| 2015-10-23 11:32:39 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 15100372 |
| | W. P. B. PERMIT: 14080811 |
| | ADD: 5300 EAST AVE. |
| | CONT: TRILLIUM CONSTRUCTION |
| | TEL: (561)371-6825 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. OCT. 23/2015 |
| | ACTION: DENIED |
| | |
| | 1) THIS AREA IS KNOWN FOR QUESTIONABLE SOILS BEARING |
| | VALUE. PLEASE PROVIDE A SOILS REPORT WITH THE MINIMUM |
| | SAFE BEARING VALUE. 2010 FBC-B 1803.5.2. QUESTIONABLE |
| | SOILS. |
| | |
| | 2A) SHEET A1 SHOWS A NEW PORTE COCHERE. THIS IS A DROP |
| | OFF AND PICK UP ZONE THAT WILL NEED TO SHOW COMPLIANCE |
| | WITH: 2010 FBC-ACCESSIBILITY SECTION 503.2 VEHICLE |
| | PULL-UP SPACE, 96 INCHES WIDE BY 20 FEET LONG MINIMUM. |
| | |
| | 2B) 2010 FBC-ACCESS AISLE 503.3. |
| | |
| | 2C) 503.3.1 ACCESS AISLES SERVING VEHICLE PULL-UPSPACES |
| | SHALL BE 60 INCHES |
| | |
| | 2D) 503.3.2 LENGTH, ACCESS AISLE SHALL EXTEND THE FULL |
| | LENGTH OF THE VEHICLE PULL-UP SPACES THEY SERVE. |
| | |
| | 2E) MARKING. ACCESS AISLES SHALL BE MARKED SO AS TO |
| | DISCOURAGE PARKING IN THEM. |
| | |
| | 3) SHEET A1 VERSES SHEET D. ON THE D- DEMOLITION SHEET |
| | NOTE # 10 INDICATES THIS DOOR OPENING TO BE REMOVE |
| | EXISITNG ENTRANCE DOOR. SHEET A1 INDICATES THIS OPENING |
| | AS E-2, A EXISITNG OPENING. THE PERMIT ISSUED SET OF |
| | PLANS INDICATES A PAIR OF 3'-0" DOORS FOR THE EXISITNG |
| | OPENING. THIS WILL BE A NEW DOOR AND SIDELIGHT, NO |
| | INFORMATION ON THE SIZE OF THE DOOR, TYPE OF DOOR, |
| | THERE IS NO DOOR SCHEDULE WITH THIS INFORMATION NOR IS |
| | THERE A PRODUCT APPROVAL FOR THIS NEW DOOR AND SIDE |
| | LIGHT. |
| | THIS IS IS ADJACENT TO THE AMBULANCE ENTRANCE DROP OFF |
| | ZONE, WILL THIS DOOR BE OVERSIZED IN WIDTH FOR |
| | STRETCHERS? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 4B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 5) SHEET 2 SERIES AND SHEET 4 THE ELEVATIONS ALL |
| | INDICATE THE USE OF STONE VENEER OF CMU CONSTRUCTION, |
| | THE PLANS INDICATE TO BE INSTALLED TO THE MANUFACTURES |
| | SPECIFICATIONS. |
| | THE PLANS DO NOT PROVIDE DIRECTION IF WHICH DIRECTION |
| | CODE COMPLIANCE IS TO BE ACHIEVED. 1405.6 ANCHORED |
| | MASONRY VENEERS, 1405.7 STONE VENEERS OR 1405.10 |
| | ADHERED MASONRY VENEERS. |
| | |
| | 6) SHEET A2.1 : |
| | |
| | 6A) INDICATES THE USE OF A GLASS CANOPY SYSTEM. PLEASE |
| | PROVIDE COMPLIANCE WITH 2010 FBC-B 2405.2 ALLOWABLE |
| | GLAZING MATERIALS AND LIMITATIONS. PLEASE PROVIDE |
| | DOCUMENTATION OF CODE COMPLIANCE. 107.3.5.5.1.1 MINIMUM |
| | PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS & |
| | STRUCTURES. |
| | |
| | 6B) THE PORTE CACHERE INDICATES THE ROOFING TO BE |
| | BUILT-UP ROOFING WITH TAPPERED INSULATION. PLEASE |
| | PROVIDE COMPLIANCE WITH: |
| | |
| | COMPONENTS & CLADDING. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 6C) SHEET S-1 SHOWS BOTH THE VULT AND VASD PRESSURES. |
| | THE CHART SHOWING THE PRESSURES HAS THE SAME PRESSURES |
| | FOR ZONE 2 AND ZONE 3. |
| | SHEET A2.1 DETAIL A/A-5 INDICATES A CUT SECTION THROUGH |
| | THE CANOPY NO 3 FOOT PARAPET. |
| | SHEET A2.2 DETAIL 6/ A6 SHOWSA CUT SECTION THROUGH THE |
| | AMBULANCE CANOPY, THERE IS NO 3 FOOT PARAPET THERE |
| | EITHER. |
| | PLEASE ADJUST THE ZONE 3 PRESSURES UP SINCE IN NEITHER |
| | CASE CAN YOU TAKE THE REDUCTION IS PRESSURES FOR A 3 |
| | FOOT HIGH PARAPET. |
| | |
| | 7) SHEET A2.2 ALSO INDICATES THE INSTALATION OF A |
| | PRE-ENGINEREED ALUMINUM CANOPY. PLEASE PROVIDE A DESIGN |
| | OF HOW THE PRE-ENGINEERED CANOPY IS TO BE HELD IN |
| | PLACE? |
| | WHAT TYPE OF STRUCTURAL ELEMENTS ARE GOING TO BE |
| | IMPLEMENTED? ADDITIONAL INFORMATION IS R EQUIRED. |
| | 107.3.5.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS & STRUCTURES. |
| | |
| | 8) SHEET A6 DETAIL # 3 SHOWS A CLEAR HEIGTH OF 11'-0" |
| | UNDER THIS CANOPY, IS THIS HIGH ENOUGH CLEAR HEIGTH FOR |
| | A AMBULANCE TO BACK IN UNDER? NOTE A CODE ISSUE, JUST A |
| | QUESTION. |
| | |
| | 9A) SHEET A-5 & S-2 BOTH SHOW THE USE OF DENSGLASS |
| | SHEATHING ON THE NEW FRONT ENTRY FEATURE. PLEASE |
| | PROVIDE THE PRODUCT APPROVAL FOR DENSEGLASS AND |
| | LIMITATIONS OF USE. IF THE PRODUCT APPROVAL HAS MORE |
| | THAN ONE SUB-SYSTEM PLEASE CIRCLE THE SUB-SYSTEM AND |
| | ASSOCIATED PRESSURES. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: (31)(C) PANEL |
| | WALLS. |
| | |
| | 9B) SHEET A5 & S2 SHOW THE USE OF STONE VENEER OVER |
| | DENSE-GLASS SHEATHING. PLEASE PROVIDE HOW THE STONE |
| | VENEER IS TO BE ADHEERED/ ATTACHED TO THE DENSEGLASS |
| | AND DOES EITHER PRODUCT HAVE LIMITATIONS AGAINST SUCH |
| | INSTALATIONS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 9C) PLEASE PROVIDE THE ROOFING PRODUCT APPROVAL FOR THE |
| | TIE IN OF THE ROOFING AND THE FRONT ENTRY FEATURE. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31) (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |