| Plan Review Stops For Permit 15100353 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-13 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-13 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-10-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-10-13 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-10-13 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2015-10-13 10:15:43 | 1ST REVIEW: FBC 2014 BUILDING | | | PERMIT #15100353 | | | 10/13/15 | | | | | | 1) PROVIDE ENGINEERING FOR ROOF TO WALL CONNECTION | | | IMPROVEMENTS AS REQUIRED BY SECTION 708.8 FBC-14 | | | EXISITING BUILDING CODE. REFER TO SECTIONS 708.8.1.1- | | | 708.8.1.7 FOR MATERIALS AND METHODS. | | | 2) PLEASE CORRECT THE EXPOSURE B CATEGORY SELECTION AND | | | FASTENING REQUIREMENTS ON PAGE 13 OF THE CERTAINTEEN | | | PRODUCT APPROVAL. THE HOME IS LOCATED IN AN EXPOSURE D | | | CATEGORY PER SECTION R301.2.1.4 FBC-14. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-11-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2015-11-13 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2015-11-12 |
Time |
10:15 |
Sent To |
B |
|
| Notes |
|
|
|