPLIANCE: MAKEUP AIR TEMPERATURE. | | | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE | | | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F | | | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS | | | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE | | | HVAC SYSTEM. | | | 2) REFER TO SECTION 507.9 AND REVISE THE PLANS TO | | | INDICATE COMPLIANCE: CLEARANCES FOR TYPE I HOOD. | | | A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO | | | COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM). | | | EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM | | | WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS | | | WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES | | | PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND | | | NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD | | | AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA | | | EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL | | | DIRECTIONS FROM THE HOOD. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | FYREWRAP, AND PROVIDE THE UL NUMBER ON THE PLANS FOR | | | THE FIRESTOPPING ASSEMBLY. | | | 4) PROVIDE THE MAKES AND MODELS OF THE EXHAUST AND | | | SUPPLY FANS AND SUBMIT NOA'S AND MANUFACTURER'S | | | SPECIFICATIONS. PLEASE NOTE THAT THE WIND LOAD CALCS ON | | | THE PLANS INDICATE FAN CURBS WHICH ARE NOT DEPICTED ON | | | THE SECTION VIEWS OF THE FANS: PLEASE CLARIFY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|