Plan Review Details - Permit 15100183
Plan Review Stops For Permit 15100183
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-16 Cont ID  
Sent By skennedy Date 2015-10-16 Time 16:21 Rev Time 0.00
Received By skennedy Date 2015-10-16 Time 16:21 Sent To  
Notes
2015-10-16 16:26:511ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE PROVIDE THE PRODUCT INFORMATION ON THE CORK
 PRODUCT TO DEMONSTRATE COMPLIANCE WITH THE FOLLOWING
 SECTIONS:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 PLEASE NOTE THAT THE PERMIT WAS ISSUED WITH PROVISO'S
 FOR THE ELECTRICAL AND MECHANICAL DESIGN TO BE AMENDED,
 SEE SHEET A-1.0.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-16 Cont ID  
Sent By skennedy Date 2015-10-16 Time 16:21 Rev Time 0.00
Received By skennedy Date 2015-10-07 Time 13:05 Sent To  
Notes
2015-10-07 13:05:43REVISION ROUTED TO SKENNEDY