| 2015-11-19 13:14:30 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC -5TH EDITION (2014). |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- THE CURRENT CODE IS THE FBC-5TH EDITION (2014) NOT |
| | 2010 FBC. REVISE ALL THE CODES REFERENCED. CHAPTER 553 |
| | F. S. |
| | |
| | 3- THIS BUILDING IS LOCATED IN EXPOSURE "D" NO "C". |
| | REVISE BUILDING EXPOSURE ON THE CODE ANALYSIS |
| | INFORMATION AND REVISE ALL THE WINDOWS AND DOORS DESIGN |
| | PRESSURES SHOWN ON EXTERIOR ELEVATIONS AND TABLES |
| | SUBMITTED. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- THIS IS NO ALTERATION LEVEL 2. THIS IS AND ADDITION. |
| | REVISE CODE ANALYSIS INFORMATION AS REQUIRED. SEC. 507 |
| | OF FBC-EXISTING BUILDING, 5TH EDITION (2014). |
| | |
| | 5- THE CODE ANALYSIS INFORMATION IS NOT LEGIBLE. THERE |
| | IS TOO MUCH BACKGROUND CONTRAST. PROVIDE CLEAR |
| | INFORMATION. SEC. 107.2.1.4 CITY AMENDMENTS. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $20,000. THE |
| | PERMIT FEE BALANCE IS $548.28. |
| | |
| | 7- THE HOUSE DATA INFORMATION SHOWN BY THE FLOOR PLAN |
| | IS INCORRECT. THE NEW FAMILY ROOM ADDITION IS 340 S.F. |
| | NO 240S.F. (15'-0" X 22'-8" = 340). REVISE AS REQUIRED |
| | AND COORDINATE THIS SQUARE FOOTAGE WITH VALUATION ON |
| | ITEM #6 ABOVE. |
| | |
| | 8- ARCHITECT OF RECORD TO PROVIDE SPECIFICATIONS ON |
| | PLAN SHOWING COMPLIANCE WITH THE HEATING REQUIREMENTS |
| | OF SEC. R303.9 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 9- ROOF PLAN: CLARIFY SPACING OF THE 2X8 ROOF JOIST. |
| | DRAWING SHOWS JOIST AT 16" O.C. , WHILE SPECIFICATIONS |
| | ON THE SAME PLAN CALL FOR 2X8 JOIST AT 24" O.C. REVISE |
| | AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 10- REVISE THE WALL SECTION: |
| | A) NEED TO SPECIFY AT LEAST 8D RING SHANK NAILS AS |
| | REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | B) CLARIFY ROOF SHEATHING FASTENING NOTE. CLARIFIED THE |
| | NAILING SPACING. WHAT'S 7 4" O.C. IN ZONE 3?. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | C) SPECIFY ROOF PITCH SHOWING COMPLIANCE WITH SEC. |
| | R905.11 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) NEED TO SHOW COMPLIANCE WITH THE 6" HEIGHT ABOVE |
| | FINISHED GRADE AS REQUIRED BY SEC. R404.1.6 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | ALSO, NEED TO COMPLY WITH THE 12" BELOW FINISHED GRADE |
| | AS REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). NOTE: MAKE SURE SIZE OF FOOTING |
| | SPECIFIED WILL COMPLY WITH BOTH REQUIREMENTS. |
| | |
| | E) SHOW COMPLIANCE WITH THE 6" CLEARANCE FROM WALL |
| | COVERING TO THE FINAL EARTH GRADE FOR TERMITE |
| | INSPECTION AS REQUIRED BY SEC. R318.7 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH |
| | ITEM ABOVE. |
| | |
| | F) NEED TO PROVIDE CROSS VENTILATION AS REQUIRED BY |
| | SEC. R806 OF FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: |
| | 4"X 24" SCREEN VENTS DON'T PROVIDE CROSS VENTILATION. |
| | |
| | G) CLEARLY SPECIFY CONNECTOR THAT FASTEN 2X6 STUDS TO |
| | THE BOTTOM PLATE. SEC. R601.2 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | H) SPECIFY SPECIFY WALL INSULATION. COORDINATE WITH THE |
| | ENERGY CALCULATIONS. SEC. R103.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | I) SPECIFY HOW MUCH EMBEDMENT IS REQUIRED FOR THE 1/2" |
| | BOTTOM PLATES ANCHORS. AND COORDINATE INFORMATION WITH |
| | THE FRAMING DETAIL SHOWN ON THE TOP RIGHT OF SAME |
| | DRAWING (INCLUDING ANCHOR SPACING). SEC. R601.2 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | J) NEED TO SPECIFY THE VAPOR RETARDER AS REQUIRED BY |
| | SEC. R506.2.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | K) NEED TO SPECIFY 7/8" MIN. STUCCO THICKNESS AS |
| | REQUIRED BY TABLE R702.1(1) OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | L) SPECIFICATIONS CALL FOR 2"X6" STUDS @16" O.C. WHERE |
| | IS THE GABLE END WALL MENTIONED ON THE SAME |
| | SPECIFICATION?. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 11- FRAMING DETAIL: CLEARLY SPECIFY ALL STRAPS (TYPE |
| | AND SIZE). SEC. R601.2 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 12- WINDOW MULLION NOA 11-1213.07 SUBMITTED: CLEARLY |
| | IDENTIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| | WITH THE REVISED DESIGN PRESSURES REQUIRED BY ITEM #3 |
| | ABOVE. SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 13- FLAT ROOF NOA 14-0611.01 SUBMITTED: PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL |
| | LIMITATION #7 OF SELECTED ASSEMBLY ON PAGE 27 AND THE |
| | LAST PAGE OF NOA SUBMITTED. NEED THE RAS 117 |
| | CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY |
| | SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | |
| | 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR THE SINGLE HUNG WINDOWS. NOA |
| | 11-1115.08 SUBMITTED EXPIRED ON SEPTEMBER 22, 2015. |
| | NEED TO PROVIDE CURRENT PRODUCT APPROVAL. |
| | |
| | 15- ARCHITECT OF RECORD TO APPROVE IN WRITING ALL THE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 16- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) NEED TO PROVIDE CURRENT FORM. THE CURRENT BUILDING |
| | CODE IN EFFECT IS THE 2014 CODE NOT 2010. FORM 402-2010 |
| | SUBMITTED CAN NOT BE USED. CHAPTER 553 F.S. |
| | |
| | B) REVISE ITEM #5. THE TOTAL AREA IS 340 NOT 240. SEC. |
| | R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) REVISE ITEM #6(B) TO MATCH TABLE 402A ON BACK OF |
| | PAGE SUBMITTED. SEC. R101.5.1.1.1 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | D) ITEM #10 DOESN'T COMPLY WITH TABLE 402A ON BACK OF |
| | PAGE SUBMITTED. NEED R-30 INSULATION. NOTE: R-30 |
| | DOESN'T FIT ON 2X8 JOIST SPECIFIED ON PLANS. |
| | PRESCRIPTIVE FORM 402 SUBMITTED DOESN'T COMPLY. NOTE: |
| | PERFORMANCE FORM 405-2014 MAY BE USED INSTEAD TO COMPLY |
| | WITH THE ENERGY CODE.. |
| | |
| | E) SPECIFY THE SEER/EER VALUE REQUIRED ON ITEM #12(B). |
| | NOTE: PROVIDE MANUFACTURER SPECS SHOWING THE SEER VALUE |
| | SPECIFIED ON THE INSTALLED VALUE ON TABLE 402A ON BACK |
| | OF PAGE SUBMITTED . SEC. R103.2 OF FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |