Plan Review Details - Permit 15100297
Plan Review Stops For Permit 15100297
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 06:30 Sent To  
Notes
2015-10-30 06:45:11BUILDING PROVISO:
 SHEET A2.1
 DOOR # 11 REQUIRES COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE FIGURE 404.2.4.1 MINIMUM 18
 INCHES MANEUVERING CLEARANCES.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-14 Cont ID  
Sent By albarran Date 2015-12-14 Time 17:05 Rev Time 0.00
Received By albarran Date 2015-12-08 Time 16:15 Sent To M
Notes
2015-12-14 17:06:30PER EMAIL DATED 12/11/15 FROM ROY SALLOUM, THIS PERMIT
 WAS ISSUED ON THE CONDITION THAT A DEDICATED SIGN
 OUTLET BE INSTALLED AT EVERY ENTRY AS PER NEC 600.5
2015-12-08 16:28:10AFTER A PHONE CALL I TRIED TO TAKE A QUICK LOOK AT THIS
 RESUB TO GET I T OUT BUT REALIZED THAT A NARRATIVE TO
 THE COMMENTS HAD NOT BEEN PROVIDED SO I CONTINUED WITH
 THE FILE I WAS WORKING ON NOT TO LOSE TRAIN OF THOUGHT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 17:44 Rev Time 0.00
Received By albarran Date 2015-11-04 Time 16:18 Sent To I
Notes
2015-11-04 17:44:58THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2008 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 2010
 EDITION OF THE FBC, (FLORIDA BUILDING CODE) AS
 APPLICABLE AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. FIRE ALARM WORK SHALL BE UNDER A SEPARATE STAND
 ALONE PERMIT.
 2. NEC 600.5 REQUIRES THAT THERE BE A DEDICATED SIGN
 OUTLET AT EVERY PEDESTRIAN ENTRY TO EVERY COMMERCIAL
 SPACE. PROVIDE SIGN JUNCTION OUTLET ABOVE EACH ENTRY
 DOOR.
 3. NEC 210.8(B) REQUIRES THAT EVERY OUTLET IN A KITCHEN
 BE GFI PROTECTED. THIS INCLUDES THE OPEN KITCHEN AREAS
 DESCRIBED ON THE PLANS.
 4. FBC-ENERGY SECTION C402.4.8 REQUIRES THAT ALL
 RECESSED LIGHTING IN THE BLDG. THERMAL ENVELOPE BE IC
 PROTECTED AND SEALED TO LIMIT AIR LEAKAGE BETWEEN THE
 CONDITIONED AND NON-CONDITIONED SPACES.
 5. FBC-B SECTION 1011, THE PATH OF EGRESS TRAVEL TO THE
 EXITS SHALL BE MARKED. A SIGN IS REQUIRED TO INDICATE
 THE CORRIDOR VIA THE VESTIBULE.
 6. NEC 408.4(B) REQUIRES THAT THE LOCATION OF THE POWER
 SOURCE BE MARKED ON ALL SWITCHBOARDS AND PANELBOARDS.
 7. NEC 110.16 REQUIRES THAT ALL ELECTRICAL EQUIPMENT BE
 LABELED WITH THE STANDARD ARC-FLASH HAZARD WARNING
 LABEL.
 8. FBC-E SECTION C405.5.2, PROVIDE A LIGHTING POWER
 ALLOWANCE CHART TO SHOW LIGHTING COMPLIANCE WITH CODE
 REQUIREMENTS.
 9. IF PANEL LA HAS A 200 AMP MAIN CIRCUIT BREAKER, WHAT
 IS THE 200 AMP DISCONNECT REFLECTED ON THE RISER
 DIAGRAM?
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-19 Cont ID  
Sent By pleduc Date 2015-10-19 Time   Rev Time 0.00
Received By pleduc Date 2015-10-19 Time 13:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-04 Cont ID  
Sent By albarran Date 2015-11-04 Time 17:46 Rev Time  
Received By albarran Date 2015-10-08 Time   Sent To  
Notes
2015-11-04 17:47:5011/4/15 FAILED ELECTRICAL AND OTHER TRADE REVIEWS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN
 "C". MA
2015-10-09 09:37:37C20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-15 Cont ID  
Sent By ccole Date 2015-12-15 Time 06:53 Rev Time 0.00
Received By ccole Date 2015-12-15 Time 06:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-22 Cont ID  
Sent By hmoser Date 2015-10-22 Time 06:42 Rev Time 0.00
Received By ccole Date 2015-10-22 Time 06:42 Sent To  
Notes
2015-10-22 06:57:041ST REVIEW: FBC 2010 MECHANICAL
 REVISION # 15100297
 MASTER # 15010300
 10/22/15
  
 1) THE WPB DEVELOPMENT SERVICES BUILDING DIVISION
 REQUIRES SEPARATE PERMITS FOR KITCHEN HOODS AND FIRE
 SUPRESSION SYSTEMS. PLEASE REMOVE SHEET M7.1 & M7.2
 FROM THE REVISED PLAN SETS OR PLACE NOTES ON THE PLAN
 TO CLARIFY THAT THE GREASE DUCT SHOWN IN THE TENANT
 SPACE IS FOR REFERENCE ONLY, AND WILL BE INSTALLED
 UNDER A SEPARATE PERMIT.
 2) SHEET M2.2: PROVIDE ENGINEERED TIE-DOWN DETAILS FOR
 THE NEW CU 1-9 AND AC STAND- SECTION 301.12 FBC-10
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  