| 2015-12-03 15:00:15 | 1ST REVIEW: FBC 2014 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | 1. SHOW DEMINTIONS INCLUDING CLEAR FLOOR SPACE OF THE |
| | BATHROOM SHALL COMPLY WITH FBC ACC. SEC 604.2, 604.3.1, |
| | 604.8.1.6 |
| | 2.GRAB BARS SHALL COMPLY WITH FBC ACC. SEC. 609.4 |
| | POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | 3.PLEASE PROVIDE WATER AND SANITARY RISER DIAGRAM.PER |
| | WPB AMEND TO FBC SEC. 107.3.5.1.3(13) |
| | 4. SHOW LOCATION OF TANKLESS WATER HEATER. PER WPB |
| | AMEND.TO FBC 107.2.1 |
| | THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF |
| | 12/9/15; |
| | 5) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR |
| | PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK |
| | BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 6) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK |
| | IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014 |
| | FBC-PLBG. TABLE 403.1. |
| | 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW |
| | FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC. |
| | 107.3.5.1.3. |
| | 8) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK |
| | SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014 |
| | FBC -PLBG.SEC.607.1. |
| | 9)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014 |
| | FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305. |
| | 10) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL |
| | INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP |
| | SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF |
| | WORK. WPB AMEND.TO FBC 107.2.1 |
| | 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 |
| | INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER |
| | CLOSET. 2014 FBC-ACCESS SEC.604.7. |
| | 12) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014 |
| | FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT |
| | ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY. |
| | SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE |
| | DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE |
| | LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | . |