Plan Review Details - Permit 15100419
Plan Review Stops For Permit 15100419
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-11-17 Cont ID  
Sent By ccole Date 2015-11-18 Time 11:50 Rev Time 0.00
Received By albarran Date 2015-11-17 Time 19:55 Sent To M
Notes
2015-11-17 20:01:54THIS PERMIT WAS APPROVED ON 11/10/15, NO ADDITIONAL
 ELECTRICAL REVIEW REQUIRED. SENT TO MECHANICAL FOR HIS
 REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-10 Cont ID  
Sent By albarran Date 2015-11-10 Time 09:28 Rev Time 0.00
Received By albarran Date 2015-11-10 Time 09:00 Sent To I
Notes
2015-11-10 09:29:10THE PREVIOUSLY REQUESTED ELECTRICAL DATA HAD BEEN
 REVIEWED WITH THE MASTER PERMIT (15050045) ALREADY IN
 FILE NET.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By albarran Date 2015-10-26 Time 20:35 Rev Time 0.00
Received By albarran Date 2015-10-26 Time 20:20 Sent To I
Notes
2015-10-26 20:35:39THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE ???2011
 EDITION OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
 1. YOU SHALL PROVIDE ELECTRICAL DATA FOR EACH OF THE
 UNITS BEING INSTALLED.
 2. YOU SHALL SUBMIT A FEEDER DIAGRAM AS DESCRIBED IN
 NEC 215.5. THE SHALL INCLUDE LOAD CALCS AND CONDUCTOR
 SIZING.
 THE PLANS SHALL BE REVISED TO ADDRESS THE HEREIN
 MENTIONED ITEMS; ONCE CORRECTED SHALL BE RESUBMITTED
 FOR ANOTHER REVIEW. WHEN RESUBMITTING, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE STANDARD CITY RE-SUBMITTAL FORM. PLEASE,
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE SUBMITTAL
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY
 APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-30 Cont ID  
Sent By albarran Date 2015-10-26 Time 20:41 Rev Time  
Received By andrian Date   Time   Sent To  
Notes
2015-11-30 16:46:59FIRED HAS NOTE 10/10/6/15 THAT REVIEW WAS PASSED AND
 ALSO STAMPED ON THE PLANS
2015-10-20 15:46:12PASSED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-18 Cont ID  
Sent By ccole Date 2015-11-18 Time 11:50 Rev Time 0.00
Received By ccole Date 2015-11-10 Time 08:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-22 Cont ID  
Sent By ccole Date 2015-10-22 Time 08:54 Rev Time 0.00
Received By albarran Date 2015-10-13 Time 14:56 Sent To  
Notes
2015-11-10 09:31:5111/10/15 MOSER ADVISED ME THAT THE ELECTRICAL DATA
 REQUESTED IN MY PREVIOUS REVIEW HAD BEEN REVIEWED AS
 PART OF THE MASTER PERMIT. I WENT BACK INTO FILE-NET TO
 CONFIRM AND SUBSEQUENTLY PASSED THE ELECTRICAL REVIEW.
 I DID NOT MOVE THE FILE.
2015-10-26 20:41:2410/26/15 FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-18 Cont ID  
Sent By ccole Date 2015-11-18 Time 11:43 Rev Time 0.00
Received By ccole Date 2015-11-18 Time 11:43 Sent To  
Notes
2015-11-18 11:49:56MECHANICAL PROVISOS
 PERMIT #15100419
 11/18/15
  
 1) A NON-COMBUSTIBLE BACKING MATERIAL SHALL BE
 INSTALLED A MINIMUM OF 18 INCHES IN ALL DIRECTIONS
 AROUND THE TYPE 1 HOODS.
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE UNIFRAX FYREWAP SHALL BE ON-SITE
 AT TIME OF INSPECTION.
 3) MIAMI-DADE NOA'S OR SITE SPECIFIC ENGINEERING FOR
 TIE DOWN OF THE EXHAUST AND SUPPLY FANS SHALL BE
 ON-SITE AT TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By ccole Date 2015-10-22 Time 08:55 Rev Time 0.00
Received By ccole Date 2015-10-22 Time 08:55 Sent To  
Notes
2015-10-22 09:27:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100419
 10/22/15
  
 1) PLEASE REFER TO SECTION 508.1.1 FBC-14 MECHANICAL
 AND SHOW COMPLIANCE: MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
 2) REFER TO SECTION 507.9 AND REVISE THE PLANS TO
 INDICATE COMPLIANCE: CLEARANCES FOR TYPE I HOOD.
 A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO
 COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FYREWRAP, AND PROVIDE THE UL NUMBER ON THE PLANS FOR
 THE FIRESTOPPING ASSEMBLY.
 4) PROVIDE THE MAKES AND MODELS OF THE EXHAUST AND
 SUPPLY FANS AND SUBMIT NOA'S AND MANUFACTURER'S
 SPECIFICATIONS. PLEASE NOTE THAT THE WIND LOAD CALCS ON
 THE PLANS INDICATE FAN CURBS WHICH ARE NOT DEPICTED ON
 THE SECTION VIEWS OF THE FANS: PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  