Plan Review Details - Permit 15100240
Plan Review Stops For Permit 15100240
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-17 Cont ID  
Sent By rmcdouga Date 2016-05-17 Time 13:32 Rev Time 0.00
Received By rmcdouga Date 2016-05-17 Time 13:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-13 Cont ID  
Sent By rmcdouga Date 2016-05-13 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2016-05-13 Time 17:00 Sent To  
Notes
2016-05-13 17:04:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-19 Cont ID  
Sent By rmcdouga Date 2015-10-19 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2015-10-19 Time 17:13 Sent To  
Notes
2015-10-19 18:18:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN DETAIL 13, THE RAFTER HAS BEEN NOTCHED IN SUCH A
 WAY THAT THE SIMPSON H1 CAN NOT BE ATTACHED WITH THE
 REQUIRED (6) 8D X 1-1/2" NAILS. FBC R802.1.9
  
 2) THE RAFTER IN DETAIL 13 HAS BEEN NOTCHED AT THE END
 OF THE MEMBER IN EXCESS OF ONE-FOURTH THE DEPTH OF THE
 MEMBER. FBC R802.1.8.1
  
 3) SPECIFY THE REQUIRED NUMBER OF FASTENERS FOR EACH OF
 THE CONNECTORS, STRAPS, HANGERS, ETC. THAT ARE SHOWN ON
 THE DRAWINGS. NOTE: THE REQUIRED NUMBER OF FASTENERS
 ARE LISTED IN THE SIMPSON CATALOG OR THE FLORIDA
 PRODUCT APPROVAL.
  
 4) SPECIFY THE 6" EXTERIOR WOOD SCREWS ATTACHING THE
 LEDGER FOR THE CEILING JOISTS TO THE EXISTING
 STRUCTURE. THE SCREW SPACING IS SPECIFIED AS 2' O.C.
 THE SCREWS ARE REQUIRED TO ENGAGE THE STRUCTURAL
 FRAMING MEMBERS OF THE EXISTING STRUCTURE. FBC 107.2.1
 & FBC R301.2.1
  
 5) SPECIFY THE SPACING, SIZE AND TYPE OF FASTENERS USED
 TO ATTACH ALL OF THE LEDGERS TO THE STRUCTURE AND ALL
 FRAMING MEMBERS TO PROVIDE A CONTINOUS LOAD PATH FROM
 THE ROOF TO THE FOUNDATION. FBC R301.1
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-05-12 Cont ID  
Sent By destabro Date 2016-05-12 Time 08:27 Rev Time 0.00
Received By destabro Date 2016-05-12 Time 08:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-10-14 Cont ID  
Sent By fmittner Date 2015-10-14 Time 14:14 Rev Time 0.00
Received By fmittner Date 2015-10-14 Time 14:14 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-13 Cont ID  
Sent By rmcdouga Date 2016-05-13 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2016-05-09 Time 14:53 Sent To  
Notes
2016-05-09 14:54:05REVISION ROUTED TO FMITTNER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-19 Cont ID  
Sent By rmcdouga Date 2015-10-19 Time 18:57 Rev Time 0.00
Received By rmcdouga Date 2015-10-07 Time 13:03 Sent To  
Notes
2015-10-08 13:04:22REVISION ROUTED TO HISTORICAL VIA SGRAHAM'S DESK