Plan Review Details - Permit 15100321
Plan Review Stops For Permit 15100321
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-13 Cont ID  
Sent By shill Date 2016-01-13 Time 16:54 Rev Time 0.00
Received By shill Date 2016-01-13 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 16:57 Rev Time 0.00
Received By shill Date 2015-11-21 Time 15:40 Sent To  
Notes
2015-11-21 16:58:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. G101, THE 1 HR CORRIDOR RATING AT THE MAIL ROOM 117
 IS NOT CONTINUOUS, FBC 1018.
  
 2. G101, PROVIDE INFORMATION REGARDING THE COILING FIRE
 DOORS AND OPERATION. THE MAIL ROOM DOES NOT HAVE AN
 EGRESS DOOR, AND THE MEANS OF EGRESS PATH SHOWS THE
 OCCUPANT GOING THROUGH THE COILING FIRE DOOR FROM THE
 ELEVATOR LOBBY 186 TO THE VESTIBLUE 122, FBC 107.
  
 3. A101A SPECIFIES A 20 MINUTE CURTAIN AT THE MAIL ROOM
 AND 45 MINUTE AT THE LIVING ROOM, G101 SPECS A 60
 MINUTE; PLEASE CORRELATE.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-28 Cont ID  
Sent By wjolin Date 2015-10-28 Time 09:17 Rev Time 0.00
Received By wjolin Date 2015-10-28 Time 09:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-01-16 Cont ID  
Sent By tklarge Date 2016-01-16 Time 09:00 Rev Time 0.00
Received By tklarge Date 2016-01-16 Time 08:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-10-31 Cont ID  
Sent By tklarge Date 2015-10-31 Time 11:44 Rev Time 0.00
Received By tklarge Date 2015-10-31 Time 05:29 Sent To  
Notes
2015-10-31 05:30:531) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB
 AMEND. TO FBC SEC. 107.3.5.1.5.
 2) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO
 DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE
 GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING
 SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5, FBC-FUEL GAS SEC. 304.5.
 3) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR
 THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT.
 PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE
 CORRECT TABLE. CLARIFY.
 4) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR
 THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE
 INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE
 THIS IS THE CORRECT TABLE. CLARIFY.
 5) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE
 PRV AT LOCATION "G" ON THE GAS DRAWING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-04 Cont ID  
Sent By cpuell Date 2016-03-04 Time 10:48 Rev Time 0.00
Received By cpuell Date 2016-01-04 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-21 Cont ID  
Sent By shill Date 2015-11-21 Time 16:58 Rev Time 0.00
Received By shill Date 2015-10-14 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By hmoser Date 2015-11-03 Time 10:27 Rev Time 0.00
Received By hmoser Date 2015-11-02 Time 14:06 Sent To  
Notes
2015-11-03 10:27:15REFER TO SECTION 1004.2.1 CARBON MONOXIDE TESTING
 2010 FBC (M)

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-16 Cont ID  
Sent By tklarge Date 2016-01-16 Time 08:41 Rev Time 0.00
Received By tklarge Date 2016-01-16 Time 08:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-31 Cont ID  
Sent By tlarge Date 2015-10-31 Time 07:55 Rev Time 0.00
Received By tklarge Date 2015-10-30 Time 06:46 Sent To  
Notes
2015-10-31 05:11:551) SHT.063-AS109 - ELEVATION DETAIL #3 IS MISLEADING
 AND THE HEIGHT OF THE COUNTER FOR THE SINK IS UNCLEAR
 AS DIMENSIONED ON THE RIGHT SIDE OF THE DETAIL.IT IS
 DIFFICULT TO DETERMINE THE HEIGHT TO THE TOP OF THE
 COUNTER. CLARIFY.
 2) SHT. 146-A400 - THE MINIMUM HEIGHT DIMENSIONS TO THE
 TOP OF THE BACKING FOR THE GRAB BARS DOES NOT COMPLY
 WITH THE FAIR HOUSING ACT. THE MINIMUM HEIGHT TO THE
 TOP OF THE BACKING FOR THE WATER CLOSET SHALL BE 38
 INCHES, NOT 36 INCHES AS SHOWN.
 B) THE MINIMUM HEIGHT DIMENSION TO THE TOP OF THE
 BACKING FOR THE GRAB BARS ON THE CONTROL WALL FOR THE
 TUB AND SHOWER SHALL BE LOCATED AT 38 INCHES, NOT 36
 INCHES AS SHOWN.
 C) THE BOTTOM OF THE BACKING FOR THE GRAB BAR ON THE
 BACK WALL OF THE TUB SHALL BE LOCATED A AMXIMUM OF 6
 INCHES ABOVE THE LIP ( TOP) OF THE TUB.
 3) THE RESPONSE TO COMMENT #8 REFERS TO DRAWING #
 A103B. THERE IS NO SUCH DRAWING IN THIS SUBMITTAL.
 CLARIFY.
 4) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER.WPB
 AMEND. TO FBC SEC. 107.3.5.1.5.
 5) PLEASE SUBMIT THE CALCULATIONS THAT WERE DONE TO
 DETERMINE THE AMOUNT OF COMBUSTION AIR REQUIRED FOR THE
 GAS APPLIANCES AND HOW THAT COMBUSTION AIR IS BEING
 SUPPLIED TO THE AREAS. WPB AMEND. TO FBC SEC. 107.2.1,
 107.3.5.1.5.
 6) THE GAS SIZING TABLE REFERENCED ON SHT.297- P412 FOR
 THE 2 PSI SYSTEM FROM NFPA 54 APPEARS TO BE INCORRECT.
 PLEASE REFER TO TABLE 6.2 (C). I BELIEVE THIS IS THE
 CORRECT TABLE. CLARIFY.
 7) THE GAS SIZING TABLE REFERENCED ON SHT.297-P412 FOR
 THE 0.5 PSI SYSTEM FROM NFPA 54 APPEARS TO BE
 INCORRECT. PLEASE REFER TO TABLE 6.2 ( B ). I BELIEVE
 THIS IS THE CORRECT TABLE. CLARIFY.
 8) SHT. 297-P412 - SHOW THE PIPE SIZE DOWNSTREAM OF THE
 PRV AT LOCATION "G" ON THE GAS DRAWING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2016-06-01 Cont ID  
Sent By shill Date 2016-06-01 Time 07:00 Rev Time 0.00
Received By shill Date 2016-06-01 Time 07:00 Sent To  
Notes
2016-06-01 07:02:066/1 RECEIVED DIGITALLY SIGNED & SEALED SHEETS C102,
 A215, P411, C107 VIA EMAIL; EMAILED TO LEM/CP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-05-26 Cont ID  
Sent By shill Date 2016-05-26 Time 17:42 Rev Time 0.00
Received By shill Date 2016-05-26 Time 17:42 Sent To  
Notes
2016-05-26 17:43:20****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE FOLLOWING SHEETS ARE NOT INCLUDED IN THE
 SIGNATURE DOCUMENT:
 C102, C107 (PHASE 1), A215, P411.
  
 PROVIDE VIA EMAIL.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-05-26 Cont ID  
Sent By shill Date 2016-05-26 Time 16:57 Rev Time 0.00
Received By shill Date 2016-05-26 Time 16:57 Sent To  
Notes
2016-05-26 17:03:01****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE FOLLOWING SHEETS ARE NOT INCLUDED IN THE
 SIGNATURE DOCUMENT:
 C102, C107 (PHASE 1), A215, P411.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-04 Cont ID  
Sent By eschneid Date 2016-03-04 Time 10:20 Rev Time 4.00
Received By eschneid Date 2016-03-03 Time 17:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-17 Cont ID  
Sent By eschneid Date 2015-11-17 Time 15:28 Rev Time 10.00
Received By eschneid Date 2015-11-17 Time 15:28 Sent To  
Notes
2015-11-17 15:29:39FAILED
  
 1) REPEAT COMMENT: ALL ELEVATIONS, SECTIONS, ROOF PLANS
 AND DETAIL SHEETS SHALL BE REVISED TO ACCURATELY
 REFLECT THE LOWER BUILDING HEIGHT TO MEET THE
 REQUIREMENTS OF RESOLUTION NO. 49-13. THE BACK-UP
 GRAPHIC INCLUDED WITH THE ORIGINAL PERMIT INDICATED
 THAT THE SLOPED TOWER ROOF MET THE HEIGHT FOR ONE
 SPECIFIC SECTION OF THE BUILDING; HOWEVER, UPON REVIEW
 OF THE CURRENTLY SUBMITTED SHEETS IT APPEARS THAT THE
 BUILDING EXCEEDS THE HEIGHT EXCEPTION AT SOME OF THE
 AREAS HOUSING THE MECHANICAL EQUIPMENT AND STAIR
 ENCLOSURES AS WELL AS THE PARAPETS. THE ELEVATION
 DIMENSION SHALL BE SHOWN FROM THE AVERAGE ELEVATION OF
 THE FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT
 OF THE AREAS UTILIZING THE HEIGHT EXCEPTION. THIS HAS
 NOT BEEN PROVIDED ON THE ELEVATION, SECTION AND
 STRUCTURAL SHEETS LISTED BELOW (NOTE: ALL SHEETS SHALL
 BE VERIFIED FOR CORRECT HEIGHT DIMENSIONS REGARDLESS OF
 LISTING BY STAFF BELOW. FAILURE TO UPDATE A SHEET THAT
 IS NOT LISTED WILL RESULT IN THE PERMIT NOT PASSING).
  
 A. PHASE ONE ELEVATIONS
  
 SHEET A201A
 SHEET A201B
 SHEET A202
 SHEET A203
 SHEET A204
 SHEET A205
 SHEET A206
 SHEET A207
 SHEET A301 - THE REVISED SHEET DOES NOT SHOW THE
 CORRECT DIMENSION POINTS AND THE BUILDING APPEARS TOO
 TALL.
 SHEET A352 - THE REVISED SHEET DOES NOT SHOW THE
 CORRECT DIMENSION POINTS AND THE BUILDING APPEARS TOO
 TALL.
  
 B. PHASE ONE SECTION DRAWINGS
  
 SHEET A302
 SHEET A303
 SHEET A304
 SHEET A491
 SHEET A492
 SHEET A496
 SHEET A497
  
 C. PHASE TWO ELEVATIONS
  
 SHEET A201A
 SHEET A201B
 SHEET A204
  
 D. PHASE TWO SECTIONS
  
 SHEET A302
 SHEET A304
 SHEET A315
 SHEET A352
 SHEET A493
 SHEET A498
  
 E. STRUCTURAL SHEETS FOR BOTH PHASES SHALL BE UPDATED
 TO SHOW THE FULL HEIGHT DIMENSION FROM GRADE.
  
 F. A NEW SHEET A315 WAS PROVIDED IN ORDER TO SHOW THAT
 THE BUILDING DOES NOT EXCEED THE PERMITTED HEIGHT.
 HOWEVER, THE SHEET A315 IS A DETAIL SHEET REFERENCED ON
 SHEET A303, WHICH WAS NOT REVISED. THE NEW DETAILS ON
 SHEET A315 DO NOT MATCH THE DETAILS SHOWN ON SHEET A303
 FOR THE TOP OF THE PARAPET. ADDITIONALLY, THE
 DIMENSIONS SHOWN PREVIOUSLY ON SHEET A303 SHOW A
 BUILDING WHICH EXCEEDS THE PERMITTED HEIGHT.
  
 G. THE HEIGHT DIMENSIONS ON SHEET A353 WERE NOT
 PROVIDED FROM GRADE ON THE OVERALL SECTION DRAWING.
 NOTE: IF THE FIVE (5) INCHES ABOVE AVERAGE GRADE SHOWN
 ON THE CUT SHEET PROVIDED WITH THE ORIGINAL PERMIT ARE
 ADDED TO THE BUILDING HEIGHT, THEN THE BUILDING EXCEEDS
 THE PERMITTED HEIGHT EXCEPTION.
  
 H. STAFF IS UNABLE TO LOCATE WHERE THE PARAPET RAILING
 DETAIL CALLED OUT ON SHEET A353(8) IS ON THE ELEVATIONS
 OR FULL SECTION DRAWINGS. NO OVERALL HEIGHT DIMENSION
 IS GIVEN TO THE TOP OF THE RAIL.
  
 2) PRIOR TO C.O. THE MINOR PD AMENDMENT TO REFLECT THE
 CHANGES TO THE BICYCLE RACK LOCATION AND THE WALKWAY
 ORIENTATION SHALL BE SUBMITTED TO AND APPROVED BY THE
 PLANNING DIVISION.
  
 3) SHEET C101 SHOWS NOTE REFERENCING AN 18 FOOT CLEAR
 FIRE TRUCK ACCESS ROAD (SOUTH OF POOL WALL). THE
 APPROVED SITE PLAN SHOWS THIS AS A 20 FOOT WIDE
 DRIVEWAY. ALL PLANS SHALL SHOW THE APPROVED 20 FOOT
 DRIVE CONDITION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  
  
  